1 GNB A division of Exide Technologies Industrial Battery Charger Installation and Operation Manual S47-0079 REV0410.
2 INDEX Page Section Description 3 - Safety Instructions 4 1.0 Installation 4 1.1 Receiving 4 1.2 Location 4 1.3 Line Voltage Adjustments 6 1.4 AC Service Requirements 6 1.5 Connecting AC Service to Charger 7 1.6 Grounding the Charger 7 1.7 Battery Connector and Charger Cable 7 1.
3 WARNING THIS EQUIPMENT CONTAINS LETHAL VOLTAGE LE VELS. INSTALLATION AND SERVICING MUST BE PERFORMED BY QUALIFIED PERSONNEL IMPORTANT: SAVE THESE INSTRUCTIONS! READ AND FOLLOW ALL INSTRUCTIONS BEFORE I NSTALLING, OPERATING, OR SERVICING CHARGER. ANY DEVI ATION CAN CAUSE SERIOUS AND PERMANENT DAMAGE.
4 SECTION 1 - INSTALLATION 1.1. Receiving Immediately upon receipt of the charger, check it agai nst the shipping invoice to ensure the shipment is complete and undamaged. Examine the outside of the packing fo r signs of r ough ha ndling before accep ting the charger f rom the carrier.
5 575 POWER TRANSFORMER SETT ING 480 L2 L2 12 3 4 56 12 3 4 56 L1 L1 12 3 4 1 3 2 4 CONTROL TRANSFORMER CONTROL TRANSFORMER NOTE: When a 120/208/240 AC inpu t unit is set for 120VAC a f use neutral (brass tube ) is required in the Line 2 (neutral) fuse position.
6 TABLE 1-1 Line Amperes Disconnect Switch Fuse Size Amps 000.0 - 02.5 30A 05 003.0 - 04.5 30A 07 005.0 - 07.5 30A 10 008.0 - 11.0 30A 15 011.5 - 15.5 30A 20 016.0 - 18.0 30A 25 018.5 - 22.0 30A 30 022.5 - 27.0 60A 35 027.5 - 32.0 60A 40 032.5 - 40.0 60A 50 040.
7 1.6 Grounding the Charger The charger must be grounded to the A C syste m ground for personnel safety. The green ground wire in the AC input wiring must be connected to the charge r groun d stud (Identified by a green dot and ground symbol).
8 SECTION 2 - OPERA TION The charger utilizes a st andard ferro-resonant tran sformer , which provides isolation from the AC service line and regulates the charging cu rrent. The transformer output is con nected to a full-wave bridge of silicon diodes, which provides DC charging current to the battery .
9 observe any defective segment s or indicators. When t he self-diagnostic is com plete, the charge st art s if no delay is set, and the yellow ‘Charging’ indicator lights. The display sho ws the charging amp s and battery volts per cell along with a message to indicate the cha rger is in phase 1 of the char ge cycle.
10 The 046-0371 control ca n provide an auto-refr esh charge as long as the battery remains connected to the charge r if enabled. If AC power is lost during th e wait period, the cont rol resumes from where it left of f after power is restored . During t he auto-refresh charge, the a mp-hours and cha rge time are added to the origi nal charge.
11 2.1.9 Charge Indications The fo llowing indications are n ot necessarily a result of a charger problem . Th ey are typically caused by external problems such as AC line, poor battery conditi ons, connections , etc.
12 Note: F3 and F4 clear automatically if the battery voltage falls wit hin acceptabl e limits. All indications except F8, F9 and F10 can be cleare d by disconnecting the battery . For F8, F9 and F10, correct the condition that caused the i ndication an d disc onnect the battery to clear the indi cation.
13 2.1.12 Programming To enter p rogramming m ode, press and hold the EDIT butto n and while holding it, press the INFO button. The display sho ws a m essage describing t he current paramet er followed by the param eter‘s value.
14 SECTION 3 - OPTIONAL FEATURES 3.1 Fusible Door-Interlock Switch (JIC Switch) The door interlock switch assembly connects the A C se rvice to the charger’s inp u t fuses for each AC line. The switch is mechanically latche d by the door so t hat it must be in the OFF position before the door can be opened.
15 4.3. AC fuse blows. POSSIBLE CAUSE A. Incorrect fuse rating. B. Incorrect AC voltage. C. Fuse Block holding clips loose. D. Shorted transformer winding. 4.4. DC fuse blows. POSSIBLE CAUSE A. Reversed battery conn ecto r. B. Incorrect fuse rating. C.
16 SECTION 5 – REPLACEABLE PARTS 5.1 Ordering Information The following information must be supp lied when orderi ng a repl acement pa rt from your service agent in order to ensure that the corre ct part is supplied: A. Model or Spec. number of char ger (Located on ch arger data plate) B.
17 5.3 Spare Parts List Part Number Description Condensers 008-0002 2 MFD 440 Volt 008-0004 4 MFD 440 Volt 008-0006 6 MFD 440 Volt 008-0008 8 MFD 440 Volt 008-0010 10 MFD 440 Volt 008-0012 12.
18 Three Phase Charger Schematic # 02 -400.
19 Single Phase Charger Schematic # 02 -416.
DWG. NO. WIRING DIAGRAM: DR. DATE: CHK: 12 11 10 987654321 2 CMP 3 PHASE, 4 TRANS, 4 GANG, STANDARD CONFIGURATION. (C1,C2,C3 AND C4) TYPICAL CIRCUIT 02-490 02-490 NOTES: * WATERING NOT AVAILABLE ON ALL CONTROLS.
デバイスExide S47-0079の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Exide S47-0079をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはExide S47-0079の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Exide S47-0079の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Exide S47-0079で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Exide S47-0079を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はExide S47-0079の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Exide S47-0079に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちExide S47-0079デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。