INST ALLA TION INSTRUCTIONS 62-0311—1 3 TB6575/TB8575 Digital F an Coil Thermostats PRODUCT DESCRIPTION The TB6575 and TB8575 are a fa mily of Digi tal F an Co il therm ostats for residential and comm ercial applications such as hotels, condomin iums, school classrooms, etc.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 2 SPECIFICATIONS Supply V olta ges: TB6575A10 16 and TB65 75B1000: • 120 V ac ±10 % at 50/60Hz • 240 V ac -15% to +10% at 50 /60Hz TB6575C.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 3 62-0311—13 T able 2. Ap plication s and Features Fig. 1. Dime nsions in in ches (mm). INSTALLATION When Installing this Pr oduct… 1. Read these inst ructions ca refully . Failure to follo w them could da mage the pro duct or caus e a hazard- ous condition.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 4 adaptor plate (50033847 -001) can be used wit h a 4 x 4 in . or a vert ical junction box for which mounting screws are supplied (see F ig. 3 on pa ge 5). 1. Prepare th e supply wires : a. Mounting on a 4 x 4 in.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 5 62-0311—13 Fig. 3. Mount ing sub-base and thermostat using the adap tor plate (50 033847-001) . T e rminal Wiring T able 3 provides the ter minal wir ing for each model an d application.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 6 T erminal Identifier LW / Y n / a i Gl Gm Gh N Rs a Sc b SB c Ps d Fly lead wire color Black Orange Red Blue Brown White None e 2 pipes; Heat.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 7 62-0311—13 Accessory Wiring Remote Pipe Sensor Wiring The remote pipe sensor is us ed for 2 pipes auto a nd 2 pipes heat and cool with auxi liar y heat change ov er . The pipe sensor will sense the temperatur e in the pipes to tell the ther mostat when the system is set for Heat or Cool.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 8 Thermostat Wiring Diagrams The figures in this section illust rate typical wiring for : • TB6575A1016,TB65 75B1000 and TB6575C1016 fan coil ther mostats, which are 120/24 0/277 V ac p owered.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 9 62-0311—13 . Fig. 13. Wirin g diagram wh en missi ng a wire for electromechanical r etrofit (120/240/ 277 V ac shown). 24 V ac Wiring Diagrams (TB8575) For the TB8575A1016 model, a 24 V ac C lass 2 NEMA rated transformer must be used.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 10 Fig. 19. T wo pipes (Heat or Cool) wi th A uxiliary Heat and Manual Ch angeover wir ing diagram (24 V a c shown ). . Fig. 20. Wirin g diagram wh en missi ng a wire for electr omechani cal retr ofit (24 V ac shown).
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 11 62-0311—13 Fig. 23. LCD displ ay sho wing default screen. Po w e r - u p At power-up, the thermostat’s LCD shows all display segments fo r two seco nds, en ters a sel f-test mo de f or a fe w seconds, and then d isplays the current room temperature (d efault screen), as shown in F ig.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 12 2 System T ype 0 Heat only 1 Cool only 2 T wo pipes: Heat or Cool; Manual Changeover 3 T wo pipes: Heat or Coo l; Seasona l Changeo ver (req.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 13 62-0311—13 10 Control Meth od for 4-Pipe A uto Changeover 1 Singl e Setpoi nt (Defaul t) Uses switching diff erential to change b etween heating and c.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 14 Installer T est (IT) Mode T o enter Installer T est Mode: • Press and hold both the Up arrow button and th e Down Ar ro w butt on for th ree (3) second s. This disp la ys all segm ents of th e LCD scre en on the LCD .
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 15 62-0311—13 3. After the desire d value displays , press the Syst em button to store your value selection and dis play the next IT code. NO TE: Ex iting Insta ller T est Mode is the same as the method for en tering t est mode , Fig.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 16 Fig. 26. Auto Chang eover with Heat/Coo l Setpoints deadband illu stration. For 4 pipe applications with Auto Changeover and a single setpoint, when Economy Setback is enabled, the setpoint will rev er t to a dual he at/cool setpoint approach.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 17 62-0311—13 T able 7. Log ic for 2 Pipes with Auxiliar y Heat If pipe temperatu re is between the two threshold values after the 5 m inute purge occur s, the therm ostat will activ ate a second 5 min ute purge to doub le check the wate r temper ature.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 18 T ROUBLESHOOTING T able 8 provides troubleshooting in formation. T able 8. T roubl eshooting. Symptom P ossible Cause Action Display does not come on. Thermostat is not being pow ered. For TB6575A/B/C, check f o r 120/240 /277 V ac b etween L and N.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 19 62-0311—13 Cooling does no t turn on (Cool On is so lid in the display). Cooling equipm ent failure. For TB6575A/ B/C: 1. Check f or 120/240/2 77 V ac at t he equipment be tween power and common , (terminals L an d N).
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS Automation and Control Solutions Honeywell Intern ational Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.hone ywell.com ® U.S . Registered T rademark © 2013 Honey well International In c. 62-0311—13 KK Re v .
デバイスHoneywell TB6575の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell TB6575をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell TB6575の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell TB6575の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell TB6575で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell TB6575を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell TB6575の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell TB6575に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell TB6575デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。