PRODUCT DAT A Put UPC Code Here 68-0291-03 ® Automatic Ignition Systems ANSI Z21.20 Y8610U Intermittent Pilot Retrofit Kit GENERAL The Y8610U is a complete kit for conver ting conventional standing pilot systems to inter mit tent pilot systems. It is used on gas-fired atmospheric furnaces, boilers, and heating appliances.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 2 ORDERING INFORMATION When purchasing replacement and modernizat io n products from your TRADELINE® whol esaler or distributor , refer to the TRADELINE® Catalog or price sheets for complete ordering number .
Y8610U INTERMITTENT PILO T RETROFIT KIT 3 68-0291—0 3 T ransformer Sizing: Add current ratings of Y8610, vent damper , and any other control system components. Multiply this total by 24V to determine the transformer V A requirement. Mounting: Mounts in any position except with terminals up.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 4 Fig. 1. Y8610U retrofit kit components. Fig. 2. S86 10U module d imensions i n inches (m m). VR8304 S8610U INTERMITTENT PILOT MODULE WITH WIRING HARNESS 392431 IGNITER- SENSOR ASSEMBL Y ALSO INCLUDED: • 394800-30 IGNITION CABLE (30 IN.
Y8610U INTERMITTENT PILO T RETROFIT KIT 5 68-0291—0 3 Fig. 3. VR8304M mo unting dimensions in inches (mm). Fig. 4. VR8 204A mounting dimensions in inc hes (mm).
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 6 Fig. 5. 392431 Igniter-sensor mounting dimensions in inches. (mm). PLANNING THE INST ALLATION WARNING Fire or Explosio n Hazard. Can cause severe in jury , death or prop erty damage. 1. Plan the installation as outlined below .
Y8610U INTERMITTENT PILO T RETROFIT KIT 7 68-0291—0 3 INST ALLATION When Inst alling this Product… 1. Read these instructions carefully . Failure to fol low them could damage the product o r cause a hazardo us condi- tion.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 8 5. Applicable only to warm air heating appliances. Inspect heat exchangers for cracks, openings or excessive cor- rosion. 6. Applicable only to boilers. Inspect for evidence of water or combustion product leaks.
Y8610U INTERMITTENT PILO T RETROFIT KIT 9 68-0291—0 3 Remove Thermocouple Unscrew or snap the thermocoup le out of the pilot burner and discard. See Fig. 7. NOTE: It could be necessary to pull out the main burner for access to the pilot burner . Do not move or relocate the pilot burner .
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 10 Inst all the Gas Control WARNING FIRE OR EXPLOSION HAZARDCAN CAUSE PROPERTY DAMAGE, SEVERE INJUR Y , OR DEA TH. Follow the se warnings exact ly: 1. Do not bend the pilot gas tubing at the gas control or at the pilot burner after the compression fitting is tightened.
Y8610U INTERMITTENT PILO T RETROFIT KIT 11 68-0291—0 3 Fig. 1 1. Install sediment trap. Mount Gas Control 1. The gas control can be mounted from 0 to 90 degrees, in any direction inclu ding vertically , from the u pright posi- tion of the gas co ntrol knob.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 12 Locate and Mount the S8610U Intermittent Pilot Module Location Identify a mounting lo cation for the S86 10U ignition contro l. The mounting location must provide: — Good, clear access to the field wiring terminals.
Y8610U INTERMITTENT PILO T RETROFIT KIT 13 68-0291—0 3 Connect Ignition Cable Use the provided ignition cable to connect the S8610U module to the pilot burne r . Be sure the ignition cable is not expo sed to high temperature while the appliance is operating .
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 14 Fig. 16. Y8610U connection s in a heating system with an atmos pheric burner and no ven t damper . SETTINGS DIP Switch (S1) Settings The factory default settings for the S8610U are recommended for retrofit applications.
Y8610U INTERMITTENT PILO T RETROFIT KIT 15 68-0291—0 3 Jumper This jumper (labeled P4) is used to lock the operating sequence selected by the DIP sw itch settings.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 16 7. Perform a gas leak test in the appliance includ ing both the inlet and outlet sides of the gas control.
Y8610U INTERMITTENT PILO T RETROFIT KIT 17 68-0291—0 3 T R OUBLESHOOTING WARNING Fire, Explosion, or Electrical Shock Hazard. Can cause severe in jury , death or prop erty damage. Do not attempt to modify the physical or electrical characteristics of this device in any way .
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 18 STEP 4: Check Pilot and Main Burner Lightoff. 1. Set the thermostat to “Call for Heat.” 2. W atch the pilot burner du ring the ignition sequence. See if one of the followin g occurs: a. Ignition spark continues after the pi lot is lit.
Y8610U INTERMITTENT PILO T RETROFIT KIT 19 68-0291—0 3 LED St atus and T roubleshooting The ignition control module has two LEDs; on e for flame sensing and one for system status: Fig. 21. Lo cation of LE Ds. • Flame Status and Sense LED — Indicate s system operation status and senses error conditions.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 20 a Flash Code Descriptions: - Flash Fast: rapi d blinking. - Heartbeat: Constant ½-second bright, ½-second dim cycles. - 4-second solid on pulse followed by “x” 1-second fla shes indicates flame current to the neare st μ A.
Y8610U INTERMITTENT PILO T RETROFIT KIT 21 68-0291—0 3 T roubleshooting Guide Refer to the Fig. 22 for troub leshooting the S8610U control module. Fig.
Y8610U INTERMITTENT PI LOT RETROFIT KIT 68-0291—0 3 22 ANSI STANDARDS Exhibit A Recommended Procedure for Safety Inspection of an Existing Appliance Inst allation as a Preliminary S tep to Applying .
Y8610U INTERMITTENT PILO T RETROFIT KIT 23 68-0291—0 3 Exhibit B Procedure for Inst alling Automatic Intermittent Pilot Systems Prior to beginning this procedure, a preliminary exami nation of the a.
Y8610U INTERMITTENT PI LOT RETROFIT KIT Automation and Control Solutions Honeywell Internationa l Inc. 1985 Douglas Drive North Golden Valley, MN 55422 Honeywell Limited-Honeywell Limitée 35 Dynamic Dr ive Toronto, Ontario M1V 4Z9 customer.honeywell.
デバイスHoneywell Y8610Uの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell Y8610Uをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell Y8610Uの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell Y8610Uの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell Y8610Uで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell Y8610Uを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell Y8610Uの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell Y8610Uに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell Y8610Uデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。