Industrial/Commercial/Residential Generator Sets Models: 20 - - 2800 kW TP-5700 7/93d Installation.
Engine exhaust fr om t his produc t cont ains chemic als known t o the S tat e of California t o cause canc er , birt h defec ts , or ot her reproduc t ive harm. W ARNING California Propos ition 65 Product Identifica tion I nformat ion Produc t ident if icat ion number s det ermine serv ice part s.
T able of Contents TP-5700 7/93 T able of Contents Product Identification Information Inside front cover ............................................ Safety Precautions and Instructions I ........................................................ Introduction i .
T able of Contents, continued TP-5700 7/93 T able of Contents Section 7 Electrical Requirements 35 .......................................................... 7.1 Batteries 35 ............................................................. 7.2 Electrical Connections 36 .
TP-5700 7/93 I Safety Precautions and Instructions Safety Precautions and Instructions IMPORT ANT SAFETY INSTRUCTIONS . Electromechanical equipment, including generator sets, transfer switches, switchgear , and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained.
TP-5700 7/93 II Safety Precautions and Instructions Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance.
TP-5700 7/93 III Safety Precautions and Instructions The fuel system. Explosive fuel vapors can cause severe injury or death. V aporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels i naw e l l - v e n t i l a t e da r e aa w a yf r o m spark-producing equipment and out of the reach of children.
TP-5700 7/93 IV Safety Precautions and Instructions Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury , or death. If the generator set is used for standby power , install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply .
TP-5700 7/93 V Safety Precautions and Instructions Servicing the transfer switch controls and accessories within the enclosure. Hazardous voltage can cause severe injury or death.
TP-5700 7/93 VI Safety Precautions and Instructions Notice NOTICE This generator set has been rewired from its nameplate voltage to 246242 NOTICE V oltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate.
TP-5700 7/93 i Introduction Introduction This manual provides installation instructions for 20 - -2800 kW generator sets. Operation manuals and wiring diagram manuals are available separately . x:in:001:001 Information in this publication represents data available at the time of print.
.
TP-5700 7/93 1 Section 1 General Section 1 General Industrial power systems give years of dependable service if installed using the guidelines provided in this manual and in applicable codes. Incorrect installation can cause continuing problems. Figure 1-1 illustrates a typical installation.
TP-5700 7/93 2 Section 1 General TP-5700-1 1. Exhaust thimble (for wall or ceiling) 2. Silencer 3. Supports 4. Flexible sections 5. Duct work for cooling air outlet 6. Mounting base 7. Controller 8. Electrical conduit 9 . W a t e rt r a pw i t hd r a i n 10.
TP-5700 7/93 3 Section 2 Load and Transport Section 2 Load a nd T ransport T o ensure personal safety while preventing damage to the product, we strongly recommend the following guidelines be observed when loading and transporting standby generator sets.
TP-5700 7/93 4 Section 2 Load and Transport D A four-point lifting method is necessary to lift the generator set. T o maintain generator balance during lifting, the lifting apparatus must utilize the four skid lifting holes mentioned in the previous paragraph.
TP-5700 7/93 5 Section 2 Load and Transport D Do not attach lifting hooks to outside reinforcing plate on skid. Attach lifting hooks to skid exactly as shown in Figure 2-4. This method utilizes the strongest portion of the mounting skid and also prevents the lifting hooks from slipping.
TP-5700 7/93 6 Section 2 Load and Transport Notes.
TP-5700 7/93 7 Section 3 Location Section 3 Location 3.1 Location Factors Location is the key to a proper installation. The following sections will deal with the factors to consider in a proper installation. Before final plans are made for locating a generator set, the following questions should be raised concerning the set and the proposed site.
TP-5700 7/93 8 Section 3 Location 3.3 Mounting T ypical mounting surface details and dimensions are shown in Figure 3-1. The recommended mounting surface is a concrete mounting pad. This must be a level surface as shown in Figure 3-2, or raised pads as shown in Figure 3-3 and Figure 3-4.
TP-5700 7/93 9 Section 3 Location The composition of the mounting pad should follow standard practice for the required loading. Common specifications call for 2500-3000 psi (176-21 1 kg/cm 2 ) concrete reinforced with eight-gauge wire mesh or number 6 reinforcing bars on 12-inch (30-cm) centers.
TP-5700 7/93 10 Section 3 Location Notes.
TP-5700 7/93 11 Section 4 Air Requirements Section 4 Air Requirements 4.1 General An ample flow of clean, cool air is required to support combustion and dissipate heat. Approximately 70% of the heat value of fuel consumed by an engine will be rejected to the cooling system and exhaust.
TP-5700 7/93 12 Section 4 Air Requirements In many installations it may be desirable to install louvers in the inlet and outlet openings. Louvers may be either stationary or movable. In areas of great temperature variation, it is often best to install movable louvers that can be thermostatically adjusted to regulate air flow and room temperature.
TP-5700 7/93 13 Section 4 Air Requirements 4.3 Forced Air With the forced-air system, cooling air is drawn in through the front of the engine, circulated around finned areas of the cylinder block and head, then ejected toward the rear or generator end of the set.
TP-5700 7/93 14 Section 4 Air Requirements 4.4 Air - V ac Cooling System The air flow direction with the Air-V ac system is the opposite of the conventional forced air cooling system. Use the Air-V ac system in confined areas since it includes a blower scroll which easily connects to the ductwork.
TP-5700 7/93 15 Section 4 Air Requirements 4.5 Air V ent The air vent system is used on some air-cooled gas and has been used on some diesel models. It includes special ductwork which directs the flow of heated air to the outlet at the top or side of t he engine.
TP-5700 7/93 16 Section 4 Air Requirements 4.6 Liquid -Cooled Models The three most common liquid cooling systems used for generator sets are unit-mounted radiator , city water , and remote radiator cooling. Since each involves somewhat different installation considerations, they will be discussed separately .
TP-5700 7/93 17 Section 4 Air Requirements The connection from the radiator duct flange to the ductwork should be heavy canvas, silicone or similar flexible material to prevent noise and vibration transmission. Sheet metal ductwork should be self-supporting.
TP-5700 7/93 18 Section 4 Air Requirements The engine water pump can be used to circulate water through the remote radiator providing that the vertical distance from the engine water pump does not exceed the engine manufacturer ’s recommendations. The allowable static head may range from 17-50 feet (5.
TP-5700 7/93 19 Section 4 Air Requirements 7 1 2 3 4 6 5 1. V entilation fan (for heat rejected from exhaust and engine) 2. City water in 3. Flexible section 4. Manual shutoff valve 5. Heated water into drain 6. Solenoid valve 7. Heat Exchanger Figure 4-1 1 Installation Using City Water Cooling System with Heat Exchanger 1 2 3 4 5 6 1.
TP-5700 7/93 20 Section 4 Air Requirements 4.1 1 Block Heaters Block heaters are recommended on all standby applications where the generator is subject to temperatures below 60 ° F( 1 6 ° C) and are available as installed accessories on all generator sets.
TP-5700 7/93 21 Section 5 Exhaust System Section 5 Exhaust System Proper installation of the exhaust system is essential to obtain satisfactory performance from a generator set. The most important factor is that the installed system must not exceed the engine manufacturer ’s maximum exhaust back pressure limit.
TP-5700 7/93 22 Section 5 Exhaust System 5.1 Flexible Section A section of flexible exhaust line should be installed within 2 feet (51 mm) of the engine exhaust outlet. This limits the stress on the engine exhaust manifold or turbocharger resulting from engine motion on its vibration mounts and temperature-induced changes in pipe dimensions.
TP-5700 7/93 23 Section 5 Exhaust System 5.4 Double -Sleeve Thimbles If the exhaust pipe should need to pass through a wall or roof, an exhaust thimble must be used to prevent exhaust pipe heat from being transmitted to the combustible material.
TP-5700 7/93 24 Section 5 Exhaust System Notes.
TP-5700 7/93 25 Section 6 Fuel Systems Section 6 Fuel Systems When planning an installation, check state and local regulations regarding fuel storage and handling.
TP-5700 7/93 26 Section 6 Fuel Systems 1 2 3 4 TP-5700-6 1. Generator set skid 2. Side view 3. Subbase fuel tank 4. End view Figure 6-2 Subbase Fuel T ank 6.2 Main Fuel T ank All main tanks should be vented so that air and other gases can escape to the atmosphere.
TP-5700 7/93 27 Section 6 Fuel Systems Flexible connections must be used wherever there may be relative motion between piping and supplied equipment. Always use flexible lines at the engine connections. These should be a minimum of six inches (15.3 cm) long.
TP-5700 7/93 28 Section 6 Fuel Systems 6.5 Auxiliary Fuel Pumps Engine-driven fuel transfer pumps usually develop a maximum of 7 psi (48 kPa) pressure and have a lift capacity of 4-6 feet (1.
TP-5700 7/93 29 Section 6 Fuel Systems 6.6 Gasoline Fuel Systems Due to code restrictions which do not allow storage of more than one gallon (3.8 L) of gasoline inside a building, gasoline fuel systems are usually limited to housed generator sets installed outdoors or portable trailer-mounted units.
TP-5700 7/93 30 Section 6 Fuel Systems 6.7 Natural or LP Gas Fuel Systems Natural and LP (liquified petroleum) gas fuel systems should be designed and installed in accordance with the requirements of NFP A 54, National Fuel Gas Code, and all applicable local codes.
TP-5700 7/93 31 Section 6 Fuel Systems 1 2 3 5 TP-5700-6 4 91 0 87 6 1. Carburetor 2. Load adjustment valve 3. Converter (vaporizer) 4. Solenoid valve 5. LP gas filter (supplied by gas supplier or installer) 6. LP gas supply 7. Natural gas supply 8. Primary regulator (supplied by gas supplier or installer) 9.
TP-5700 7/93 32 Section 6 Fuel Systems 6.8 Flexible Connector An approved flexible connector should always be used between stationary gas piping and the engine-mounted fuel system components. It should be at least six inches (15.3 cm) long or as recommended by the generator supplier based upon engine specifications.
TP-5700 7/93 33 Section 6 Fuel Systems 6.1 1 LP Gas Fuel Characteristics LP gas is supplied as a liquid in pressure tanks. It is easily adaptable to stationary applications where complete independence of an outside fuel supply is required.
TP-5700 7/93 34 Section 6 Fuel Systems 6.15 Natural Gas Natural gas is in a vapor state as supplied from the utility . This fuel system, therefore, consists of the same basic components and is used in the same general sequence as LP gas systems.
TP-5700 7/93 35 Section 7 Electrical Requirements Section 7 Electrical Requirements Before installing the generator set, provide for electrical connections through conduit to the transfer switch and other accessories for the generator set. Carefully install the selected generator set accessories.
TP-5700 7/93 36 Section 7 Electrical Requirements 7.2 Electrical Connections Several electrical connections must be made between the generator set and other components of the system for proper operation. Because of the large number of accessories and possible combinations, this manual does not address specific applications.
TP-5700 7/93 37 Section 7 Electrical Requirements 7.4 T erminal Connector T orque Use the torque values shown in Figure 7-4 or Figure 7-5 for terminal connectors. Refer to UL-486A, UL-486B, and UL-486E for information on terminal connectors for aluminum and/or copper conductors.
TP-5700 7/93 38 Section 7 Electrical Requirements 7.5 Automatic T ransfer Switches A typical standby system has at least one automatic transfer switch connected to the generator set output to automatically transfer the electrical load to the generator set if the normal source fails.
TP-5700 7/93 39 Section 7 Electrical Requirements 7.9 Remote Emergency Stop Switch The emergency stop switch allows immediate shutdown of the generator from a remote location. If the emergency stop switch is activated, the emergency stop lamp on the generator controller lights and the unit shuts down immediately .
TP-5700 7/93 40 Section 7 Electrical Requirements TP-5700 7/93 GENERA TOR JUNCTION BOX SAFEGUARD CIRCUIT BREAKER TERMINAL STRIP (IN JUNCTION BOX) RUN RELA Y KIT BA TTERY HEA TER KIT GENERA TOR HEA TER.
TP-5700 7/93 Appendix A-1 Appendix A Abbreviations The following list contains abbreviations that may appear in this publication. A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC analog to digital converter adj.
TP-5700 7/93 A-2 Appendix kg kilogram kg/cm 2 kilograms per square centimeter kgm kilogram-meter kg/m 3 kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, k Ω kilo-ohm kPa kilop.
.
E 1993, 2001, 2003 by Kohler Co. All rights reserved. TP-5700 7/93d KOHLER CO. Kohler , Wisconsin 53044 Phone 920-565-3381, Web site www .kohlergenerators.com Fax 920-459-1646 (U.S.A. Sales), Fax 920-459-1614 (International) For the nearest sales and service outlet in U.
デバイスKohler Generator Sets 20--2800 kWの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Kohler Generator Sets 20--2800 kWをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはKohler Generator Sets 20--2800 kWの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Kohler Generator Sets 20--2800 kWの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Kohler Generator Sets 20--2800 kWで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Kohler Generator Sets 20--2800 kWを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はKohler Generator Sets 20--2800 kWの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Kohler Generator Sets 20--2800 kWに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちKohler Generator Sets 20--2800 kWデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。