Lifebreathメーカー200MAX RXの使用説明書/サービス説明書
ページ先へ移動 of 36
* LEA VE FOR HOMEO WNER NOTE: Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice.
2 Introduction ................................................................2 Warranty ....................................................................2 ERV Questions & Answers ........................................3 Climate Map .........
3 What is the difference between an HRV and an ERV? The core in an HRV (Heat Recovery Ventilator) trans- fers heat from one air stream to the other. This is called sensible heat.
4.
5 Removably Heat Recovery Core Drain Pan Drain spout FRONT TOP knockout for side mounting of EXHAUST return port 6" round collar converted to oval minimum 18 inches (459 mm) required for service access Threaded inserts (4) at corners SUPPLY Fresh air from outside 5" round collar SUPPLY Fresh air to building 6" round (conv.
6 ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor.
7 ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS High effficiency electronic comutated ECM motor for maximum energy sav- ings.
8 ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor.
9 BALANCING DAMPER 33 5/8" (850mm) ST ALE AIR FROM INSIDE FRESH AIR FROM OUTSIDE ST ALE AIR TO OUTSIDE FRESH AIR TO INSIDE 14 3/4" (375) 19" (483) *All Duct Connections 6" (150mm) CONDENSATE DRAINS FILTERS BLOWERS *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
10 14 3/4" (375) 19" (483) *All Duct Connections 6" (150mm) *NOTE: F ront clearance of 25 inches (635 mm) is recommended for servicing unit.
11 ENGINEERING DATA THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service. MOTORS AND BLOWERS Each air stream has one centrifugal blower driven by a common PSC motor.
12 49 " (1245) ST ALE AIR TO OUTSIDE FRESH AIR TO INSIDE 14 3/4" (375) 19" (483) Ports 7" (178 mm) CONDENSATE DRAINS BLOWERS *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
13 49 " (1245) ST ALE AIR TO OUTSIDE FRESH AIR TO INSIDE 14 3/4" (375) 19" (483) Ports 7" (178 mm) CONDENSATE DRAINS BLOWERS *NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
14 OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min. (3 wire) 99-109 Air Sentry™ Air Quality Monitor designed to accept remote- ly mounted Control Pad 99-186 Weatherhoods , Two - 6” (150mm) c/w 1/4” (6mm) mesh screen WARRANTY Units carry a 5 year warranty on the energy recovery core and replace- ment parts.
15 ST ALE AIR TO OUTSIDE ST ALE AIR FROM HOUSE FRESH AIR TO INSIDE 14 3 / 4 " (375) 19" (483) * All Duct Connections 6"(150mm) FIL TERS *NOTE: F ront clearance of 25 inches (635 mm) is recommended for servicing unit.
16 Operating the ControlAir 15 Plugging in the HRV/ERV energizes the unit. A self test function will be performed every time the HRV/ERV is energized (refer to “Self Test” for more details). After the self test has completed successfully the HRV/ERV will default to Speed 1.
17 Press and hold the fan selection button on the Control Pad. After 5 seconds the control will begin to cycle each mode holding each for 2 seconds. Release the button when the desired mode of operation is reached. Modes of Operation LED Indication OFF No LED’ s illuminated HR V/ER V is off, no controls will initiate operation.
18 The Control Pad Mounted in the Control Module YEL GRN ORG RED BLK Speed Indicator Lights Speed 5 - flashing yello w Speed 4 - solid yello w Speed 3 - solid yello w Speed 2 - solid yello w Speed 1 - solid yello w Mode Indicator Light OFF ...........
19 AIR SENTRY™ Air Quality Sensor PART NO. 99-109 Connects to RED, GREEN and YELLOW terminals. Use a minimum of three lead 18 gauge low voltage wire.
20 Some models have a built-in dehumidistat (an optional remote wall mount dehumidistat can be installed, see Optional Remote Controls), to control harmful, excess humidity during the heating season . The dehumidis- tat operates in % of RH (relative humidity) with 80 being high and 20 being low.
21 95 MAX Port Specifications The 95 Max Heat Recovery Ventilator (HRV) has been designed to allow the installer to choose between two possible positions on the cabinet for the INDOOR EXHAUST (return from building) port. Illustrations in this manual show standard (side mounted) port loca- tion.
22 Location The HRV/ERV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV/ERV would be located in the mechanical room or an area close to the outside wall where the weatherhoods will be mounted.
23 A well designed and installed ducting system will allow theHRV/ERV to operate at its maximum efficiency. Always try to keep duct runs as short and straight as possible.
24 In homes without a forced air furnace, fresh air should be supplied to all bedrooms and living areas, exclud- ing bathrooms, kitchen and utility areas. It should be supplied from high wall or ceiling locations. Grilles that diffuse the air comfortably such as the Techgrille™ are recommended.
25 DIRECT CONNECTION of the SUPPL Y AIR STREAM to the FURNA CE COLD AIR RETURN (Stale air drawn fr om key areas of home) Forced Air Furnace Outdoors *Unit is normally balanced on HIGH speed with furnace blower ON. EXHA UST AIR from various par ts of home.
26 Simplified Installation Option 1 (Return/Return Method) Note: Option 1 is the pr eferred / r ecommended method when doing a simplified installation. Example diagram only - duct configuration may change depending on model *Unit is normally balanced on HIGH speed with furnace blower ON.
27 Simplified Installation Option 2 (Supply/Return Method) RETURN AIR DIRECT CONNECTION of both the HRV/ERV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN & SUPPLY AIR SIDE Outdoors Cool Air Return NOTES: 1. Furnace blower is required to operate when ventilation from HRV/ERV is required.
28 Fully Dedicated System Example diagram only - duct configuration may change depending on model Please Note: It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.
It is necessary to have balanced air flows in an HRV/ERV. The vol- ume of air brought in from the outside must equal the volume of air exhausted by the unit.
30 Push and turn with slotted screwdriver. Damper automatically locks when pressure is released. When connecting ductwork to the collar, take note where screws are located. Screws should be located no further than 1/2” from outside edge of collar, so as not to impede operation of the damper.
31 1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In win- ter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).
32 1. Inspect Exterior Hoods at least once a month Make sure exhaust and fresh air supply hoods are not blocked up or restricted by leaves, grass, or dirt. WARNING: Blockage of hoods may cause an imbal- ance. 2. Clean Air Filters Four Times a Year The standard filters equipped with your ERV are removable and washable.
33 SYMPT OM CA USE SOLUTION Poor Air Flows Supply air feels cold Dehumidistat is not Operating Humidity Levels are too High Condensation is appearing on the windows Humidity Levels are too Low HRV/ERV.
34 Interlocking HRV Operation to an Airhandler/Furnace Blower - ControlAir 15 Electronics R GW YC R GW Y Furnace Thermostat Wire Connector T9 T10 T11 T12 T13 T14 T5 T4 T3 GROUND HIGH V OL T A GE 12V L.
35 F AN MOT OR GRN T12 T13 CAP A CIT OR WHITE BLK BRO WN BRO WN DIRECT MOUNTED CAP ACIT OR T9 T10 T11 T12 T13 T14 T5 T4 T3 GROUND DOOR SWITCH WHITE BLACK HIGH V OL T AGE 12V LO W V OL T AGE FIELD INST.
36 HIGH V OL T A GE 12V LO W VOL T A GE FIELD INST ALLED LEGEND 12V LO W VOL T A GE Note: If any of the original wire as supplied with the unit must be replaced, use only TEW certified wire IMPORT ANT.
デバイスLifebreath 200MAX RXの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Lifebreath 200MAX RXをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLifebreath 200MAX RXの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Lifebreath 200MAX RXの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Lifebreath 200MAX RXで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Lifebreath 200MAX RXを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLifebreath 200MAX RXの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Lifebreath 200MAX RXに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLifebreath 200MAX RXデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。