Manual No. H-504 2008-02-15 RETROFIT INSTRUCTIONS FOR GSTC / SETC / NHTC / NHDI / NHSC Inst allation Manual TM.
Page ii 2008-02-15 PROPRIETARY NOTICE This document and the info rmation disclosed herei n are propriet ary data of W AL TER MEIER L TD. Neither this document nor the information cont ained herein shall be reproduced used, or disclosed to others without the written authoriza tion of W AL TER MEIER L TD.
2008-02-15 TABLE OF CONTENTS Subject Page 10-00 LINKS 2 - FIELD INSTALLATION OF A SE-50 1. FIELD INSTALLATION OF A SE-50 SERIES HUMIDIFI ER WITH A LINKS 2 REMOTE PACKAGE . . . . . . . 2 A. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . .
10-00 Page 1 2008-02-02 10-00 LINKS 2 - FIELD INSTALLATION OF A SE-50.
10-00 Page 2 2008-02-02 (1) FIELD INSTALLATION OF A SE- 50 SERIES NORTEC LINKS 2 REMO TE PACKAGE A. STEP 1 - INSTALLATION (1) Mount the LINKS 2 remote package in a convenient location. Note that the remote package does not need to be mounted in close proximity to the humidifier.
10-10 Page 1 2008-02-15 10-10 LINKS 2 - FIELD CONVERSION OF A GSTC/SETC.
10-10 Page 2 2008-02-15 (1) FIELD CONVERSION OF A GS TC/SETC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: A. WIRING THE NORTEC LINKS 2 MODUL E (1) Most of the wiring conn ec.
10-10 Page 3 2008-02-15 B. MOUNTING THE LI NKS 2 ASSE MBLY (1) Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the GS or SE unit. If pilot holes for the mounting screws are not already present on the humidifier frame follow steps 2 and 3.
10-10 Page 4 2008-02-15 C. CONFIGURING TH E HUMIDIFIERS (1) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can be determined by the presence of the Links module.
10-20 Page 1 2008-02-15 10-20 LINKS 2 - FIELD CONVERSION OF A NHTC.
10-20 Page 2 2008-02-15 (1) FIELD CONVERSION OF A NHTC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: Figure 1. Component Identification A. MOUNT THE LINKS 2 ASSEMBLY (1) The Nortec LINKS 2 assembly mounts on the top, right corner of the elect rical compartment.
10-20 Page 3 2008-02-15 Figure 2. Hook Position Figure 3. Assembly Mounting Location Hook Position Hook Position.
10-20 Page 4 2008-02-15 B. CONFIGURING THE H UMIDIFIERS (1) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can be determined by the presence of the Links module.
10-30 Page 1 2008-02-15 10-30 LINKS 2 - FIELD CONVERSION OF A NHDI/SC.
10-30 Page 2 2008-02-15 (1) FIELD CONVERSION OF A NHDI/SC SERIES HUMIDIFIER WITH NORTEC LINKS 2 BACNET, LONWORK S AND N2 MODULES: Figure 1. Component Identification A. MOUNT THE LINKS 2 ASSEMBLY (1) Refer to Figure 2 for the mounting location of the Nortec LINKS 2 Bracket on the NHDI or NHSC unit.
10-30 Page 3 2008-02-15 Figure 2. LINKS 2 Bracket Placement B. WIRING THE NORTEC LINKS 2 MODUL E (1) Most of the wiring connections for the Nortec LINKS 2 module will have already been finished at the factory, however, there are a few connections that will need to be made to connect the module to the NHDI/SC series humidifier.
10-30 Page 4 2008-02-15 Figure 3. NHDI LINKS 2 Slave Installation (3) Installation of LINKS 2 Slave Option (a) The LINKS 2 module is capable of supporting up to 8 humidifiers when each unit is equipped with a TTL to RS-485 signal conv erter. The LINKS 2 slave option consists of a small bracket with the signal converter mounted on one side.
10-30 Page 5 2008-02-15 (4) Configuring the Humidifiers (a) Since Nortec LINKS 2 can connect to a maximum of 8 units, it will be necessary to set the unit address for each humidifier. The lead unit can b e determined by the presence of the LINKS module and should be set to modbus address 1.
WARRANTY (1) WALTER MEIER INC. and/or WALTER MEIER LTD. (hereinafter collective ly referred to as THE COMPANY), warrant for a period of two years afte r installation or 30 months from manufacturer’s.
Authorized Agent: INST ALLA TION DA TE (MM/DD/YYYY) MODEL # SERIAL # CYLINDER # U.S.A. W alter Meier (Climate USA) Inc. 826 Proctor Avenue Ogdensburg, NY 13669 TEL: 1-866-NORTEC-1 EMAIL: nortec@humidity .com WEBSITE: www .humidity .com CANADA W alter Meier (Cli mate Canada) Ltd.
デバイスNortec Industries SETCの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Nortec Industries SETCをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはNortec Industries SETCの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Nortec Industries SETCの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Nortec Industries SETCで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Nortec Industries SETCを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はNortec Industries SETCの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Nortec Industries SETCに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちNortec Industries SETCデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。