OMRON ETHE RNET Direct DASe rver User’s Guide Ver 1.x Rev 1.4 DR 170 14 KLINKMANN AUTOMATION P.O. Box 38 FIN-00371 Helsinki Finland tel. int. + 358 9 5404940 fax int.
Klinkmann Automation Omron Ethernet DASe rver i Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Contents Before You Begin ............. .............. ............. ............. ............. ............. ............. ............. .
Klinkmann Automation Omron Ethernet DASe rver ii Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Componen t Environments ...... .......
Klinkmann Automation Omron Ethernet DASe rver 2 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CHAPTE R 1 Introduction This chapte r provides you with an overv iew of the KL INKMANN OMRON Ethernet Direct DAServer, including the application- and bus-level communicat ions protocols, item naming conventions a nd DAServer featu res.
Klinkmann Automation Omron Ethernet DASe rver 3 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Microsoft W indows program capable of acting as a DDE, S uiteLink ™ or OPC client t hat can also coexist with FactorySuite ™ 2000 and greater.
Klinkmann Automation Omron Ethernet DASe rver 4 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 FastDDE FastDDE provides a means o f packing ma ny proprietary W on derware Dynamic Data Exchange messages into a single Microsof t DDE message.
Klinkmann Automation Omron Ethernet DASe rver 5 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 To access a n OPC item, th e OPC client nee ds to conn ect to the DAServer (either in- process or out-of -process) and create an OPC group def ining the da ta-acquisition properties f or the collection o f item s to be ad ded.
Klinkmann Automation Omron Ethernet DASe rver 6 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 • topic nam e: Meaningfu l names are configured in th e DAServer to identif y specific devices. These na mes are th en used a s the topic n ames in all con versations with that device.
Klinkmann Automation Omron Ethernet DASe rver 7 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 /2003 insta llation package, Comm andline In stallation”) can be o btained f rom Klinkm ann software downloads page: http://www .klinkmann.
Klinkmann Automation Omron Ethernet DASe rver 8 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CHAPTE R 2 Before starting the OMRON E thernet DAServer This chapte r contains instructions h ow to configure OMRON PLCs to be accessible by Omron Ethe rnet DAServer in OMRON Ethernet FA network.
Klinkmann Automation Omron Ethernet DASe rver 9 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Configuration sof tware tool, app ropriate (and recom mended ) for all OMRON controllers is OMRON CX- Programmer W indows Programing Software (see “OMRON CX-Progr ammer Users Manual”) .
Klinkmann Automation Omron Ethernet DASe rver 10 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 W hen CX-Programmer establishes comm unication with PLC, select " Operating Mode" (from PLC's m enu) and set "Program" m ode.
Klinkmann Automation Omron Ethernet DASe rver 11 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 W hen IO Tab le is received, display the slot list under Main Rack (press " +" button in the "PLC IO Ta ble - NewPLC1" dialog box).
Klinkmann Automation Omron Ethernet DASe rver 12 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Click "Unit Setup". T he "E thernet Unit CPU Bus Unit" dialog box a.
Klinkmann Automation Omron Ethernet DASe rver 13 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Enter Address Conversion type, FINS UDP port n umber an d Sub-net Mask. Edit the IP Address Tab le: the com puter where Omron Et hernet DAServer is running must be a dded to the IP Ad dress Table.
Klinkmann Automation Omron Ethernet DASe rver 14 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 To com plete the co nfiguration: f rom th e "Etherne t Unit CPU Bus Unit" (or f rom the "PLC IO Table - NewPLC1") dialog box select "Options" an d click "Transf er to PLC" .
Klinkmann Automation Omron Ethernet DASe rver 15 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 by-time poll area D500…D509 and time -by-time gets unsolicited comma nd assigning to items D500…D509 values of PL Cs D10…D19 area.
Klinkmann Automation Omron Ethernet DASe rver 16 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14.
Klinkmann Automation Omron Ethernet DASe rver 17 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CHAPTE R 3 Configuration Once the KL INKMANN Omron Ethernet DAServer has been insta lled, a small am ount of configuration is required.
Klinkmann Automation Omron Ethernet DASe rver 18 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 4. From the Sy stem Management Consol e, fin d the Om ron Ethernet DAServer in the DA Server Manager tree, th e location in which it is installed.
Klinkmann Automation Omron Ethernet DASe rver 19 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 DAServer Manager, click the Help topics on the SMC Help menu. B oth the MMC Help and the DAServer Manager Help are displayed. An Adobe Acrobat version of the DAServer Manager documentation (DAServerManager.
Klinkmann Automation Omron Ethernet DASe rver 20 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Note: See the DAServer Manager documentat ion for gene ral informat ion about working in this snap-in environmen t.
Klinkmann Automation Omron Ethernet DASe rver 21 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 • To activate the DAServer, right-click on ArchestrA .
Klinkmann Automation Omron Ethernet DASe rver 22 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Enter/modif y SOCKET param eters. Host Name (IP A ddr.) Enter the Com puter’s Interne t Address (IP Add ress) if it has m ore than o ne.
Klinkmann Automation Omron Ethernet DASe rver 23 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 This conf iguration view has 15 paramete rs (configuration requires proven network info.
Klinkmann Automation Omron Ethernet DASe rver 24 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 C/CPM2x series offers 5 o ptions (C200HS, C20 0H, C1000H, C2000 H, CPM2x) and CQM1 series of fers 1 option (CQM1).
Klinkmann Automation Omron Ethernet DASe rver 25 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 • Check or uncheck th e Slave Mode check box to select the principles how to obtain data f rom correspond ing controller. If Sla ve Mode is not checked (Master mode ) – DAServer polls data from controller all the tim e.
Klinkmann Automation Omron Ethernet DASe rver 26 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Note: Default Wat chdog state is “non-active”, i.e. Wa tchdog Time Interval is equa l to z ero. Note: In order to u se the DAServer, you must a ctivate it.
Klinkmann Automation Omron Ethernet DASe rver 27 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Here the “Custome r ID” is “computer-depend ent” string generated by DASOmronEt h and “Product ID” is DASOm ronEth produ ct code and version.
Klinkmann Automation Omron Ethernet DASe rver 28 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Note: W hen you select anot her part of the DAServer tree hierarchy, you are promp ted to save the modif ications to t he conf iguration set.
Klinkmann Automation Omron Ethernet DASe rver 29 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 The Device Group pa rameters dialog can b e used to configure pref erred Read mode a nd W rite optimization mode.
Klinkmann Automation Omron Ethernet DASe rver 30 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 changed in the following sequence: DM0, 500R, DM1, 50 2R, DM2, ... then DAServer creates a sepa rate write message for ea ch new write v alue.
Klinkmann Automation Omron Ethernet DASe rver 31 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Since you more tha n likely want v ery fast response , the tem ptation is to set the Upd ate Interval to a value close to 0 seconds.
Klinkmann Automation Omron Ethernet DASe rver 32 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Each device item de finition sh ould conta in a unique nam e fo r the PLC associat ed with it.
Klinkmann Automation Omron Ethernet DASe rver 33 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 1. In the Item Reference colum n, doub le-click on the area in the same horizontal line as the selected device item. 2. Type in the actual PLC item name in the f rame tha t appea rs.
Klinkmann Automation Omron Ethernet DASe rver 34 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 The Om ron Ethernet DAServer is hot-configurable. T he f ollowing hot-configuration function ality is incorporated in Omron Ethernet DASe rver: • Modifying Global Configuration parameters.
Klinkmann Automation Omron Ethernet DASe rver 35 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CHAPTE R 4 Item Names The Om ron Ethernet DAServer supports item/po int names co nsistent with the point naming conventions use d by OMRON PLCs and programming sof tware.
Klinkmann Automation Omron Ethernet DASe rver 36 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 contains 800 0 hex. In this case item nam e DM100 or DM100U would be displa yed in client as 3276 8. Signed quantities m ay be read f rom the same chan nel by appending the suff ix ' S ' (or ' s ') to the item na me.
Klinkmann Automation Omron Ethernet DASe rver 37 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 High-order Byte Only the high-order byte (MSB - most significant 8-bits) of each word is used for read. To use this form at, appe nd the su ff ix ' D ' to the item name.
Klinkmann Automation Omron Ethernet DASe rver 38 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CS1/CJ1 PLCs The f ollowing table lists the supporte d item na mes f or the CS1/CJ1 PLCs: Memory Area Prefix Tag Type Range Value Rang e Format Suff ix CIO Area (Bit status) CIO Discrete CIO0:00.
Klinkmann Automation Omron Ethernet DASe rver 39 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Item/poin t names, corresponding to CIO Area, may be without pref ix.
Klinkmann Automation Omron Ethernet DASe rver 40 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 C200HX/C200HG/C200HE PLC s The f ollowing table lists the supporte d item na mes f or the C200HX , C200HG and C200HE PLCs.
Klinkmann Automation Omron Ethernet DASe rver 41 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 (****) Read only The f ollowing examples show the correct forma t for ite m name s for C200 HX, C200HG, C200HE PLCs and SYSMAC Board: IR2:01 - Inte rnal Relay Area (Bit status), word address 2, b it number 1 .
Klinkmann Automation Omron Ethernet DASe rver 42 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Step Tim er Present Value PVS Integer PVS0... PVS1023(***) ( *) u s b f g l m d e c Expansion area Current bank (Bit status) E Discrete E0:00.
Klinkmann Automation Omron Ethernet DASe rver 43 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Item/poin t names, corresponding to Inp ut/Output register area CIO, may be without prefix.
Klinkmann Automation Omron Ethernet DASe rver 44 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 C/CPM2x PLCs The f ollowing table lists the suppo rted item na mes f or the C-series PLCs: Memory Area Prefix Tag Type Range Value Range Format Suff ix CIO area (Bit status) IR D iscrete IR0:00.
Klinkmann Automation Omron Ethernet DASe rver 45 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Memory Area Prefix Tag Type Range Value Range Format Suff ix IR & SR areas (Bit status)(***) IR Discrete IR0:00...IR255 :15 or 0.00...
Klinkmann Automation Omron Ethernet DASe rver 46 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CQM1 PLCs The f ollowing table lists the supporte d item na mes f or the CQM1 PLCs: Memory Area Prefix Tag Type Range Value Range Format Suff ix IR & SR area (Bit status) IR Discrete IR0:00.
Klinkmann Automation Omron Ethernet DASe rver 47 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 102 - IR Output area (W ord conte nts), word address 102 LR62.
Klinkmann Automation Omron Ethernet DASe rver 48 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 DA Server Global Sy stem Item The f ollowing system item refers to sp ecific inf ormation regarding a global con dition of the DAServer.
Klinkmann Automation Omron Ethernet DASe rver 49 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 practical application, OP C clients should ref erence $SYS$Sta tus at any hierarchy levels other than the root. $SYS$ErrorCode Lo ngint/ Read Detailed error code of th e communicat ions state to the device.
Klinkmann Automation Omron Ethernet DASe rver 50 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 DA Server Device-Grou p-Specific Sy stem Items The f ollowing system items refer to sp ecific inf ormation regarding device groups that h ave been conf igured in the DAServer.
Klinkmann Automation Omron Ethernet DASe rver 51 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 or a -1 to test a client reaction on write errors). If the value of th is item is zero, it cannot be poked. $SYS$ReadComplet e Integer/ ReadW rite Used to access the state of initial reads on all item s in the corresponding device group.
Klinkmann Automation Omron Ethernet DASe rver 52 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 device groups with a zero update int erval (manual protocol triggering). Generic OPC Sy ntax DAServer serves as a container for th e OPC Groups, which provide the m echanism f or containing and logically organizing OPC items.
Klinkmann Automation Omron Ethernet DASe rver 53 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CHAPTE R 5 Troubleshootin g This chapte r describes the trou bleshooting tools you can use to de al with the Omron Ethernet DAServer problems you may encounter.
Klinkmann Automation Omron Ethernet DASe rver 54 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 YourOPCA ccessPa th is the assemb ly of hierarchy node nam es leading to a specific controller device. $SYS$Status is the discrete item used to monitor the status of conne ctivity with the controller device.
Klinkmann Automation Omron Ethernet DASe rver 55 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 In this example, e ach time th e value of <tagname> changes in the PLC, th e DAServer will automatically send the new value to the ce ll containing the f ormula in E xcel.
Klinkmann Automation Omron Ethernet DASe rver 56 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Error Messages and Cod es Generic DAServer error messages and Om ron Ethernet-DAServer-specific m essages are supported. Use the Log Flag data to customize the m essages logged to the Lo g Viewer.
Klinkmann Automation Omron Ethernet DASe rver 57 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 value from 0 to 65535 . < Socket _ ControllerName >: Invalid W atchdog Address <InvalW dAd dress> - must be valid Item name. Do n ot process W atchdog.
Klinkmann Automation Omron Ethernet DASe rver 58 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Item <Item Name> (<Pointer to Item_Class_Obj.>) was not created: ma x allowed message's length <Max_Length> is not suf ficient.
Klinkmann Automation Omron Ethernet DASe rver 59 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 and writing back modif ied word value into PLC’s memory. Here the processing of first step f ailed. < Socket _ ControllerName >: Item <Pointer to Item_Class_Obj.
Klinkmann Automation Omron Ethernet DASe rver 60 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Serv er-Specific Error Codes There are f ollowing server-specific error codes, shown in the table , that augme nt those provided by the DAS Too lkit.
Klinkmann Automation Omron Ethernet DASe rver 61 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 number to o large. numbe r below the maximum nod e numb er. 0 3 Send error caused by lack of available spa ce in PLC internal buf f ers. Reduce the t raff ic on the Ethernet Unit.
Klinkmann Automation Omron Ethernet DASe rver 62 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 operation m anual) 04 Node number setting error. Make sure the no de number is within specified ran ge and that there are no duplicate node nu mbers.
Klinkmann Automation Omron Ethernet DASe rver 63 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 UDP/TCP socket number was not within the proper range and 8. 01 An incorrect memory area or unavailable expansion mem . area has been used.
Klinkmann Automation Omron Ethernet DASe rver 64 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 data transf er between the CPU unit an d a CPU Bus Unit). issue the ERROR CLEAR comman d 0A An error occured during CPU Bus Unit data transfer.
Klinkmann Automation Omron Ethernet DASe rver 65 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 CHAPTE R 6 Reference Contents • DAServer Architecture • Componen t Environments DA Serv er A rchitecture Note: DAServers are supported on Microsoft W indows 2000 an d W indows XP only.
Klinkmann Automation Omron Ethernet DASe rver 66 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 Each physical part of a DAServer is comprised of a set o f .exe and /or .dll modu les. W onderware provides the Plug-ins and the DAS En gine.
Klinkmann Automation Omron Ethernet DASe rver 67 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 The PL C Protocol Layer provides a protocol-translation funct ion for sp ecific hardware, such as OMRON FinsGateway; and it serves as an interf ace between th e DAS Engine and the hardware.
Klinkmann Automation Omron Ethernet DASe rver 68 Om ron Ethernet DAS erver Ver 1.x User Manual Re v 1.4 17014m14 KLINKMANN AUTOMATION Omron Ethe rnet Direct DAServer Revision History Mar 2005 Rev 1.0 First Release Dec 2005 Rev 1.1 “Comput er Node” Address rem oved from CONTROLLER Object pa rameters conf iguration.
デバイスOmron DR 170 14の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Omron DR 170 14をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはOmron DR 170 14の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Omron DR 170 14の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Omron DR 170 14で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Omron DR 170 14を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はOmron DR 170 14の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Omron DR 170 14に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちOmron DR 170 14デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。