OMRON ETHE RNET D irect DAServ er User’s Guide Ver 1.x Rev 1.4 DR 170 14 KLINKMANN AUTOMATION P.O. Box 38 FIN-00371 Helsinki Finland tel. int. + 358 9 5404940 fax int.
Klinkmann A utomation Omron E thernet DAServer i Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Contents Before You B egin .............. ............... ............... ............... ................ ............... ............... .
Klinkmann A utomation Omron E thernet DAServer ii Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Component Environments ...... ........
Klinkmann A utomation Omron E thernet DAServer 2 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CHAPTER 1 Introduction This chapte r provides you wi th an overview of the KLINKMANN OMRON Ethernet Direct DAServer, including the application- and bus-level communication s protocols, item naming conventions an d DAServer features.
Klinkmann A utomation Omron E thernet DAServer 3 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Microsoft W indows program capable of acting as a DDE, SuiteLink ™ or OPC client that can also coexist with FactorySuite ™ 2000 and greater.
Klinkmann A utomation Omron E thernet DAServer 4 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 FastDDE FastDDE provides a means of packing man y proprietary W onderware Dynamic Data Exchange messages into a single Microsoft DDE message.
Klinkmann A utomation Omron E thernet DAServer 5 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 To access an OPC item, the OPC client needs to connect to the DAServer (either in- process or out-of -process) and create a n OPC group def ining the data-acquisition properties fo r the collection of items to be added .
Klinkmann A utomation Omron E thernet DAServer 6 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 • topic nam e: Meaningfu l names are con figured in the DAServer to identify specific devices. These na mes are then used as the topic name s in all conversations with that device.
Klinkmann A utomation Omron E thernet DAServer 7 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 /2003 installatio n package, Comm andline Installation ”) can be obtain ed from Klinkmann software downloads page: http://www .klinkmann.
Klinkmann A utomation Omron E thernet DAServer 8 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CHAPTER 2 Before starting the OMRON E thernet DAServer This chapte r contains instructions ho w to configure OMRON PLCs to be acce ssible by Omron Etherne t DAServer in OMRON Ethernet FA network.
Klinkmann A utomation Omron E thernet DAServer 9 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Configuration sof tware tool, appropriate (and recomme nded) f or all OMRON controllers is OMRON CX-Pr ogrammer W indows Programing Software (see “OMRON CX-Pr ogrammer Users Manual”) .
Klinkmann A utomation Omron E thernet DAServer 10 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 W h en CX-Programmer establishes comm unication with PLC, select " Operating Mode" (from PLC's m enu) and set "Program" mod e.
Klinkmann A utomation Omron E thernet DAServer 11 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 W h en IO Ta ble is received, display the slot list under Main Rack (press " +" button in the "PLC IO Ta ble - NewPLC1" dialog box).
Klinkmann A utomation Omron E thernet DAServer 12 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Click "Unit Setup". T he "Eth ernet Unit CPU Bus Unit" dia log box .
Klinkmann A utomation Omron E thernet DAServer 13 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Enter Address Conversion type, FINS UDP port nu mber and Sub-net Mask. Edit the IP A ddress Table: the compu ter where Omron Ethernet DAServer is running must be a dded to th e IP Address T able.
Klinkmann A utomation Omron E thernet DAServer 14 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 To comp lete the con figuration: f rom the "E thernet Unit CPU Bus Unit" (or from the "PLC IO Table - NewPLC1") dialog box select " Options" and click "Transfe r to PLC".
Klinkmann A utomation Omron E thernet DAServer 15 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 by-time poll area D500…D509 and time-by-time gets unso licited command assigning to items D500…D509 values of PLCs D10…D19 area.
Klinkmann A utomation Omron E thernet DAServer 16 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14.
Klinkmann A utomation Omron E thernet DAServer 17 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CHAPTER 3 Configuration Once the KL INKMANN Omron Ethernet DASe rver has been installed, a small amoun t of configuration is required.
Klinkmann A utomation Omron E thernet DAServer 18 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 4. From the S y stem Management Consol e, find the Omron Et hernet DAServer in the DA Se rver Manager tree, the location in which it is installed.
Klinkmann A utomation Omron E thernet DAServer 19 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 DAServer Manager, click the Help topics on the SMC Help menu. Bot h the MMC Help and the DASe rver Manager Help are displayed. An Adobe Acrobat version of th e DAServer Manager documentation (DAServerManager.
Klinkmann A utomation Omron E thernet DAServer 20 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Note: See the DAServer Manager documentation for general inf ormation ab out working in this snap-in environmen t.
Klinkmann A utomation Omron E thernet DAServer 21 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 • To activate the DAServer, right-cli ck on A rchestrA .
Klinkmann A utomation Omron E thernet DAServer 22 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Enter/modif y SOCKET param eters. Host Name (IP A ddr.) Enter the Com puter’s Internet Address (IP Address) if it has more th an one. If there is only one Internet A ddress for com puter then you can use def ault add ress 0.
Klinkmann A utomation Omron E thernet DAServer 23 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 This conf iguration view has 15 parameters (conf iguration requires proven network info.
Klinkmann A utomation Omron E thernet DAServer 24 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 C/CPM2x series offers 5 o ptions (C200HS, C200H, C10 00H, C2000H, CPM2x) and CQM1 series of fers 1 op tion (CQM1).
Klinkmann A utomation Omron E thernet DAServer 25 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 • Check or uncheck the Slave Mode check box to select the p rinciples how to obtain data f rom corresponding controller. If Slave Mode is not checked (Master mode) – DAServer polls data from controller all the time .
Klinkmann A utomation Omron E thernet DAServer 26 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Note: Default Watch dog state is “no n-active”, i.e. Watchd og Time Interval is e qual to z ero. Note: In order to u se the DAServer, you must activate it.
Klinkmann A utomation Omron E thernet DAServer 27 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Here the “Customer ID” is “comp uter-dependen t” string generated by DASOmronEth and “Product ID” is DASOmron Eth product co de and version.
Klinkmann A utomation Omron E thernet DAServer 28 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Note: W hen you select another p art of th e DAServer tree hierarchy, you are prompted to save the modif ications to the configuration se t.
Klinkmann A utomation Omron E thernet DAServer 29 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 The Device Group pa rameters dialog can be used to con figure prefe rred Read mode and W rite o ptimization mode.
Klinkmann A utomation Omron E thernet DAServer 30 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 changed in the following sequence: DM0, 500R, DM1, 502 R, DM2, ... then DAServer creates a separat e write message for each new wri te value.
Klinkmann A utomation Omron E thernet DAServer 31 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Since you more tha n likely w ant very fast response, the temp tation is to set t he Update Interval to a value close to 0 seconds.
Klinkmann A utomation Omron E thernet DAServer 32 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Each device item de finition sho uld contain a u nique name f or the PL C associated with it.
Klinkmann A utomation Omron E thernet DAServer 33 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 1. In the Item Reference column , double-click on the area in the sa me horizontal line as the selected d evice item. 2. Type in the actual PLC item name in th e frame that app ears.
Klinkmann A utomation Omron E thernet DAServer 34 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 The Om ron Ethernet DASe rver is hot-configurable. The following hot-configuration function ality is incorporated in Omron Eth ernet DAServer: • Modifying Global Configuration p arameters.
Klinkmann A utomation Omron E thernet DAServer 35 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CHAPTER 4 Item Names The Om ron Ethernet DASe rver supports item/point na mes consistent with the point naming conventions used by OMRON PLCs and programming soft ware.
Klinkmann A utomation Omron E thernet DAServer 36 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 contains 8000 hex. In this case item name DM100 or DM100U would be displayed in client as 3276 8. Signed quantities ma y be read from the same channel by appending the suff ix ' S ' (or ' s ') to the item name .
Klinkmann A utomation Omron E thernet DAServer 37 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 High-order Byte Only the high-order byte (MSB - most significant 8-bits) of each word is used for read. To use th is format, append th e suff ix ' D ' to the item name.
Klinkmann A utomation Omron E thernet DAServer 38 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CS1/CJ1 PLCs The f ollowing table lists the supported item name s for the CS1/CJ1 PLCs: Memory Area Prefix Tag Type Range Value Rang e Format Suff ix CIO Area (Bit status) CIO Discrete CIO0:00.
Klinkmann A utomation Omron E thernet DAServer 39 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Item/point names, correspo nding to CIO Area, m ay be without prefix.
Klinkmann A utomation Omron E thernet DAServer 40 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 C200HX/C200HG/C200HE PLCs The f ollowing table lists the supported item name s for the C200HX , C200HG and C200HE PLCs.
Klinkmann A utomation Omron E thernet DAServer 41 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 (****) Read only The f ollowing examples show the correct format for item names f or C200HX, C200HG, C200HE PLCs and S YSMAC Board: IR2:01 - Interna l Relay Area (Bit status), word address 2, bit nu mber 1.
Klinkmann A utomation Omron E thernet DAServer 42 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Step Tim er Present Value PVS Integer PVS0... PVS1023(***) (*) u s b f g l m d e c Expansion area Current bank (Bit status) E Discrete E0:00.
Klinkmann A utomation Omron E thernet DAServer 43 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Item/point names, correspo nding to Input/O utput register area CIO, ma y be without prefix.
Klinkmann A utomation Omron E thernet DAServer 44 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 C/CPM2x PLCs The f ollowing table lists the supported item name s for the C-series PLCs: Memory Area Prefix Tag Type Range Value Range Format Suff ix CIO area (Bit status) IR Di screte IR0:00.
Klinkmann A utomation Omron E thernet DAServer 45 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Memory Area Prefix Tag Type Range Value Range Format Suff ix IR & SR areas (Bit status)(***) IR Disc rete IR0:00...IR255 :15 or 0.00..
Klinkmann A utomation Omron E thernet DAServer 46 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CQM1 PLCs The f ollowing table lists the supported item name s for the CQM1 PLCs: Memory Area Prefix Tag Type Range Value Range Format Suff ix IR & SR area (Bit status) IR Discrete IR0:00.
Klinkmann A utomation Omron E thernet DAServer 47 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 102 - IR Output area (W ord contents), word address 1 02 LR62.
Klinkmann A utomation Omron E thernet DAServer 48 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 DA Server Global Sy stem Item The f ollowing sy stem item refers to spe cific inform ation regarding a global condition o f the DAServer.
Klinkmann A utomation Omron E thernet DAServer 49 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 practical application, OP C clients should ref erence $SYS$Statu s at any hierarchy levels other than the root. $SYS$ErrorCode Lo ngint/ Read Detailed error code of the communicat ions state to th e device.
Klinkmann A utomation Omron E thernet DAServer 50 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 DA Server Device-Group -Specific Sy stem Items The f ollowing sy stem items refer to spe cific inform ation regarding device groups that have been conf igured in the DASe rver.
Klinkmann A utomation Omron E thernet DAServer 51 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 or a -1 to test a client reaction on write errors). If the value of this item is zero, it cannot be poked. $SYS$ReadComplete Integer/ ReadW rite Used to access the state of initial reads on all item s in the corresponding device group.
Klinkmann A utomation Omron E thernet DAServer 52 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 device groups with a zero update inte rval (manual protocol triggering). Generic OPC Sy ntax DAServer serves as a container for th e OPC Groups, which provide the me chanism f or containing and logically organizing OPC items.
Klinkmann A utomation Omron E thernet DAServer 53 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CHAPTER 5 Troubleshooting This chapte r describes the trouble shooting tools you can use to deal with the Omron Ethernet DAServer problems you m ay encounter.
Klinkmann A utomation Omron E thernet DAServer 54 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 YourOPCA ccess Path is the assemb ly of hierarchy node nam es leading to a sp ecific controller device. $SYS$Status is the discrete item used to m onitor the sta tus of co nnectivity w ith the controller device.
Klinkmann A utomation Omron E thernet DAServer 55 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 In this example, ea ch time the value of <tagname> changes in th e PLC, the DASe rver will automatically send the new value to the cell con taining the f ormula in Excel.
Klinkmann A utomation Omron E thernet DAServer 56 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Error Messages and Codes Generic DAServer error messages and Omron Ethernet-DAServer-specific messa ges are supported. Use t he Log Flag data to cu stomize the messages logged to t he Log Viewer.
Klinkmann A utomation Omron E thernet DAServer 57 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 value from 0 to 65535 . < Socket _ ControllerName >: Invalid W at chdog Address <InvalW dAdd ress> - must be valid Item name. Do n ot process W atchdog.
Klinkmann A utomation Omron E thernet DAServer 58 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Item <ItemNam e> (<Pointer to Item_Class_Obj.>) was not created: ma x allowed message's length <Max_Length> is not suf ficient.
Klinkmann A utomation Omron E thernet DAServer 59 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 and writing back modif ied word value into PLC’s memory. Here the processing of first step f ailed. < Socket _ ControllerName >: Item <Pointer to Item_Class_Obj.
Klinkmann A utomation Omron E thernet DAServer 60 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Serv er-Specific Error Codes There are f ollowing server- specific error codes, shown in the table, t hat augment those provided by the DAS Too lkit.
Klinkmann A utomation Omron E thernet DAServer 61 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 number too large. number below the maximum node number. 0 3 Send error caused by lack of available spa ce in PLC internal buf fe rs. Reduce the traf fic o n the Ethernet Unit.
Klinkmann A utomation Omron E thernet DAServer 62 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 operation m anual) 04 Node number setting error. Make sure the no de number is within specified ran ge and that there are no d uplicate node num bers.
Klinkmann A utomation Omron E thernet DAServer 63 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 UDP/TCP socket number was not within the proper range and 8. 01 An incorrect memory area or unavailable expansion mem. area has been u sed.
Klinkmann A utomation Omron E thernet DAServer 64 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 data transf er between the CPU unit and a CPU Bus Unit). issue the ERROR CLEAR comman d 0A An error occured d uring CPU Bus Unit data transfer.
Klinkmann A utomation Omron E thernet DAServer 65 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 CHAPTER 6 Reference Contents • DAServer Architecture • Componen t Environments DA Server A rchitecture Note: DAServers are supported on Microsoft W indows 2000 and W indows XP only.
Klinkmann A utomation Omron E thernet DAServer 66 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 Each physical part of a DAServer is comprised of a set of .exe and/or .dll m odules. W o nderware provides the Plug-ins and the DAS Engine.
Klinkmann A utomation Omron E thernet DAServer 67 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 The PLC Prot ocol Layer provides a protocol-translation f unction f or specif ic hardware, such as OMRON FinsGateway; and it serves as an interf ace between the DAS Engine and the h ardware.
Klinkmann A utomation Omron E thernet DAServer 68 Omr on Ethernet DA Server Ver 1.x User Manual Rev 1.4 17014m14 KLINKMANN AUTOMATION Omron Etherne t Direct DAServer Revision History Mar 2005 Rev 1.0 First Release Dec 2005 Rev 1.1 “Com puter Node” Add ress removed from CONTROLLER Object param eters conf iguration.
デバイスOmron ETHERNET DIRECT DR 170 14の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Omron ETHERNET DIRECT DR 170 14をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはOmron ETHERNET DIRECT DR 170 14の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Omron ETHERNET DIRECT DR 170 14の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Omron ETHERNET DIRECT DR 170 14で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Omron ETHERNET DIRECT DR 170 14を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はOmron ETHERNET DIRECT DR 170 14の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Omron ETHERNET DIRECT DR 170 14に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちOmron ETHERNET DIRECT DR 170 14デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。