Raypakメーカー105Bの使用説明書/サービス説明書
ページ先へ移動 of 31
CATALOG NO. 6100.60A Effective: 10-1-99 Replaces: 6-15-99 Fig. # 9258 Part No. 240776 OPERA TING AND INST ALLA TION INSTRUCTIONS Model 105B Cast Iron VERSA ABOVE GROUND POOL and SP A HEA TER WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Contents 2 PART ONE - Owner's Operating Instructions 2 SECTION 1 / START-UP PROCEDURES 2 Before Start-Up 3 Lighting Instructions & Shut-Off Procedures (manually lighted pilot MV) 4 Operating .
P ART ONE - OWNER'S OPERA TING INSTRUCTIONS BEFORE START-UP BURNERS Clean main burners and air louvers of dust, lint and debris. Keep heater area clear and free from com- bustibles, flammable liquids and chemicals. Do not obstruct the flow of combustion and ventilating air.
1. STOP! Read the safety information above. 2. Set the thermostat on the lowest setting. 3. Turn On/Off switch to the "Off" position. 4. Remove heater door panel.
TO TURN OFF GAS TO APPLIANCE 1. STOP! Read the safety information above. 2. Set the thermostat to the lowest setting. 3. Turn off all electric power to the appliance. 4. This appliance is equipped with an ignition device which automatically lights the pilot.
AFTER START-UP Feel the inlet and outlet pipes. Outlet pipe should be only slightly warmer than the inlet. It should not be hot. WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
COLD WEATHER OPERATION MODERATE CLIMATE: Heater operation can con- tinue during short term cold spells. When tempera- tures are below freezing, flow (continuous pump op- eration) must be maintained. CAUTION: Do not use the heater to maintain water temperatures just above freezing or for freeze protec- tion.
P ART 2 - INST ALLA TION / SER VICE INSTRUCTIONS SECTION 1 RECEIVING EQUIPMENT On receipt of your equipment it is suggested that you visually check for external damage to the carton. If the carton is damaged, a note should be made on the Bill of Lading when signing for equipment.
CLEARANCES ALL HEATERS For clearances from combustible surfaces, see chart below. Clearances from Combustible construction. Indoor Installation: Top* (Drafthood) - 30"; Vent - 6"; Back - 5"; Right Side - 6"; Left Side - 6"; Floor - 0.
HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY) In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high vertical walls, or install a wind break so the heater is not in direct wind current.
VENTING CONNECTIONS VENT TERMINAL (Outdoor) STACKLESS TOP STEP 1: Remove the (4) screws which fasten jacket top to heater. STEP 2: Lower outdoor top onto unit lining up slots in outdoor top with screw holes in jacket top. STEP 3: Reinstall (4) screws to secure jacket top and outdoor top to unit.
VENT PIPING WARNING: Indoor boilers require a draft hood that must be connected to a vent pipe and properly vented to the outside. Failure to follow this procedure can cause fire or fatal carbon monoxide poisoning.
GAS SUPPLY CONNECTIONS Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve located outside the heater jacket.
PLUMBING FOR WATER CONNECTIONS LOCATION The VERSA heater requires water flow and positive pressure to fire and operate properly. It must therefore be installed downstream of the discharge side of the filter pump. A typical installation is plumbed as follows: 1.
ELECTRICAL WIRING NOTE: If it is necessary to replace any of the original wiring, it must be replaced with 105 ° C wire or its equivalent, except all black wire must be replaced with 150 ° C wire or its equivalent.
15 WIRING DIAGRAM MILLIVOLT UNITS Fig. #9266 WIRING DIAGRAM KEY Fig. # 8096 PINK CONNECTOR BLUE CONNECTOR.
WIRING DIAGRAM I.I.D. UNITS IGNITION DEVICE - HONEYWELL Fig. # 9250 16.
WIRING DIAGRAM IID UNITS IGNITION DEVICE - ROBERTSHAW Fig. # 9251 17.
SECTION 4 / SERVICING INSTRUCTIONS GENERAL LOCATION OF CONTROLS 18 CONTROLS/ADJUSTMENTS/ REPLACEMENTS TEMPERATURE CONTROLS The water temperature is controlled by the heater thermostat on the upper front panel of the heater. The control center contains an On/Off toggle switch and a thermostat.
PRESSURE SWITCH ADJUSTMENT: 1. With pump and heater on, turn adjustment knob (clockwise) until a click is heard from the gas valve. 2. Turn adjustment knob (counter clockwise) 1/4 turn. 3. Turn pump off and on several times. Heater should shut off immediately.
BURNER DRAWER REMOVAL 1. Shut off main electrical power switch to heater. 2. Shut off gas upstream of heater. 3. Remove front door. 4. Disconnect gas line from gas valve. 5. Remove (2) screws that mount burner tray to unit. 6. Disconnect wires that terminate at gas valve.
TUBE CLEANING PROCEDURE Establish a regular inspection schedule, frequency depending on local water condition and severity of service. Do not let the tubes clog up solidly. Clean out deposits over 1/16" in thickness. The heater may be cleaned from the return header side, without breaking pipe connections.
SECTION 5 / TROUBLE SHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed.
If pilot burner remains lit. Jump across pressure switch terminals If main burner does not fire, remove jumper Check for adequate water flow from filter Replace pressure switch Jump across thermostat If main burner fires, remove jumper If main burner does NOT fire.
ELECTRICAL (ELECTRONIC IGNITION IID) WARNING HIGH VOLTAGE For qualified Technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light.
SECTION 6/REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable.
26 9-P 1-P 12-P 5-P 14-P MV IID 13-P 15-P 14-P 7-P 3-P Fig. #8132 Fig. #8133.
27.
28.
LIMITED WARRANTY RAYPAK RESIDENTIAL SPA HEATERS GAS MODEL 105B GENERAL Raypak, Inc. warrants that all parts of this product will be free from defects in materials and workmanship under normal use and .
Raypak, Inc. , 31111 Agoura Road, Westlake Village, CA 91361-4699 (818) 889-1500 FAX (818) 889-4522 Raypak Canada LTD , 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX (905) 677-8036 Raypak Australia Pty. Ltd , 7 Geddes St.
デバイスRaypak 105Bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Raypak 105Bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRaypak 105Bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Raypak 105Bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Raypak 105Bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Raypak 105Bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRaypak 105Bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Raypak 105Bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRaypak 105Bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。