Manual 2100-563C Page 1 of 40 MC4000 SERIES SOLID ST A TE DUAL UNIT LEAD/LAG CONTROLLER INST ALLA TION INSTRUCTIONS & REPLACEMENT P ARTS LIST Manual No.: 2100-563C Supersedes: 2100-563B File: V ol. III T ab 19 Date: 06-25-12 Bard Manufacturing Company , Inc.
Manual 2100-563C Page 2 of 40 CONTENTS Figures Figure 1 Controller Connections 1-S tage (W A/WL, W**A/ W**L Series) A/C w/No Economizers ..... 17 Figure 2 Controller Connections 2-S tage (W A*S/WL*S Series) A/C - No Economizers .
Manual 2100-563C Page 3 of 40 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-563C Page 4 of 40 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-563C Page 5 of 40 SPECIFICATIONS/FEATURES FOR BASIC CONTROLLER MC4000 Basic Controller •Input power: 18-32 VAC, 60/50Hz, power is supplied from A/C #1 and/or A/C #2 •Isolation circuitr.
Manual 2100-563C Page 6 of 40 SPECIFICATIONS/FEATURES FOR ALARM BOARDS MC4000-A w/Optional Base Alarm Board (Inputs/Outputs) NOTE: If this alarm board was not originally factory installed, it can be field-installed at anytime. Bard part number is AB3000-A.
Manual 2100-563C Page 7 of 40 LOW VOLTAGE FIELD WIRING The MC4000 is powered from the air conditioners that it is controlling, 24 VAC (18-32V) low voltage only. Circuitry in the MC4000 isolates the power supplies of the two air conditioners so that no back feeds or phasing problems can occur.
Manual 2100-563C Page 8 of 40 GENERAL PROGRAMMING OVER VIEW MC4000 CONTROLLER BUTTONS AND FUNCTION On/Off Button 1. Press and release the On/Off button to turn On controller , 4-character display will illuminate and Lead unit LED will light. 2. Press and release the On/Off button to turn Of f controller.
Manual 2100-563C Page 9 of 40 HUMIDITY CONTROL OPTION Note: This function is not available if controller is configured for heat pump. The standard air conditioning system can be adapted to perform deh.
Manual 2100-563C Page 10 of 40 4 th cooling set point is 2F (default setting, user selectable 2-3F) warmer than Stage 3. On a call for 4th S tage cooling the Stage 4 LED comes on solid (no delay), and the lag unit compressor will switch to compressor S tage 2 full capacity operation.
Manual 2100-563C Page 11 of 40 6. 2-S tage Compr essor Units with Newer ECONWMT Economizers (See Note A) 1 st stage cooling set point is the setting (SP) input into the controller .
Manual 2100-563C Page 12 of 40 3 rd cooling set point is 2F (default setting, user selectable 2-3F) warmer than Stage 2. On a call for 3 rd Stage cooling the blower of the lag unit is turned on (if no.
Manual 2100-563C Page 13 of 40 5. 2-S tage Compr essor Units with Newer ECONWMT Economizers (See Note A) 1 st stage cooling set point is the setting (SP) input into the controller .
Manual 2100-563C Page 14 of 40 SPECIFICATIONS FOR OPTIONAL REMOTE COMMUNICATION BOARD CB4000 COMMUNICATION BOARD Note: If this communication board was not originally factory installed it can be field-installed at anytime. Bard part number is CB4000. Either the –A or –B alarm board is required for CB4000 to operate properly.
Manual 2100-563C Page 15 of 40 USER P AGE 1. The designated Admin person can assign up to 9 additional users and set-up as Admin, W rite or Read authority . 2. User Name and password must be assigned, each must be at least 3 characters long, and are case sensitive.
Manual 2100-563C Page 16 of 40 CONTROLLER WIRING The MC4000 can be used for controlling two (2) air conditioners with or without economizers. It can also be configured for two (2) heat pumps without economizers.
Manual 2100-563C Page 17 of 40 m e t s y S e p y T l e d o M s e i r e S o N r e z i m o n o c E B - 0 0 0 4 C M r o A - 0 0 0 4 C M n o i t a c i n u m m o C h t i w r e z i m o n o c E o N – d r a.
Manual 2100-563C Page 18 of 40 FIGURE 2 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERS.
Manual 2100-563C Page 19 of 40 FIGURE 3 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS – NO ECONOMIZER WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 20 of 40 FIGURE 4 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS – NO ECONOMIZERS WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 21 of 40 FIGURE 5 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS.
Manual 2100-563C Page 22 of 40 FIGURE 6 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS.
Manual 2100-563C Page 23 of 40 FIGURE 7 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOAR.
Manual 2100-563C Page 24 of 40 FIGURE 8 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 25 of 40 FIGURE 9 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS.
Manual 2100-563C Page 26 of 40 FIGURE 10 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS.
Manual 2100-563C Page 27 of 40 FIGURE 11 CONTROLLER CONNECTIONS 1-STAGE (WA/WL, W**A/W**L SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 28 of 40 FIGURE 12 CONTROLLER CONNECTIONS 2-STAGE (WA*S/WL*S SERIES) AIR CONDITIONERS WITH (ECONWMT) ECONOMIZERS AND WITH ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 29 of 40 FIGURE 13 CONTROLLER CONNECTIONS HEAT PUMPS – NO ECONOMIZER.
Manual 2100-563C Page 30 of 40 FIGURE 14 CONTROLLER CONNECTIONS HEAT PUMPS – NO ECONOMIZER WITH OPTIONAL ALARM BOARD & CB4000 COMMUNICATION BOARD.
Manual 2100-563C Page 31 of 40 ALARM WIRING Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized.
Manual 2100-563C Page 32 of 40 FIGURE 15 ALARM BOARD CONNECTIONS FOR NORMALLY CLOSED "NC" OPEN-ON-ALARM STRATEGY IMPOR T ANT! LED display boar d is shipped loo se to protect it fr om possible damage during installation of the wiring to main contr oller board and/or the alarm boar d.
Manual 2100-563C Page 33 of 40 FIGURE 16 ALARM BOARD CONNECTIONS FOR NORMALLY OPEN "NO" CLOSE-ON-ALARM STRATEGY IMPOR T ANT! LED display board is shipped loose to pr otect it fr om possible damage during installation of the wiring to main contr oller board and/or the alarm boar d.
Manual 2100-563C Page 34 of 40 PROGRAMMING INSTRUCTIONS To swap lead and lag unit positions, press the ADVANCE button. To enter the Program mode, press the PROGRAM button and release it when the message PROG appears on the display. When in Program mode, the DOWN and UP arrows are used to scroll through the programming steps.
Manual 2100-563C Page 35 of 40 7961-731 Comfort Mode Press “Comfort” button once to reset to 72F/22C Cooling and 68F/20C Heating for 1-hour . Display will flash during override period. Press 2nd-time to cancel during override if desired, or controller will automatically revert to selected SP after 1-hour .
Manual 2100-563C Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS-2954 12 9 3 4 5 7 6 11 2 1 10 8.
Manual 2100-563C Page 37 of 40 . g w D . o N . o N t r a Pn o i t p i r c s e D0 0 0 4 C MA - 0 0 0 4 C MC A - 0 0 0 4 C MB - 0 0 0 4 C MC B - 0 0 0 4 C MA - 0 0 0 3 B AB - 0 0 0 3 B A 0 0 0 4 B C 1 4.
Manual 2100-563C Page 38 of 40 This page intentionally lef t blank..
Manual 2100-563C Page 39 of 40 This page intentionally lef t blank..
Manual 2100-563C Page 40 of 40 This page intentionally lef t blank..
デバイスBard MC4000の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bard MC4000をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBard MC4000の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bard MC4000の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bard MC4000で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bard MC4000を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBard MC4000の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bard MC4000に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBard MC4000デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。