Vectorメーカー6SE70 VCの使用説明書/サービス説明書
ページ先へ移動 of 57
DROM-02069 Quick Startup Gu ide for SIMOVERT MASTERDRIVES 6SE70 VC Vector Control Section 1: Parameterization of Base Dri ve Section 2: Parameterization of Rectifier Section 3: Simovis Trace Setu p Me.
Page 2 Versio n 1.0 March 1, 2000 We reserv e the right to modify functions, technical data, standards, dr awings and parameters. We have che cked the content s of this document to ensure th at they coincide with the described hard ware and software. However, dev iations cannot be completely ruled-out, so we cannot guarantee complete conformance.
Version 1.0 March 1, 2000 Page 3 Note: This Quick Startup Guide is not an autonomous document, but is intended to direct users to the section in the Operating Instructio ns which are important for start -up. Thus, these brief instructions can only be completel y valid when used in conjunction with the Operating Instructions.
Page 4 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 5 Section 1: Parameterization of Base Unit SIMOVERT MASTERDRIVES 6SE70 VC Vector Control 1.1 Power Section Defintion 1.2 Factory Reset 1.3 Basic Start-up 1.3.1 Volts/Hz w ithout encoder feedback 1.3.2 Volts/Hz with encod er feedback 1.
Page 6 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 7 1.1 Power Section Definition Note: Pow er Section is pre -defined at the factory . Powe r Section Definition is required if a new board CUVC board is put in to the drive or boards are switched between uni ts with d ifferent ratings.
Page 8 Versio n 1.0 March 1, 2000 Unit List P070: Parameter Value (P WE) P072: Rated Output Current in Amp s In[A] Frequency Conv erter AC-AC type 3 AC 200V to 230V PWE Order Number In[A ] *1 14 6SE7021-1CA60 10.6 21 6SE7021-3CA60 13.3 27 6SE7021-8CB60 17.
Version 1.0 March 1, 2000 Page 9 Frequency Conv erter AC-AC type 3 AC 380V to 460V PWE A ir Cool ed PWE Water Cooled Order Number In[A ] *1 3 6SE7016-1EA61 6.1 9 6SE7018-0EA61 8.0 11 6SE7021-0EA61 10.2 18 6SE7021-3EB61 13.2 25 6SE7021-8EB61 17.5 35 6SE7022-6EC61 25.
Page 10 Versio n 1.0 March 1, 2000 Frequency Inv erter DC-AC type DC 510V to 650V PWE A ir Cool ed PWE Water Cooled Order Number In [A ] *1 4 6SE7016-1TA61 6.1 10 6SE7018-0TA61 8.0 12 6SE7021-0TA61 10.2 19 6SE7021-3TB61 13.2 26 6SE7021-8TB61 17.5 36 6SE7022-6TC61 25.
Version 1.0 March 1, 2000 Page 11 Frequency Conv erter AC-AC type 3 AC 500V to 575V PWE A ir Cool ed PWE Water Cooled Order Number In[A ] *1 1 6SE7014-5FB61 4.5 5 6SE7016-2FB61 6.2 7 6SE7017-8FB61 7.8 16 6SE7021-1FB61 11.0 23 6SE7021-5FB61 15.1 30 6SE7022-2FC61 22.
Page 12 Versio n 1.0 March 1, 2000 Frequency Inv erter DC-AC type DC 675V to 810V PWE A ir Cool ed PWE Water Cooled Order Number In [A ] *1 2 6SE7014-5UB61 4.5 6 6SE7016-2UB61 6.2 8 6SE7017-8UB61 7.8 17 6SE7021-1UB61 11.0 24 6SE7021-5UB61 15.1 31 6SE7022-2UC61 22.
Version 1.0 March 1, 2000 Page 13 Frequency Inv erter DC-AC type DC 675V to 810V PWE A ir Cool ed PWE Water Cooled Order Number In [A ] *1 161 6SE7043-3UR60 3270.0 165 6SE7044-1UR60 4090.0 169 6SE7044-8UR60 4900.0 173 6SE7045-7UR60 5720.0 177 6SE7046-5UR60 6540.
Page 14 Versio n 1.0 March 1, 2000 DC 890V to 930V PWE A ir Cool ed PWE Water Cooled Order Number In[A ] *1 77 6SE7031-0WG60 97.0 81 6SE7031-2WF60 118.0 89 6SE7031-5WF60 145.0 97 6SE7031-7WG60 171.0 107 6SE7032-1WG60 208.0 111 201 6SE7033-0WJ60 297.0 115 203 6SE7033-5WJ60 354.
Version 1.0 March 1, 2000 Page 15 1.2 Factory Reset P053 = 6 P060 = 2 P366 = 0 P970 = 0 6: Paramete r Changes permitte d via PMU and Seria l Interfa ce (OP1 and PC) 2: Menu Sele ct = Fix ed Settings S.
Page 16 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 17 1.3 Basic Start-up without Motor C onnected to Load 1.3.1 Volts/Hz w ithout Encoder P060 = 5 P071 = ? P095 = ? P097 = ? P101 = 460 P102 = xxx P104 = ? P105 = ? P060=5.
Page 18 Versio n 1.0 March 1, 2000 P106 = ? P107 = 60 P108 = xxxx P115 = 1 P340 = 3 P383 = xxxx P452 = 100 P106 = NEMA Mo tor Nameplated efficien cy (if un known se t =0.
Version 1.0 March 1, 2000 Page 19 P453 = -100 P060 = 1 P128 = xxxx P462 = xxxx P464 = xxxx P443i2= 11 P453 = Max imum Reverse Speed in Percentage (usually -100%) P060 = Return to Paramete r Menu P128 = Max imum Motor Current Options: P128 = P102 P128=1.
Page 20 Versio n 1.0 March 1, 2000 Connect External Wiring as connection diagram . Step 1: Dry set of contacts be tween terminal s X101, p in#1 and pin#5 for Local/Remote Mode Selecti on. Jumper i f not required. Step 2: Dry set of contacts be tween terminal s X101, p in#1 and pin#8 for Coast to Stop Selecti on.
Version 1.0 March 1, 2000 Page 21 Speed value i s determined by P402. A se lection of P40 2=100% w ill be a full speed reference setpoin t. Step 6: Fault Sta tus is prov ided by a 24 Vdc signal at terminal s X101 pin#3 with r espec t to pin#2 . Leav e open if no t required .
Page 22 Versio n 1.0 March 1, 2000 1.3.2 Volts/Hz w ith Encoder Note: Com plete section 1.3.1 b efore op erating th e mot or wi th encoder fee dback. P060 = 5 P100 = 0 P130 = ? P151 = ? P060 = 1 P060=.
Version 1.0 March 1, 2000 Page 23 Additional Conn ection for +15 Vdc E ncoder. Step 10: Set Spe ed Referen ce to 20% . Step 11: Prov ide Start command. No te tha t if Signal A and Signal B are reversed, the motor w ill accele rate rapid ly. Step 12: Conne ct the motor to the load, unl ess the plan is to change to Vector Control.
Page 24 Versio n 1.0 March 1, 2000 1.3.3 Vector Control without Encoder Feedback Note: Com plete section 1.3.1 ( Volts/Hz contr ol wi thout encod er feedback) .
Version 1.0 March 1, 2000 Page 25 P115=5 Wait P115=5 Contr oller Optimiza tion Alarm messag e “A080” w ill appear, and a start command must be issued within 20 second s to perform the test, otherwise P 115 will un set.
Page 26 Versio n 1.0 March 1, 2000 1.3.4 Ve ctor Control with En coder Feedba ck Note: Complete section 1.3. 1 (Volts/Hz control w ithout e ncoder feedb ack), and section 1.3 .3 (Vector co ntrol w ithout enc oder fee dback) Step 10: Op erat e the unco upled motor if sectio ns 1.
Version 1.0 March 1, 2000 Page 27 Wait P115=5 Wait This test w ill adjust the following parameters P103, P120 Wait for di splay to change back to o 009. P115=5 Contr oller Optimiza tion Alarm messag e “A080” w ill appear, and a start command must be issued within 20 second s to perform the test, otherwise P 115 will un set.
Page 28 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 29 1.4 Drive Control Word Function Diagra m s will be refe rred to in brackets with their num ber. Please refer to function di agrams i n the co mpendiu m.
Page 30 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 31 1.5 Communication Bo ard Co nfiguration P060 = 4 CBx Inserted? P711 = ? to P721.1…5 = ? SLB Inserted? P740 = ? P741 = ? P742 = ? P743 = 0 P745 = ? P746 = ? P749.
Page 32 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 33 Section 2: Parameterization of a Rectifer Unit SIMOVERT MASTERDRIVES 6SE70 VC Vector Control 2.0 Power Section Defintion 2.
Page 34 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 35 2.0 Power Section Definition Note: Pow er Section is pre -defined at the factory . Powe r Section Definition is required i f a new board CUR board is p ut into the driv e or boards are sw itched between units with different ratings.
Page 36 Versio n 1.0 March 1, 2000 Unit List P070: Parameter Value (P WE) P075: Rated DC Output Curren t in Amp s In[A] Large Common Rectifier AC-DC type 3 AC 380V to 460V PWE Order Number In[A 103 6SE7038-2EH85-0AA0 821.0 105 6SE7041-0EH85-0AA0 1023.
Version 1.0 March 1, 2000 Page 37 Regenerative Rectifier AC-DC type 3 AC 380V to 460V PWE Air Cool PWE Water Cool Order Number In[A ] 14 6SE7022-1EC85-1AA0 21.0 20 6SE7024-1EC85-1AA0 41.0 31 6SE7028-6EC85-1AA0 86.0 39 6SE7031-7EE85-1AA0 173.0 42 6SE7032-2EE85-1AA0 222.
Page 38 Versio n 1.0 March 1, 2000 Regenerative Rectifier AC-DC type 3 AC 660V to 690V PWE Air Cool PWE Water Cool Order Number In[A ] 36 6SE7031-4HE85-1AA0 140.0 43 6SE7032-2HE85-1AA0 222.0 47 6SE7032-7HE85-1AA0 270.0 53 6SE7034-2HE85-1AA0 420.0 56 6SE7035-3HE85-1AA0 536.
Version 1.0 March 1, 2000 Page 39 2.1 Factory Reset P051 = 3 P052 = 2 P077 = 0 P052 = 0 P052 = 1 P51=3 : Ex port Mode P52=2: Function select “Ini tialization” P077=0 for standard defaul t P052=0 R.
Page 40 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 41 2.2 Basic Start-up (Regenerative Rectifier without Autotransformer) P051 = 2 P053 = 6 P052 = 5 P071 = 460 P320 = 20 P773 = 1.
Page 42 Versio n 1.0 March 1, 2000 P052 = 21 P052 = 0 With DC BUS connected to the COMM ON DC BU S of the sy stem, set P52=21 and prov ide a start command at terminal X101, pin #9 The circui t iden tifica tion te st will take about 10 second s. P052=0 Drive back to ready mode.
Version 1.0 March 1, 2000 Page 43 Connect External Wiring as connection diagram . Step 1: Dry set of contacts be tween terminal s X101, p in#6 and pin#13 for Local/Remo te Mode Sele ction. Jumper if not requ ired. Step 2: Dry set of contacts be tween terminal s X101, p in#6 and pin#10 for Coast to Stop Selection.
Page 44 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 45 2.3 Basic Start-up (Regenerative Rectifier with Autotransformer) P051 = 2 P053 = 6 P052 = 5 P071 = 460 P320 = 20 P773 = 1.
Page 46 Versio n 1.0 March 1, 2000 P571 = 0 P318 = 95 P052 = 21 P052 = 0 P571=0 Selects Au totransformer P318 = 95% Selects percentage of nomin al DC BUS voltage. In cases w here the input line v oltage is dependable a setting o f 100% i s permissible.
Version 1.0 March 1, 2000 Page 47 Section 3: Simovis Trace Setup Method SIMOVERT MASTERDRIVES 6SE70 VC Vector Control.
Page 48 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 49 3.0 Simovis Trace Load Simovis from Vector Control Documentation CD Launch Simovis from Desktop Icon Add a Drive in Simovis Bus Configuration Select USS Bus Address, Drive and SW Version. N ote: Proper S imovis Ca ble must be us ed.
Page 50 Versio n 1.0 March 1, 2000 Select Tr ace from Diagnostics Menu Bar Verify Drive Connection Green Box should be li t up in the l ower left c o rner Double Click Selected Drive to start Sim ovis.
Version 1.0 March 1, 2000 Page 51 A D C B Select Record Se ttings in the Lower Left Corner Select Desired Channels to Record Set the Record In terval and Pre-trigger Select Trigger Channel To Trigger .
Page 52 Versio n 1.0 March 1, 2000 B A C D Select “Function Block Grafics” from the Parameter Menu Bar Select Function N umber 289 Zoom X 2 (with right Mo use click) Set Trigger B inector in U076.01 (i.e. U 076.01 = 18 Din5) Activate B lock U952.89 = 4 A C B D K431 ca n now be used to trigger th e Trace function when Bi nector (i .
Version 1.0 March 1, 2000 Page 53 Go to the Trace Window (Diagnost ics Menu – Trace) Verify Record Settings Start Trace Trigger Tr ace Observe S t atus Me ssage A D C B A C D B.
Page 54 Versio n 1.0 March 1, 2000 A B C Select Dat a Trace A Click Da ta Set to make it A ctive Scale Vertical Axis B Click a nd Drag scale to s hift it up and down. Y ▲ & Y ▼ to ch ange Scal e Scale Horizontal Axis C Click a nd dra g “T ” marker to sh ift Hori zon tal Sc ale .
Version 1.0 March 1, 2000 Page 55 Section 4: When to Re-Tune the Drive SIMOVERT MASTERDRIVES 6SE70 VC Vector Control.
Page 56 Versio n 1.0 March 1, 2000.
Version 1.0 March 1, 2000 Page 57 4.0 Conditions that would merit re-tuning the d rive Hardware addition s made to the drive, su ch as an output rea c tor or a dv/dt fil t er.
デバイスVector 6SE70 VCの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Vector 6SE70 VCをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはVector 6SE70 VCの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Vector 6SE70 VCの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Vector 6SE70 VCで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Vector 6SE70 VCを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はVector 6SE70 VCの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Vector 6SE70 VCに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちVector 6SE70 VCデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。