Improper installation or excessive force will damage the motherboard and modules being installed or removed.
Ensure AC and Battery power is disconnected before installing or removing any boards, modules, or cables.
Fire-Link 3 circuit boards contain static-sensitive components. Operators should always be grounded with a proper wrist strap before handling any boards to remove any static charges from the body. Use static suppressive packaging to protect electronic assemblies.
Installer and operators should use proper conduit and wire isolation to keep Power-Limited and other wiring at least 1/4 inches apart.
The Wireless Input/Output unit mounting plate is compatible with 3” by 2” single gang device boxes, 3-3/4” by 4” double gang boxes, 4” by 2” single gang utility boxes, standard 4” by 4” boxes, and standard 4” octagon boxes.

LT-6212 Rev 0 Nov 2021


Figure 1 Parts of the Wireless Input/Output unit
The Wireless Input/Output unit may be mounted on the wall or ceiling.
Wire the mounting plate to the standard 120 VAC or 240 VAC service with three wires.

Figure 2 Mounting Plate (Front View)


Figure 3 Mounting Plate (Back View)

Figure 4 Mounting the Wireless Input/Output unit on the Mounting Plate

You must configure each Wireless Input/Output unit with both a PAN ID and channel ID.
For all Wireless Input/Output units on the same floor or zone, set the channel ID and PAN ID to the same channel ID and PAN ID as the Zone Controller for that floor or zone. All devices in the same zone should have the same channel ID and PAN ID. Refer to LT-6210 Fire-Link 3 Manual for DIP switch settings.

Connect included red jumper wire to battery terminals to activate batteries.
Figure 5 Location of Wireless Input/Output unit DIP Switches and Connections
Wire notification appliance as show in Figure 6, please refer to LT-6210 Fire-Link 3 Manual for complete instructions.

Arrange wires to allo mounting of applian to WIO without damaging wires.
Arrange wires to allow mounting of notification appliance to WIO without damaging wires.
Figure 6 Wiring the Notification Appliance Mounting Plate to WIO unit