Cancels : II 569C-7 2-4 II 569C-72 -5 8/15/00 IMPORT ANT — READ BEFORE INST ALLING 1. Read an d become fam iliar w ith these install ation instruc tions b efore insta lling t his unit (Fig . 1). 2. Be sure the i nst alla tion conf orms t o all a ppl icab le local a nd na tion al code s.
— 2 — INST ALLA TION NO TE: When inst alli ng any a cces sory i tem, see the m anuf ac- turer’s installation instructions packaged with the accessory . A quali f ie d age nc y must us e f ac t ory - au th orize d ki ts or acc e s- sories when mo dify ing this unit.
— 3 — T a ble 1 — Ph ysical Data LEGEND *Unit is factory supplied w ith holding charge only . †T y pical operating charge with 25 f t of interconnec ting piping. **Storage capacity of condenser coil with coil 80% fu ll of liquid R-22 at 124 F .
— 4 — DIMENSIONS (f t- i n. ) UNIT A B C D E F With Alum inum Coils (Standar d) 569C072 1-6 1 / 2 1-2 3 / 4 —1 - 2 1 / 4 1-4 5 / 16 2-9 5 / 16 569C090 1-8 1-6 1 / 2 2-9 13 / 16 1- 3 2- 5 / 16 3-.
— 5 — B. Filter Drier and Moistu re Indica tor The fil ter d rier i s factor y ins talled. Mois ture in dicat or i s a field-ins talled acc essory and s hould be instal led just aft er liqui d line s hutof f valv e at th e evapo rat or coil . Do no t use a receiver .
— 6 — the current within 10%. Use the formula shown in T able 4, Note 2, to de termine the percent vo ltage imbal ance. Ope rat ion o n impr oper line volta ge or exces sive ph ase im bala nce cons tit utes abu se a nd may cau se dama ge t o elec trica l co mponen ts.
— 7 — T ab le 4 — Ele ctrical Data LEGEND NO TES: 1. In compliance with NEC requirements f or multimotor and combina- tion load equipment (refer to NEC Ar ticles 430 and 440), the over- current protective de vice f or t he unit shall be fuse or HA CR breaker .
— 8 — VI. A CCESSOR Y INST ALLA TION At t his ti me a ny requi red access ories shoul d be in stalled on the un it. Refer to T a ble 5 for a vailabl e ac cessorie s .
— 9 — ST ART -UP I. ST ART -UP AND ADJUSTMENTS A. Chec king Co oling Contr ol Operation Start an d check the uni t for proper co olin g contro l opera tion as fol lo w s: 1.
— 10 — SER VICE I. CLEANING Inspe ct unit interi or at t he beginn ing of each co oling se ason and as ope ratin g condition s require . A. Condenser Coil Inspect co il monthly . Clean conden ser coil an nually , or as requir ed by loca tion and ou tdoor-air conditions.
— 11 — IV . CAP A CITY CONTROL (576B12 0 Only) A suction pressu re-actuated u nloader con trols 2 cy linders and provides capacity control. Unloa ders are fa ctory set (see T able 1) , but may b e field adjus ted: A. Contr ol Set Po int The c ontro l se t po int ( cylin der l oad p oint ) is adju stab le from 0 to 85 psig .
— 12 — VIII. REFRIGERANT SER VICE POR TS Eac h unit has 3 s ervic e port s: on e on th e suc tion li ne , on e on the liq uid line, and on e on the comp resso r discha rge line. Be sure caps on the po rts are tight. IX. H IGH FL O W V AL V ES Located on the compres sor hot gas and suction tubes are High Flow V alves .
— 13 — TROUBLESHOO TING GUIDE NO TE: See Fig. 15 and 16 for component arrangements. SYMPT OM CA USE REMED Y Compressor does not run — Contactor open P ower off . Restore power . Fuses blown. Replace with correct fuses after finding cause and correcting.
Copyright 20 00 Br yant H eating & Coo ling Sy stems 801 CA T ALOG NO. 5356-90 3 LEGEND FOR FIG. 15 AND 16 C— Contactor , Compressor CAP — Capacitor CB — Circuit Breaker CH — Crankcase Hea.
CL-1 ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDO OR: MODE L NO . ____________ ______ _____ _________ __ SERIAL NO . ___ _____ _________ _____ ______ ________ INDOOR: AI R HANDL ER MAN UF ACTUR ER _____ _________ ______________ _____ ______ ________ ______ _____ ___ MODE L NO .
Copyright 20 00 Br yant H eating & Cool ing Sy stems 801 CL-2 CA T ALOG NO . 5356-903 CUT ALONG DOT TED LINE CUT ALONG DO TTED LINE III. ST ART -UP CHECK EV APORA T OR-F AN SPEED AND RECORD .
デバイスBryant 576bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 576bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 576bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 576bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 576bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 576bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 576bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 576bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 576bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。