Thermidistat™ Control Installation, Start-Up, and Operating Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. INDEX Page SAFETY CONSIDERATIONS ...........
INSTALLATION Step 1—Thermidistat Control Location Thermidistat Control should be mounted: • Approximately 5 ft (1.5m) from floor. • Close to or in a frequently used room, preferably on an inside partitioning wall. • On a section of wall without pipes or duct work.
3. A2—for 2-speed air conditioner 4. H2—for 2-speed heat pump 5. dF—for 1-speed dual fuel 6. d2—for 2-speed dual fuel 7. HS—for 1-speed heat pump with Intelligent Heat Staging (3-stage auxiliary heat with 40FK, FK4C, or FV4A Series fan coils.
3. Use up and down buttons to move between F and C on large display. 4. Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.
Option 10—Dual Fuel Equipment All dual fuel installations must be equipped with a high pressure switch to turn off compressor under a high indoor coil pressure condition.
will be supplied, resulting in additional outputs being turned on. If room overheats, specified outputs will not turn off, guaranteeing a sufficiently warm leaving air temperature during defrost.
3. Use up and down buttons to move between OF and ON on large display. Factory default is OF. 4. Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.
TO TEST COOLING AND DEHUMIDIFICATION: Press MODE button until COOL icon turns on. Cooling begins within 10 sec and remains on for 4 minutes. If system is 2-speed, low speed comes on for first 2 minutes, followed by high speed for second 2 minutes. At the end of 4-minute run, cooling stops, and MODE reverts back to OFF.
4. Auto and Fan Humidify The 2 choices of AUTO and FAN can be selected together. This provides both functions simultaneously. 5. Humidify Off The humidify function can be turned off completely. This does not require changing existing set points. To Select Humidification (Between NORMAL, FAN, AUTO, FAN and AUTO, or OFF) (See Table 4.
humidity removal is desired, this should be done, if possible. Fan coils have the capability of removing this off delay, furnaces do not. On FK or FV Fan Coils, set delay tap to 0/0. On standard fan coils, a jumper can be cut to disable off delay. Refer to fan coil Installation Instructions for details.
Vacation Dehumidification Normal Dehumidify, Cool to Dehumidify, and Dehumidify OFF, are all available in vacation mode, and selection of 1 of these can be different from that of occupied. Vacation dehumidification selection and set points are remembered the next time vacation is used.
THERMIDIST A T CONTROL CONFIGURA TION RECORD Date Owner/Operator A) Hardware Configuration Switch A ____ AC/HP Select. (OFF = AC) Switch B ____ 1 or 2-Speed Compressor . (OFF = 1-Speed) Switch C ____ Smar t Recov ery . (OFF = Enable) Switch D ____ Installer T est.
デバイスCarrier Access Thermidistatの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier Access Thermidistatをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier Access Thermidistatの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier Access Thermidistatの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier Access Thermidistatで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier Access Thermidistatを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier Access Thermidistatの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier Access Thermidistatに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier Access Thermidistatデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。