JA
Carrier logo
公式取扱説明書

Carrier GT-S

56 ページ·2.1 MB·ヒートポンプ·PDF·EN
Carrier GT-S
目次 80セクション GEOTHERMAL SPLIT SYSTEMS · GT-S OUTDOOR SPLIT (38WQS) SERIES - SIZES 018-060 · GT-PX INDOOR SPLIT (50YDS) SERIES - SIZES 026-064 · GT-G INDOOR SPLIT (50YCS) SERIES - SIZES 018-060 · … 表示非表示
GEOTHERMAL SPLIT SYSTEMSp.1GT-S OUTDOOR SPLIT (38WQS) SERIES - SIZES 018-060p.1GT-PX INDOOR SPLIT (50YDS) SERIES - SIZES 026-064p.1GT-G INDOOR SPLIT (50YCS) SERIES - SIZES 018-060p.1INDOOR & OUTDOOR SPLIT GEOTHERMALp.1HEATING AND COOLING COMFORT SYSTEMSp.1Geothermal Advantagesp.4Highest Effi ciencyp.4Better Investmentp.4Maximum Comfortp.4Before choosing a geothermal system, many application factors must be evaluated including:p.4Environmentally Friendlyp.4Indoor & Outdoor Split Geothermal Comfort Systemsp.5Closed Loop Systemsp.5Ground Water Systemsp.5GT-PXp.6Rounding Out the Product Linep.6Puron ® Refrigerantp.6Copeland Two-Stage Scroll Compressorp.6Two-Stage Indoor Splitp.7Puron ® Systemsp.7Other New Featuresp.7Service Advantagesp.7Application Flexibilityp.7Factory Qualityp.7Advanced Unit Controls Withp.8Easy Diagnostics And Unit Protection Sentinel Functionsp.8Options & Accessoriesp.8Puron ® HFC 410A Refrigerantp.8Features and Benefi tsp.9Optional Factory Installed Hot Water Genorator With Internal Pumpp.9Three Easy, Lift-out Service Access Panels with Stainless Steel Front Panelp.9Fully Insulated Water and Refrigerant Linesp.9Brass Swivel Water Connectionsp.9Oversized Water Coilp.9Backseating Brass Service Valves with Service Portp.9Low Profi le Control Boxp.9Two-Stage Copeland UltraTech™ Unloading Scroll Compressorp.9GT-GSp.10Operating Effi cienciesp.10Single-Stage Indoor Splitp.11R22 Systemsp.11Epoxy Powder Coat Painted Stackable Cabinetp.11Easy Service Access From Three Sidesp.11Digital Controlsp.11Copeland Scroll Compressorsp.111” Brass Swivel Water Connectionsp.11GT-Sp.12What is the GT-S?p.12Why “Paradigm Shift”?p.12The GT-S Conceptp.12Single-Stage Outdoor Splitp.13Internally Mounted Flow Controllerp.15Copeland Scroll Compressor (Rotary in 018)p.15Powder Coated Galvanized Heavy Gauge Steelp.15Insulated Weather Resistant Cabinetp.15Hot Water Generator Readyp.15Integral Carrying Handlesp.15ARI/ISO/ASHRAE 13256-1p.16GT-PX (50YDS) Performance Data - English (IP) Unitsp.16ARI/ISO/ASHRAE 13256-1 English (IP) Unitsp.16Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pumpp.16Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°Fp.16Model Loadp.16Capacityp.16EER Btuh/Wp.16Btuh COP Capacityp.16Btuh COPp.16Btuhp.16GT-PX (50YDS) Performance Data - Metric (SI) Unitsp.16ARI/ISO/ASHRAE 13256-1 Metric (SI) Unitsp.16Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°Cp.16EER W/Wp.16Watts COP Capacityp.16Watts COPp.16Wattsp.16GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Unitsp.17Modelp.17GT-GS (50YCS) & GT-S (38WQS) Performance Data - Metric (SI) Unitsp.17EERp.17
Page 1 of the Carrier GT-S user manual — GEOTHERMAL SPLIT SYSTEMS
1ページ · クリックして拡大
1ページ
Carrier GT-S — GEOTHERMAL SPLIT SYSTEMS diagram (page 1)
図 1

GEOTHERMAL SPLIT SYSTEMS

GT-S OUTDOOR SPLIT (38WQS) SERIES - SIZES 018-060

GT-PX INDOOR SPLIT (50YDS) SERIES - SIZES 026-064

GT-G INDOOR SPLIT (50YCS) SERIES - SIZES 018-060

INDOOR & OUTDOOR SPLIT GEOTHERMAL

HEATING AND COOLING COMFORT SYSTEMS

DatePageDescription 08/10/05AllFirst Published
Page 2 of the Carrier GT-S user manual — GEOTHERMAL SPLIT SYSTEMS
2ページ · クリックして拡大
2ページ
Page 2 of the Carrier GT-S user manual — GEOTHERMAL SPLIT SYSTEMS
Page 3 of the Carrier GT-S user manual — GEOTHERMAL SPLIT SYSTEMS
3ページ · クリックして拡大
3ページ
Page 3 of the Carrier GT-S user manual — GEOTHERMAL SPLIT SYSTEMS
Page 4 of the Carrier GT-S user manual — Environmentally Friendly
4ページ · クリックして拡大
4ページ

Geothermal Advantages

Agency (EPA) and the De part ment of Energy (DOE). Because it is lowest in CO2 emissions, geothermal tech nol o gy provides a solution to global warming by primarily using the natural energy of the earth. In contrast, traditional space conditioning systems depend upon the exploitation and burning of fossil energy sources with the resultant greenhouse gas emis sions. Also, Puron® HFC 410A refrigerant is used in the GT-PX series equipment for minimum global warming impact and zero ozone depletion.

Geothermal systems transfer heat from a build ing to the earth in the cooling mode, or from the earth to the building in the heating mode. Water is used as the heat transfer medium, either in a closed loop piping system, or by directly pumping well water. By using this stable thermal source, geothermal heat pumps provide energy effi cient comfort year around.

Highest Effi ciency

Better Investment

The extremely high levels of effi ciency are possible because a geothermal heat pump only uses electricity to move heat, not produce it. A geothermal unit typically supplies 4 kilo watts of heat for every kilowatt of elec tric i ty used. Three of these kilo watts of heat come directly from the earth itself, and are clean, free, and renewable. Overall, geothermal technology offers the highest cooling EER’s and heating COP’s available in the industry. Most systems also include a hot water generator, which diverts a portion of the supplied heat to the domestic water heater. This provides a substantial portion of a family’s hot water needs at a very low cost. Overall, geothermal technology offers the highest cooling EER’s and heating COP’s available in the industry.

Low life-cycle costs are provided by the low op er at ing and maintenance costs of geothermal systems, even when the higher initial in stal la tion costs are considered. In new con struc tion, monthly energy savings typically exceed the increased mort gage payments. Therefore, cash fl ow can be positive from the start. In retrofi t systems, a buyer who purchases with cash usually realizes a return on in vest ment well above certifi cate of deposit rates. And, with equip ment life ex ceed ing 20 years, a Carrier geothermal system is a lasting in vest ment.

Electric utilities, recognizing the dual benefi ts of high effi ciency and low electric peak demand, often provide incentives to purchase these systems.

Maximum Comfort

Before choosing a geothermal system, many application factors must be evaluated including:

Geothermal heat pumps also provide higher comfort levels than traditional space conditioning equipment. By using a relatively warm source of heat such as the earth, supply air temperatures are signifi cantly higher in the heating mode than traditional air-source heat pumps. Geo ther mal heat pumps also cycle much less often than fossil furnaces, creating a consistent indoor temperature with comfortable relative humidity.

  • Ground water availability and quality
  • Loop installation costs
  • Land area available
  • Sub-soil conditions
  • Local codes
  • Owner preferences Carrier dealers have the expertise and computer software to determine the best type of system. Many regions have contractors specializing in the in stal la tion of the ground loop portion of the system.

Environmentally Friendly

The environmental advantages of geothermal systems have caught the eye of governmental agencies such as the En vi ron men tal Pro tec tion

Page 5 of the Carrier GT-S user manual — Ground Water Systems
5ページ · クリックして拡大
5ページ

Indoor & Outdoor Split Geothermal Comfort Systems

Closed Loop Systems

Vertical Loops are the ideal choice when available land area is limited. Drilling equipment is used to bore small- diameter vertical holes. Two pipes joined together with a u-bend fi tting are inserted into the vertical bore. Bore hole depth ranges from 100-300 feet per system ton. Bores must be spaced from 10-15 feet apart and properly grouted. The land space required ranges from 100-200 square feet per system ton.

Carrier GT-S — Indoor & Outdoor Split Geothermal Comfort Systems diagram (page 5)
図 2 · Indoor & Outdoor Split Geothermal Comfort Systems

Closed Loop Systems consist of an underground heat exchange network of sealed, high strength poly eth yl ene plastic pipe and a Flow Controller pumping module. When cooling, the loop fl uid temperature will rise, and rejected heat is dissipated into the cooler earth. Con verse ly, while heating, the loop fl uid temperatures fall, and heat is absorbed from the earth. Carrier Flow Controller pumping modules utilize small wattage pumps to circulate the water/antifreeze fl uid within the piping system. The plastic heat exchange loop is closed and ther mal ly fusion-welded at all connections in the same manner as natural gas distribution lines. Closed loops do not require a ground water supply or drain, and they are not subject to mineral build up.

Pond (Lake) Loops are very economical to install when a body of surface water is available, because ex ca va tion costs are mostly eliminated. Coils or “slinky” mats of pipe are simply placed on the bottom of the pond (lake). In most cases, 1/4 to 1/2 acre of water surface, with a min i mum depth of 8-10 feet, is needed for a typical res i dence.

Carrier GT-S — Indoor & Outdoor Split Geothermal Comfort Systems diagram (page 5)
図 3 · Indoor & Outdoor Split Geothermal Comfort Systems

Closed Loops can be installed in vertical or hor i zon tal confi gurations, or submerged in a pond or lake. When designed properly, all three alternatives operate with similar effi ciency. Carrier high density poly eth yl ene plastic pipe is used for all closed loop installations. Pipe con nec tions are heat fused to form joints that are stronger than the pipe itself. Carrier loop piping has a life expectancy in excess of 50 years.

Horizontal Loops are often considered when adequate land space is available. The pipes are placed in trenches, excavated by a backhoe or chain trencher to a depth of 4-6 feet. De pend ing on design, from 1-6 pipes are installed in each trench. Multiple pipe and coiled “slinky” con fi g u ra tions are often used to conserve land re quire ments and reduce overall installed loop costs. Horizontal boring technology can also be used to install u-bend loops 10-15 feet deep with minimal landscaping disruption. Trench lengths range from 100-400 feet per system ton. Trenches must be spaced from 6-10 feet apart. The overall land area required ranges from 750-1,500 square feet per system ton.

Ground Water Systems

Carrier GT-S — Ground Water Systems diagram (page 5)
図 4 · Ground Water Systems

Open loop systems utilize ground water as a direct energy source when good quality water is available at a reasonable pumping depth. A well must have enough capacity to deliver a minimum of 1.5 gpm per system ton during peak op er a tion. Ditches, fi eld tiles, ponds and streams are the most common discharge systems. Re in jec tion or semi-closed recirculation wells can also be utilized in some regions. In ideal con di tions, an open loop ap pli ca tion can be the most eco nom i cal type of system to install.

Carrier GT-S — Ground Water Systems diagram (page 5)
図 5 · Ground Water Systems
Page 6 of the Carrier GT-S user manual — Copeland Two-Stage Scroll Compressor
6ページ · クリックして拡大
6ページ

GT-PX

Rounding Out the Product Line

and allows for steady cooling comfort. Homeowners now have a better, more effi cient way to power their heating and cooling system, raising their level of comfort, while lowering energy bills. So when your customers need a new heating and cooling system, make sure it has the best technology inside – the Copeland Scroll UltraTech™ compressor.

Building upon the overwhelming market success of the GT-PX packaged unit, the split system uses the same components in a more fl exible confi guration. The GT-PX split system compressor section can be coupled with a variety of air handlers and add-on furnace coils to achieve the highest effi ciencies of any split system heat pump on the market today, while still providing the fl exibility of an all-electric or dual fuel system and a remote compressor section location. Split systems are often used in areas where it would be diffi cult to install a packaged unit, such as in an attic or crawl space.

Save with superior effi ciency. Over 40% of summer utility bills can come from the air conditioner compressor operation. A system with the Copeland Scroll UltraTech™ compressor delivers higher effi ciency than any other single compressor system. In fact, systems with UltraTech™ provide up to 60% greater energy effi ciency as compared to 10 SEER systems – which can save homeowners hundreds of dollars a year in energy costs.

Carrier GT-S — GT-PX diagram (page 6)
図 6

Puron ® Refrigerant

  • Puron ® is a non-chlorine based (HFC 410A) refrigerant, that with R-407C and R-134A, is seen as the future of all refrigerants used worldwide. HFC 410A characteristics compared to R22 are:
  • Binary and near azeotropic mixture of 50% R-32 and 50% R-125.
  • Higher effi ciencies (50-60% higher operating pressures).
  • Zero ozone depletion potential and low global warming potential.
  • Virtually no glide. Unlike other alternative refrigerants, the two components in HFC 410A have virtually the same leak rates. Therefore, refrigerant can be added if necessary without recovering the charge.

Take it easy with quieter control. Copeland Scroll UltraTech™ is remarkably quiet at both full- and part-load capacity. In fact, it is up to four times quieter than a reciprocating compressor. Homeowners can enjoy its superior effi ciency and comfort without having to hear the operation.

Learn the beauty of the design. With Copeland Scroll UltraTech™, two internal bypass ports enable the system to run at 67% part-load capacity for better effi ciency and humidity control. Based on demand, the modulation ring is activated, sealing the bypass ports and instantly shifting capacity to 100%. Take advantage of “shift on the fl y” stage changing (no stopping and starting required like other two-stage compressors).

Carrier GT-S — Puron ® Refrigerant diagram (page 6)
図 7 · Puron ® Refrigerant
Carrier GT-S — Puron ® Refrigerant diagram (page 6)
図 8 · Puron ® Refrigerant

Copeland Two-Stage Scroll Compressor

Carrier GT-S — Copeland Two-Stage Scroll Compressor diagram (page 6)
図 9 · Copeland Two-Stage Scroll Compressor

Achieve a greater level of comfort. The Copeland Scroll UltraTech™ provides superior comfort than fi xed-capacity compressors by incorporating a revolutionary two- step design. With a unique 67% part-load capacity step, systems with UltraTech™ maintain precise temperature levels and lower relative humidity. This eliminates uneven peaks and valleys

Choose proven scroll performance. While Copeland Scroll UltraTech™ builds on established scroll technology, it is still a scroll at heart, which means it operates with fewer moving parts, no volumetric effi ciency drop-off or compression leakage. The result is unsurpassed reliability and virtually silent operation for both indoor and outdoor applications.

Page 7 of the Carrier GT-S user manual — Factory Quality
7ページ · クリックして拡大
7ページ

Two-Stage Indoor Split

Puron ® Systems

Other New Features

  • Two-Stage operation for ultra high effi ciencies and unsurpassed comfort.
  • Operating temperature range and high effi ciency allow shorter loops.
  • Optional hot water generator with internal pump generates hot water at considerable savings.
  • Rugged and highly effi cient next generation Copeland UltraTech™ scroll compressors provide the industry’s highest effi ciencies and full capacity with reduced cycling losses.
  • Oversized coaxial tube water-to-refrigerant heat exchangers operate at low liquid pressure drop. Convoluted copper (and optional cupronickel) water tube functions effi ciently at low-fl ow rates and provides freeze-damage resistance.
  • Stylish two-tone look with textured black powder coat paint and stainless steel front access panel.
  • Liftout handle for front access panel.
  • Factory supplied (fi eld-installed) fi lter drier for trouble free reliability.
  • Easy access low profi le horizontal control box.
  • Double isolated compressor for quiet and vibration free operation.
  • Spring-mounted compressor for additional noise suppression.
  • Open Service-Friendly Cabinet (i.e, all components in compressor section can be serviced from the front).

Service Advantages

  • Removable panels - 3 for compressor section (plus removable top panel).
  • Low profi le control box grants easy access to all internal components.
  • Factory supplied (fi eld installed) liquid line fi lter/drier.
  • Brass swivel-type water connections for quick connection and elimination of wrenches or sealants during installation.
  • Bi-directional thermal expansion valve.
  • CXM control features status lights with memory for easy diagnostics.
  • Unit Performance Sentinel alerts homeowner of potential performance issues.
  • Circuit breaker protected 75VA control transformer.
  • High and low pressure service ports on refrigerant circuit.
  • Accurate refrigerant sensing freeze protection.

The GT-PX Series Split System has abundant features and industry leading effi ciency.

Application Flexibility

  • Four Capacities 026, 038, 049, and 064.
  • Extended range operation (20-120°F EWT) and fl ow rates as low as 1.5 gpm per ton.
  • Compressor section match-ups for a variety of air handlers and add-on furnace coils for the ultimate in system and fuel type fl exibility.
  • Precharged compressor section with back-seating service valves for quick installation.
  • Circuit breaker protected loop and hot water generator pumps.
  • Field selectable freeze protection setting for well or loop.
  • Puron ® HFC 410A zero ozone depletion refrigerant.
  • Highest effi ciencies for split systems in ARI/ISO/ ASHRAE/ANSI 13256-1 ratings for heating COP’s, cooling EER’s with low water fl ow rates.

Factory Quality

  • All units are built on our Integrated Process Control Assembly System (IPCS). The IPCS is a unique state of the art manufacturing system that is designed to assure quality of the highest standards of any manufacturer in the water-source industry. Our IPCS system: - Verifi es that the correct components are being assembled.
Page 8 of the Carrier GT-S user manual — Puron ® HFC 410A Refrigerant
8ページ · クリックして拡大
8ページ

GT-PX

  • - Automatically performs special leak tests on all joints. - Conducts pressure tests. - Performs highly detailed run test unparalleled in the HVAC industry. - Automatically disables packaging for a “failed” unit. - Creates computer database for future service analysis and diagnostics from run test results.
  • Heavy gauge galvanized steel cabinets are epoxy powder coated for durable and long-lasting fi nish.
  • All refrigerant brazing is done in a nitrogen atmosphere.
  • All units are deep evacuated to less than 100 microns prior to refrigerant charging.
  • All joints are both helium and halogen leak tested to insure annual leak rate of less than 1/4 ounce.
  • Coaxial heat exchanger, refrigerant suction lines and all water lines are fully insulated to eliminate condensation problems in low temperature applications.
  • Noise Reduction features include: double isolation mounted compressors, compressor springs, insulated compressor compartment, and interior cabinet insulation using 1/2” coated glass fi ber.
  • Safety features include: high pressure and loss of charge to protect the compressor; condensate overfl ow protection; low water temperature limit sensors to safeguard the coaxial heat exchanger and air coil; hot water high limit and low compressor discharge temperature switch provided to shut down the hot water generator when conditions dictate. Fault lockout enables emergency heat and prevents compressor operation until thermostat or circuit breaker has been reset.
Carrier GT-S — GT-PX diagram (page 8)
図 10
Carrier GT-S — GT-PX diagram (page 8)
図 11
Carrier GT-S — GT-PX diagram (page 8)
図 12
Carrier GT-S — GT-PX diagram (page 8)
図 13
Carrier GT-S — GT-PX diagram (page 8)
図 14
Carrier GT-S — GT-PX diagram (page 8)
図 15
Carrier GT-S — GT-PX diagram (page 8)
図 16
Carrier GT-S — GT-PX diagram (page 8)
図 17
Carrier GT-S — GT-PX diagram (page 8)
図 18
Carrier GT-S — GT-PX diagram (page 8)
図 19
Carrier GT-S — GT-PX diagram (page 8)
図 20

Advanced Unit Controls With

Easy Diagnostics And Unit Protection Sentinel Functions

Options & Accessories

Carrier GT-S — Advanced Unit Controls With diagram (page 8)
図 21 · Advanced Unit Controls With
  • Optional hot water generator with internally mounted pump.
  • Optional cupronickel coaxial heat exchanger.
  • Electronic thermostat.
  • Closed loop Flow Controller.
  • Electronic auto-changeover thermostat with 3stage heat, 2-stage cool and indicator LED’s.
  • Hose kits.

Puron ® HFC 410A Refrigerant

Page 9 of the Carrier GT-S user manual — Backseating Brass Service Valves with Service Port
9ページ · クリックして拡大
9ページ

Two-Stage Indoor Split

Puron ® Systems

Features and Benefi ts

Optional Factory Installed Hot Water Genorator With Internal Pump

Three Easy, Lift-out Service Access Panels with Stainless Steel Front Panel

Fully Insulated Water and Refrigerant Lines

Brass Swivel Water Connections

Carrier GT-S — Two-Stage Indoor Split diagram (page 9)
図 22 · Two-Stage Indoor Split
Carrier GT-S — Two-Stage Indoor Split diagram (page 9)
図 23 · Two-Stage Indoor Split
Carrier GT-S — Two-Stage Indoor Split diagram (page 9)
図 24 · Two-Stage Indoor Split
Carrier GT-S — Two-Stage Indoor Split diagram (page 9)
図 25 · Two-Stage Indoor Split
Carrier GT-S — Two-Stage Indoor Split diagram (page 9)
図 26 · Two-Stage Indoor Split

Oversized Water Coil

Carrier GT-S — Oversized Water Coil diagram (page 9)
図 27 · Oversized Water Coil
Carrier GT-S — Oversized Water Coil diagram (page 9)
図 28 · Oversized Water Coil
Carrier GT-S — Oversized Water Coil diagram (page 9)
図 29 · Oversized Water Coil
Carrier GT-S — Oversized Water Coil diagram (page 9)
図 30 · Oversized Water Coil
Carrier GT-S — Oversized Water Coil diagram (page 9)
図 31 · Oversized Water Coil
Carrier GT-S — Oversized Water Coil diagram (page 9)
図 32 · Oversized Water Coil

Backseating Brass Service Valves with Service Port

Low Profi le Control Box

Two-Stage Copeland UltraTech™ Unloading Scroll Compressor

Page 10 of the Carrier GT-S user manual — Service Advantages
10ページ · クリックして拡大
10ページ

GT-GS

Application Flexibility

  • High and low pressure service ports in the refrigerant circuit.
  • Refrigerant sensing freeze protection for more accurate low temperature cut-out.
  • Eight Capacities 018, 024, 030, 036, 042, 048, and 060.
  • Voltage availability in 208-230/60/1.
  • Stackable cabinets.
  • Extended range operation (20-120°F EWT) and fl ow rates as low as 1.5 gpm per ton.
  • Circuit breaker protected loop and hot water gen er a tor pumps.
  • Field selectable low temperature cut-out selection setting for well or loop.
  • Corner located electrical box for wiring access from two sides.
  • Compressor mounting springs “matched” to each compressor for maximum quietness.
  • Narrow cabinet for movement through doorways.
  • Precharged refrigerant circuit with backseating service valves for quick installation.

Factory Quality

  • All units are built on our Integrated Process Control Assembly System (IPCS). The IPCS is a unique state of the art manufacturing system that is designed to assure quality of the highest standards of any manufacturer in the water-source industry. Our IPCS system: - Verifi es that the correct components are being assembled. - Automatically performs special leak tests on all joints. - Conducts pressure tests. - Performs highly detailed run test unparalleled in the HVAC industry. - Automatically disables packaging for a “failed” unit. - Creates computer database for future service analysis and diagnostics from run test results.
  • Heavy gauge galvanized steel cabinets are epoxy powder coated for durable and long-lasting fi nish.
  • All refrigerant brazing is done in a nitrogen atmosphere.
  • All units are deep evacuated to less than 100 microns prior to refrigerant charging.
  • All joints are both helium and halogen leak tested to insure annual leak rate of less than 1/4 ounce.
  • Coaxial heat exchanger, refrigerant suction lines and all water lines are fully insulated to eliminate condensation problems in low temperature applications.
  • Noise Reduction features include: double isolation mounted compressors, compressor springs, insulated compressor compartment, and interior cabinet insulation using 1/2” coated glass fi ber.
  • Safety features include: high pressure and loss of charge to protect the compressor; condensate overfl ow protection; low water temperature limit sensors to safeguard the coaxial heat exchanger and air coil; hot water high limit and low compressor discharge temperature switch provided to shut down the hot water generator when conditions dictate. Fault lockout enables emergency heat and prevents compressor operation until thermostat or circuit breaker has been reset.

Operating Effi ciencies

  • ARI/ASHRAE/ISO 13256-1 ratings for heating COP’s, cooling EER’s and low water fl ow rates.
  • Operating and temperature range allow shorter loops.
  • Optional hot water generator with internal pump generates hot water at considerable savings.
  • Rugged, super quiet, and highly effi cient scroll compressors.
  • Oversized coaxial tube water to refrigerant heat exchangers operate at low liquid pressure drop.
  • Convoluted copper (and optional cupronickel) water tube functions effi ciently at low-fl ow rates and provides freeze-damage resistance.

Service Advantages

  • Removable panels-3 for compressor.
  • Brass swivel-type water and HWG connections for quick connection and elimination of wrenches or sealants during installation.
  • Solid state digital compressor module provides reliable lockout, diagnostic, and time delay functions.
  • High side loss-of-charge sensing reduces nuisance low pressure faults.
  • LED Fault and status indication with memory for easy diagnostics.
  • Designed for front-access service in tight ap pli ca tions.
Page 11 of the Carrier GT-S user manual — Copeland Scroll Compressors
11ページ · クリックして拡大
11ページ

Single-Stage Indoor Split

R22 Systems

Options & Accessories

Carrier GT-S — Single-Stage Indoor Split diagram (page 11)
図 33 · Single-Stage Indoor Split
Carrier GT-S — Single-Stage Indoor Split diagram (page 11)
図 34 · Single-Stage Indoor Split
  • Optional hot water generator with internally mounted pump.
  • Optional cupronickel coaxial heat exchanger.
  • Wide thermostat selection.
  • Closed loop fl ow controller.
  • Hose kits.
Carrier GT-S — Single-Stage Indoor Split diagram (page 11)
図 35 · Single-Stage Indoor Split

Features and Benefi ts

Epoxy Powder Coat Painted Stackable Cabinet

Easy Service Access From Three Sides

Carrier GT-S — Features and Benefi ts diagram (page 11)
図 36 · Features and Benefi ts
Carrier GT-S — Features and Benefi ts diagram (page 11)
図 37 · Features and Benefi ts

Fully Insulated Water and Refrigerant Lines

Digital Controls

Backseating Brass Service Valves with Service Port

Carrier GT-S — Fully Insulated Water and Refrigerant Lines diagram (page 11)
図 38 · Fully Insulated Water and Refrigerant Lines

Copeland Scroll Compressors

1” Brass Swivel Water Connections

Page 12 of the Carrier GT-S user manual — The GT-S Concept
12ページ · クリックして拡大
12ページ

GT-S

What is the GT-S?

In new construction, the GT-S offers many benefi ts over packaged geothermal units: The fl uid loop is kept outside, which keeps large diameter piping, fl ammable antifreezes and fl ushing carts (a large, messy service tool) out of the home. The outdoor compressor means noise and most service activity will remain outside. The indoor air handlers are quiet, require less space and allow less costly ductwork (they don’t have to be side return with canvas collars and plenum lining). Also, a GT-S can utilize a gas furnace as the blower and supplemental heat (dual fuel or add-on) which removes a major consumer barrier in that geothermal has traditionally forced the homeowner to make an all-electric home decision. An add-on application also allows the option of sizing the geothermal component to the cooling load, rather than heating, which may further reduce fi rst costs. The GT-S should be able to tap a larger new construction segment than geothermal currently captures, even when marketed through existing geothermal dealers.

Carrier introduced the industry to the fi rst ever “outdoor” geothermal split system with internal pumping for residential applications. We are giving the consumer choices for unit location! The unit may be installed inside or outside, thereby satisfying the requirements of almost any home. When installed outside, the unit may be placed on an existing pad and easily connected to existing electric service. And with this installation option, the fl uid loop remains outside avoiding extensive installation inside the home. The GT-S is geothermal without the hassle.

Why “Paradigm Shift”?

We have defi ned the paradigm shift as follows: to advance a model of technology beyond the familiar. But what do we mean? Essentially, our GT-S is taking traditional geothermal technology a step further by offering a unique split system design suitable for any home. Home owners can now enjoy all the savings of a geothermal system with lower installation costs and less hassle. More importantly, the GT-S is opening up the previously illusive retrofi t market. Hence, our slogan “From Air to Water...”. The GT-S is a competitive product designed to shift traditional air source homeowners to the benefi ts of water source geothermal technology.

In the replacement market, the GT-S greatly expands the range of suitable geothermal applications. Current geothermal retrofi ts have required a complete change out of all existing equipment, elaborate ductwork modifi cations, complex routing of interior loop fl uid lines including below grade foundation penetrations, upgraded electrical service and unit feeders (110v furnace being changed to 240v heat pump with electric backup), and more. This assumes that a geothermal package unit can even be adapted to fi t into the existing space. This process is expensive and disruptive to the owner (they typically don’t want to change radically from what they have); hence the lack of geothermal retrofi ts existing. In contrast, the GT- S can be installed outside on the same line set and electric service supplying the existing air conditioner or heat pump condensing unit. The loop stays outside. Only the indoor coil might need to be changed on an existing furnace, or possibly the air handler on an older heat pump. The purchase timing could be driven by a fi rst-time central cooling addition; the upgrade replacement of an aging or broken air conditioner, heat pump or furnace; an HVAC change necessitated by a renovation; or an effi ciency upgrade driven by a utility marketing program.

From the utility perspective, the GT-S just about perfectly embodies what the utility industry has been searching for in geothermal: Lower fi rst cost, simple and easy to service, fi ts traditional dealer practices and broad market appeal especially for retrofi t, etc. The GT-S can pull geothermal out of its high end niche into more of a mainstream segment.

The GT-S Concept

The GT-S provides a unique solution to many of the problems associated with single-package geothermal units. In addition, it substantially reduces overall installed costs and perhaps more importantly, opens up the largely untapped retrofi t market (which, for conventional equipment, is over 3 times larger than the new construction market).

Page 13 of the Carrier GT-S user manual — Single-Stage Outdoor Split
13ページ · クリックして拡大
13ページ

Single-Stage Outdoor Split

R22 Systems

The GT-S does not need to be located outside. It can be placed in garages, carports, basements, crawl spaces, etc. This may be important to some homeowners who may be very concerned about outdoor aesthetics. They also can utilize ground water if placed in an appropriate indoor location. Noise is not a problem as the GT-S is extremely quiet (the box is sealed and insulated). The GT-S also has excellent heating and latent cooling capacities compared with competitive high effi ciency geothermal units. In many cases a GT-S produces the heating

output of one size larger competitor unit. And the GT-S is likely to be the highest EER per dollar cost unit available in the geothermal industry today.

The goal for the GT-S Series is based upon application fl exibility, effi ciency, reliability and a solid state microprocessor compressor control, producing a reliable, simple product both easy to service and install. Its effi ciency and application fl exibility make it the “Paradigm” of geothermal heat pumps.

Carrier GT-S — Single-Stage Outdoor Split diagram (page 13)
図 39 · Single-Stage Outdoor Split
Carrier GT-S — Single-Stage Outdoor Split diagram (page 13)
図 40 · Single-Stage Outdoor Split

PVC Condensate · with vented trap · with vented trap

Page 14 of the Carrier GT-S user manual — Service Advantages
14ページ · クリックして拡大
14ページ

GT-S

Application Flexibility

  • High and low pressure service ports in the refrigerant circuit.
  • Refrigerant sensing freeze protection for more accurate low temperature cut-out.
  • Eight Capacities 018, 024, 030, 036, 042, 048, and 060.
  • Voltage availability in 208-230/60/1.
  • Stackable cabinets.
  • Extended range operation (20-120°F EWT) and fl ow rates as low as 2.25 gpm per ton (geothermal closed loop operation).
  • Circuit breaker protected loop and hot water gen er a tor pumps.
  • Field selectable low temperature cut-out selection setting for geothermal closed loop operation.
  • Easily accessible electrical box for wiring.
  • Weather-resistent cabinet.
  • Internally-mounted (fi eld installed) Flow Controller
  • Precharged refrigerant circuit with backseating service valves for quick installation.

Factory Quality

  • All units are built on our Integrated Process Control Assembly System (IPCS). The IPCS is a unique state of the art manufacturing system that is designed to assure quality of the highest standards of any manufacturer in the water-source industry. Our IPCS system: - Verifi es that the correct components are being assembled. - Automatically performs special leak tests on all joints. - Conducts pressure tests. - Performs highly detailed run test unparalleled in the HVAC industry. - Automatically disables packaging for a “failed” unit. - Creates computer database for future service analysis and diagnostics from run test results.
  • Heavy gauge galvanized steel cabinets are epoxy powder coated for durable and long-lasting fi nish.
  • All refrigerant brazing is done in a nitrogen atmosphere.
  • All units are deep evacuated to less than 100 microns prior to refrigerant charging.
  • All joints are both helium and halogen leak tested to insure annual leak rate of less than 1/4 ounce.
  • Coaxial heat exchanger, refrigerant suction lines and all water lines are fully insulated to eliminate condensation problems in low temperature applications.
  • Noise Reduction features include: double isolation mounted compressors, compressor springs, insulated compressor compartment, and interior cabinet insulation using 1/2” coated glass fi ber.
  • Safety features include: high pressure and loss of charge to protect the compressor; condensate overfl ow protection; low water temperature limit sensors to safeguard the coaxial heat exchanger and air coil; hot water high limit and low compressor discharge temperature switch provided to shut down the hot water generator when conditions dictate. Fault lockout enables emergency heat and prevents compressor operation until thermostat or circuit breaker has been reset.

Operating Effi ciencies

  • ARI/ASHRAE/ISO 13256-1 ratings for heating COP’s, cooling EER’s and low water fl ow rates.
  • Operating and temperature range allow shorter loops.
  • Optional remoted-mounted hot water generator with internal pump generates hot water at considerable savings.
  • Rugged, super quiet, and highly effi cient scroll compressors (rotary for size 018).
  • Oversized coaxial tube water to refrigerant heat exchangers operate at low liquid pressure drop.
  • Convoluted copper (and optional cupronickel) water tube functions effi ciently at low-fl ow rates and provides freeze-damage resistance.

Service Advantages

  • Removable side and top panels for easy access to water/refrigerant circuits.
  • Low ambient temperature switch activates loop pump in extreme temperatures.
  • Solid state digital compressor module provides reliable lockout, diagnostic, and time delay functions.
  • High side loss-of-charge sensing reduces nuisance low pressure faults.
  • LED Fault and status indication with memory for easy diagnostics.
Page 15 of the Carrier GT-S user manual — Digital Controls
15ページ · クリックして拡大
15ページ

Single-Stage Outdoor Split

R22 Systems

Options & Accessories

Carrier GT-S — Single-Stage Outdoor Split diagram (page 15)
図 41 · Single-Stage Outdoor Split
Carrier GT-S — Single-Stage Outdoor Split diagram (page 15)
図 42 · Single-Stage Outdoor Split
Carrier GT-S — Single-Stage Outdoor Split diagram (page 15)
図 43 · Single-Stage Outdoor Split
  • Optional remote-mounted hot water generator with internally mounted pump.
  • Optional cupronickel coaxial heat exchanger.
  • Wide thermostat selection.
  • Closed loop fl ow controller.
Carrier GT-S — Single-Stage Outdoor Split diagram (page 15)
図 44 · Single-Stage Outdoor Split
Carrier GT-S — Single-Stage Outdoor Split diagram (page 15)
図 45 · Single-Stage Outdoor Split

Features and Benefi ts

Internally Mounted Flow Controller

Copeland Scroll Compressor (Rotary in 018)

Powder Coated Galvanized Heavy Gauge Steel

Carrier GT-S — Features and Benefi ts diagram (page 15)
図 46 · Features and Benefi ts

Digital Controls

Insulated Weather Resistant Cabinet

Hot Water Generator Ready

BackSeating Brass Service Valves with Service port

Integral Carrying Handles

Page 16 of the Carrier GT-S user manual — ARI/ISO/ASHRAE 13256-1 Metric (SI) Units
16ページ · クリックして拡大
16ページ

ARI/ISO/ASHRAE 13256-1

GT-PX (50YDS) Performance Data - English (IP) Units

ARI/ISO/ASHRAE 13256-1 English (IP) Units

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F

Model Load

Capacity

EER Btuh/W

Capacity

Btuh COP Capacity

EER Btuh/W

Capacity

Btuh COP Capacity

EER Btuh/W

Capacity

Btuh COP

Btuh

Btuh

Btuh

026 Full 24,700 15.0 31,400 5.3 28,600 23.2 25,600 4.7 26,400 18.0 19,500 3.9

026 Part 18,300 16.3 24,300 5.4 22,000 29.4 19,200 4.6 20,800 24.5 16,600 4.1

038 Full 35,900 14.8 44,700 5.0 40,100 21.4 35,900 4.5 37,300 16.7 27,000 3.8

038 Part 24,400 16.5 30,300 5.6 28,000 27.1 24,400 4.6 27,100 23.7 21,400 4.1

049 Full 48,100 14.6 59,400 5.2 53,900 20.9 47,700 4.6 50,200 16.6 37,200 4.0

049 Part 33,300 16.0 42,000 5.4 38,700 26.8 33,800 4.7 37,000 22.8 29,900 4.2

064 Full 56,900 14.5 74,000 4.7 63,800 19.2 58,800 4.3 59,500 15.3 45,700 3.6

064 Part 40,800 15.8 52,700 5.2 46,000 25.7 42,300 4.4 44,800 22.2 37,500 4.0

GT-PX (50YDS) Performance Data - Metric (SI) Units

ARI/ISO/ASHRAE 13256-1 Metric (SI) Units

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C

Model Load

Capacity

EER W/W

Capacity

Watts COP Capacity

EER W/W

Capacity

Watts COP Capacity

EER W/W

Capacity

Watts COP

Watts

Watts

Watts

026 Full 7,239 4.4 9,203 5.3 8,382 6.8 7,503 4.7 7,737 5.3 5,715 3.9

026 Part 5,363 4.8 7,122 5.4 6,448 8.6 5,627 4.6 6,096 7.2 4,865 4.1

038 Full 10,522 4.3 13,101 5.0 11,753 6.3 10,522 4.5 10,932 4.9 7,913 3.8

038 Part 7,151 4.8 8,880 5.6 8,206 7.9 7,151 4.6 7,943 6.9 6,272 4.1

049 Full 14,097 4.3 17,409 5.2 15,797 6.1 13,980 4.6 14,713 4.9 10,903 4.0

049 Part 9,760 4.7 12,309 5.4 11,342 7.9 9,906 4.7 10,844 6.7 8,763 4.2

064 Full 16,676 4.2 21,688 4.7 18,699 5.6 17,233 4.3 17,438 4.5 13,394 3.6

064 Part 11,958 4.6 15,445 5.2 13,482 7.5 12,397 4.4 13,130 6.5 10,991 4.0

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature. Heating capacities based upon 68°F DB, 59°F WB entering air temperature. All ratings based upon 208V operation.

Page 17 of the Carrier GT-S user manual — Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
17ページ · クリックして拡大
17ページ

Indoor & Outdoor Split Geothermal Comfort Systems

ARI/ISO/ASHRAE 13256-1

GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Units

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F

Model

Capacity

EER Btuh/W

Capacity

Btuh COP Capacity

EER Btuh/W

Capacity

Btuh COP Capacity

EER Btuh/W

Capacity

Btuh COP

Btuh

Btuh

Btuh

018 16,600 14.4 20,300 4.8 18,500 22.1 15,500 4.0 17,800 16.2 12,800 3.5

024 23,500 14.5 29,300 4.7 25,700 20.6 22,800 3.9 25,200 16.6 18,600 3.5

030 28,000 14.7 34,000 4.7 30,200 20.8 26,400 3.9 29,800 16.4 21,500 3.5

036 32,800 14.5 39,200 4.4 34,900 20.1 31,900 3.9 34,700 15.9 25,900 3.3

042 39,800 14.1 48,300 4.7 44,100 19.7 37,800 3.9 42,000 15.5 31,700 3.6

048 44,500 14.2 52,500 4.8 47,500 19.3 42,000 3.9 47,400 15.9 35,800 3.6

060 55,100 13.0 72,700 4.6 57,800 17.2 57,100 3.7 57,600 14.2 47,200 3.5

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature. Heating capacities based upon 68°F DB, 59°F WB entering air temperature. All ratings based upon 208V operation.

GT-GS (50YCS) & GT-S (38WQS) Performance Data - Metric (SI) Units

Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump

Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C

Model

Capacity

EER

Capacity

Watts COP Capacity

EER

Capacity

Watts COP Capacity

EER

Capacity

Watts COP

Watts

W/W

Watts

W/W

Watts

W/W

018 4,865 4.2 5,950 4.8 5,422 6.5 4,543 4.0 5,217 4.7 3,751 3.5

024 6,887 4.2 8,587 4.7 7,532 6.0 6,682 3.9 7.386 4.9 5,451 3.5

030 8,206 4.3 9,965 4.7 8,851 6.1 7,737 3.9 8.734 4.8 6,301 3.5

036 9,613 4.2 11,489 4.4 10,229 5.9 9,349 3.9 10,170 4.7 7,591 3.3

042 11,665 4.1 14,156 4.7 12,925 5.8 11,079 3.9 12,309 4.5 9,291 3.6

048 13,042 4.2 15,387 4.8 13,921 5.7 12,309 3.9 13,892 4.7 10,492 3.6

060 16,149 3.8 21,307 4.6 16,940 5.0 16,735 3.7 16,882 4.2 13,834 3.5

Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature. Heating capacities based upon 68°F DB, 59°F WB entering air temperature. All ratings based upon 208V operation.

Page 18 of the Carrier GT-S user manual — WQS = OUDOOR SPLIT SYSTEM
18ページ · クリックして拡大
18ページ

Model Nomenclature

3 2 1 Y D S 0 5

8 6 7 5 4 C 0 8 N

12 11 10 9 1 3 C

GT-PX Nomenclature GT-GS Nomenclature

UNIT TYPE:

PACKAGING:

YDS = INDOOR PURON SPLIT SYSTEM CONDENSING UNIT

1=SINGLE PACK,DOMESTIC

REVISION LEVEL:

SIZE:

0 = CURRENT REVISION

AIRFLOW CONFIGURATION: VOLTAGE:

064 3 = 208V, 230V/1PH/60Hz

UNIT SIZES 018 thru 060

OPTION

RETURN

DISCHARGE

FILTER

HEAT EXCHANGER OPTIONS:

N

NONE

NONE

NONE

C = COPPER WATER COIL

D = COPPER WATER COIL W/HOT WATER GENERATOR N = CUPRO-NICKEL WATER COIL P = CUPRO-NICKEL WATER COIL W/HOT WATER GENERATOR

CONTROL:

C = CXM

Rev.: 08/15/05D

3 2 1 Y C S 0 5

8 6 7 5 4 L 0 4 N

12 11 10 9 1 3 C

UNIT TYPE:

PACKAGING:

YCS = INDOOR SPLIT SYSTEM

1=SINGLE PACK,DOMESTIC

CONDENSING UNIT

REVISION LEVEL:

SIZE:

0 = CURRENT REVISION

AIRFLOW CONFIGURATION: VOLTAGE:

036 3 = 208V, 230V/1PH/60Hz

UNIT SIZES 018 thru 060

OPTION

RETURN

DISCHARGE

FILTER

HEAT EXCHANGER OPTIONS:

N

NONE

NONE

NONE

C = COPPER WATER COIL

D = COPPER WATER COIL W/HOT WATER GENERATOR N = CUPRO-NICKEL WATER COIL P = CUPRO-NICKEL WATER COIL W/HOT WATER GENERATOR

CONTROL:

L = CXM

Rev.: 03/16/04D

38WQS Nomenclature

5 4 3 2 Q S 0 2

7 6 8 10 S S C 3

11 1 2 0 1

W

UNIT TYPE:

PACKAGING:

WQS = OUDOOR SPLIT SYSTEM

1 = SINGLE PACK, DOMESTIC

CONDENSING UNIT

REVISION LEVEL:

SIZE:

1 = CURRENT REVISION

VOLTAGE:

STANDARD:

SS = STANDARD

HEAT EXCHANGER OPTIONS:

N = CUPRO-NICKEL WATER COIL C = COPPER WATER COIL

Rev.: 04/18/04D

Show 6 more labels / short text on this page
038 049 · 024 030 · 048 060 · 024 030 036 · 3=208V,230V/1PH/60Hz · 042 048 060
Page 19 of the Carrier GT-S user manual — ° F
19ページ · クリックして拡大
19ページ

Indoor & Outdoor Split Geothermal Comfort Systems

Heating Cooling

LWT = EWT - HE GPM x 500

LWT = EWT + HR GPM x 500

LC = TC - SC

LAT = EAT + HC CFM x1.08

S/T = SC

LAT (DB) = EAT (DB) - SC CFM x1.08

TC

CFM = airfl ow, cubic feet/minute EWT = entering water temperature, ˚F GPM = water fl ow in US gallons/minute EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) HC = air heating capacity, Mbtuh TC = total cooling capacity, Mbtuh SC = sensible cooling capacity, Mbtuh KW = total power unit input, KiloWatts HR = total heat of rejection, Mbtuh HE = total heat of extraction, Mbtuh

HWC = Hot Water Generator (desuperheater) capacity, Mbtuh WPD = Water coil pressure drop (psi & ft hd) EER = Energy Effi ciency Ratio = BTU output/Watt input COP = Coeffi cient of Performance = BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F LC = latent cooling capacity, Mbtuh S/T = sensible to total cooling ratio

GT-GS & GT-S Performance Correction Factors

Heating Corrections Cooling Corrections Sens Clg Cap Multiplier - Entering DB °F Ent Air DB

Htg Cap Power Heat of

Cap 70 75 80 80.6 85 90 95 Power Heat of

° F

WB ° F

60 1.019 0.896 1.054 60 0.881 0.943 1.067 1.192 1.240 * * * 0.983 0.899

65 1.010 0.948 1.028 65 0.940 0.797 0.952 1.106 1.125 1.261 * * 0.991 0.949

68 1.004 0.980 1.011 66.2 0.976 0.693 0.868 1.043 1.063 1.217 * * 0.997 0.980

70 1.000 1.000 1.000 67 1.000 0.624 0.812 1.000 1.023 1.188 1.343 1.352 1.000 1.000

75 0.997 1.059 0.979 70 1.012 0.697 0.820 0.835 0.944 1.067 1.257 1.002 1.010

80 0.993 1.118 0.957 75 1.024 0.637 0.658 0.817 0.983 1.159 1.005 1.019

Rev. 5/2/00M * Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*" ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

Show 4 more labels / short text on this page
Ent Air · Total Clg · Ext · Rej
Page 20 of the Carrier GT-S user manual — WB ° F
20ページ · クリックして拡大
20ページ

GT-PX

Performance Correction Factors

Airfl ow Correction Factors

TT Full Load Air Flow Corrections

CFM Per Ton of Clg

% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext

240 60 0.925 0.788 0.913 0.922 0.946 1.153 0.896 275 69 0.946 0.829 0.926 0.942 0.959 1.107 0.924 300 75 0.960 0.861 0.937 0.955 0.969 1.078 0.942 325 81 0.972 0.895 0.950 0.968 0.977 1.053 0.959 350 88 0.983 0.930 0.965 0.979 0.985 1.032 0.974 375 94 0.992 0.965 0.982 0.990 0.993 1.014 0.988 400 100 1.000 425 106 1.007 1.033 1.020 1.009 1.006 0.989 1.011 450 113 1.012 1.064 1.042 1.018 1.012 0.982 1.019 475 119 1.016 1.092 1.066 1.025 1.018 0.979 1.027 500 125 1.018 1.116 1.091 1.032 1.022 0.977 1.033 520 130 1.019 1.132 1.112 1.037 1.026 0.975 1.038

TT Part Load Air Flow Corrections

CFM Per Ton of Clg

% of Nominal Total Cap Sens Cap Power Heat of Rej Htg Cap Power Heat of Ext

240 60 0.920 0.781 0.959 0.927 0.946 1.241 0.881 275 69 0.942 0.832 0.964 0.946 0.960 1.163 0.915 300 75 0.956 0.867 0.969 0.959 0.969 1.115 0.937 325 81 0.969 0.901 0.975 0.970 0.978 1.076 0.956 350 88 0.981 0.934 0.982 0.981 0.986 1.043 0.973 375 94 0.991 0.967 0.990 0.991 0.993 1.018 0.988 400 100 1.000 425 106 1.007 1.033 1.011 1.008 1.006 0.990 1.010 450 113 1.013 1.065 1.023 1.015 1.012 0.986 1.017 475 119 1.018 1.098 1.036 1.021 1.017 0.983 1.024 500 125 1.021 1.131 1.051 1.026 1.021 0.981 1.030 520 130 1.023 1.159 1.063 1.030 1.024 0.979 1.034

Entering Air Correction Factors

TT Full Load Entering Air Corrections

Full Load Heating Corrections Full Load Cooling Corrections

Sens Clg Cap Multipliers- Entering DB °F

Cap 60 65 70 75 80 80.6 85 90 95 100 Power Heat of

°F Htg Cap Power Heat of

WB ° F

40 1.052 0.779 1.120 45 0.832 1.346 1.461 1.603 0.946 0.853 45 1.043 0.808 1.102 50 0.850 1.004 1.174 1.357 0.953 0.870 50 1.035 0.841 1.084 55 0.880 0.694 0.902 1.115 1.331 0.964 0.896 55 1.027 0.877 1.065 60 0.922 0.646 0.875 1.103 1.329 1.356 0.977 0.932 60 1.019 0.915 1.045 65 0.975 0.639 0.869 1.096 1.123 1.320 0.993 0.979 65 1.010 0.957 1.023 66.2 0.990 0.582 0.812 1.039 1.066 1.262 1.482 0.997 0.991 68 1.004 0.982 1.010 67 1.000 0.545 0.774 1.000 1.027 1.223 1.444 1.000 1.000 70 1.000 1.000 1.000 70 1.040 0.630 0.853 0.880 1.075 1.297 1.517 1.011 1.035 75 0.989 1.045 0.974 75 1.117 0.601 0.627 0.821 1.046 1.275 1.510 1.033 1.101 80 0.976 1.093 0.946 Rev.: 03/29/04 * Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*" ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

*

TT Part Load Entering Air Corrections

Part Load Heating Corrections Part Load Cooling Corrections

Sens Clg Cap Multipliers- Entering DB °F

Cap 60 65 70 75 80 80.6 85 90 95 100 Power Heat of

°F Htg Cap Power Heat of

WB ° F

40 1.084 0.732 1.161 45 0.876 1.286 1.302 1.389 0.981 0.895 45 1.073 0.764 1.140 50 0.883 1.002 1.099 1.241 0.985 0.901 50 1.060 0.802 1.117 55 0.903 0.706 0.871 1.060 1.271 0.989 0.918 55 1.046 0.846 1.090 60 0.935 0.617 0.844 1.079 1.319 1.349 0.993 0.945 60 1.031 0.893 1.061 65 0.979 0.595 0.849 1.098 1.128 1.342 0.998 0.982 65 1.016 0.945 1.031 66.2 0.991 0.531 0.789 1.040 1.070 1.284 1.522 0.999 0.993 68 1.006 0.978 1.013 67 1.000 0.486 0.747 1.000 1.030 1.245 1.481 1.000 1.000 70 1.000 1.000 1.000 70 1.035 0.583 0.842 0.873 1.090 1.327 1.552

* 1.003 1.030 75 0.984 1.058 0.968 75 1.105 0.552 0.584 0.811 1.057 1.290 1.510 1.008 1.088 80 0.968 1.117 0.936 Rev.: 03/29/04 * Sensible capacity equals total capacity (no latent capacity) at conditions shown as "*" ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

Show 12 more labels / short text on this page
Airflow Cooling Heating · Airflow Cooling Heating · Ent Air · Total Clg · Ent Air DB · Rej · Ext · Ent Air · Total Clg · Ent Air DB · Rej · Ext
Page 21 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
21ページ · クリックして拡大
21ページ

Two-Stage Indoor Split

50YDS026 Part Load With FV4003

Puron ® Systems

530 CFM Nominal (Rated) Airfl ow Cooling, 530 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 7.00 4.5 10.4 450 10.9 1.17 7.2 92.4 2.73 1.9 20 7.00 4.5 10.4 530 11.1 1.12 7.4 89.4 2.90 1.7 30 3.50 1.2 2.8 450 22.1 11.7 0.62 24.1 35.6 - 13.2 1.23 9.1 97.2 3.15 2.0 30 3.50 1.2 2.8 530 22.5 12.5 0.63 24.6 35.7 - 13.4 1.18 9.4 93.4 3.33 1.7 30 5.75 2.9 6.7 450 22.3 11.7 0.61 24.3 36.6 - 13.8 1.23 9.7 98.4 3.29 2.0 30 5.75 2.9 6.7 530 22.7 12.5 0.62 24.8 36.6 - 14.0 1.18 10.0 94.5 3.48 1.7 30 7.00 4.1 9.5 450 22.4 11.7 0.60 24.4 37.3 - 14.0 1.23 9.9 98.8 3.34 1.9 30 7.00 4.1 9.5 530 22.8 12.5 0.61 24.9 37.4 - 14.2 1.18 10.2 94.8 3.53 1.7 40 3.50 1.1 2.5 450 22.6 12.6 0.70 24.9 32.3 - 16.0 1.32 11.6 102.9 3.55 2.0 40 3.50 1.1 2.5 530 23.0 13.5 0.71 25.4 32.4 - 16.2 1.27 11.9 98.3 3.74 1.8 40 5.75 2.6 6.0 450 22.8 12.6 0.65 24.9 35.1 - 16.7 1.32 12.3 104.4 3.71 2.0 40 5.75 2.6 6.0 530 23.2 13.5 0.66 25.4 35.2 - 16.9 1.27 12.6 99.5 3.90 1.7 40 7.00 3.6 8.3 450 22.9 12.6 0.65 25.0 35.2 - 16.9 1.32 12.5 104.8 3.75 2.0 40 7.00 3.6 8.3 530 23.3 13.5 0.66 25.5 35.3 - 17.1 1.27 12.8 99.9 3.95 1.7 50 3.50 1.0 2.3 450 22.1 12.9 0.79 24.8 28.0 0.7 18.6 1.38 14.1 108.3 3.95 2.1 50 3.50 1.0 2.3 530 22.5 13.8 0.80 25.3 28.1 0.7 18.9 1.32 14.5 103.0 4.20 1.8 50 5.75 2.4 5.5 450 22.4 12.9 0.74 24.8 30.3 0.6 19.4 1.38 14.8 109.9 4.12 2.1 50 5.75 2.4 5.5 530 22.8 13.8 0.75 25.3 30.4 0.6 19.7 1.32 15.2 104.4 4.37 1.8 50 7.00 3.4 7.9 450 22.4 12.9 0.72 24.8 31.1 0.6 19.6 1.38 15.0 110.3 4.16 2.0 50 7.00 3.4 7.9 530 22.8 13.8 0.73 25.3 31.2 0.6 19.9 1.32 15.4 104.8 4.42 1.8 60 3.50 1.0 2.3 450 21.1 12.8 0.90 24.1 23.4 1.1 21.3 1.44 16.4 113.8 4.34 2.2 60 3.50 1.0 2.3 530 21.5 13.7 0.92 24.6 23.4 1.1 21.6 1.38 16.9 107.7 4.59 1.9 60 5.75 2.3 5.3 450 21.6 13.0 0.83 24.4 26.0 1.0 22.2 1.45 17.3 115.7 4.49 2.2 60 5.75 2.3 5.3 530 22.0 13.9 0.85 24.9 25.9 1.0 22.5 1.39 17.8 109.3 4.74 1.9 60 7.00 3.2 7.4 450 21.7 13.0 0.81 24.4 26.8 0.9 22.4 1.45 17.5 116.1 4.53 2.1 60 7.00 3.2 7.4 530 22.1 13.9 0.83 24.9 26.6 0.9 22.7 1.39 18.0 109.7 4.79 1.9 70 3.50 0.9 2.1 450 19.6 12.4 1.03 23.2 19.0 1.4 24.0 1.48 19.0 119.4 4.75 2.3 70 3.50 0.9 2.1 530 20.0 13.3 1.05 23.6 19.0 1.5 24.3 1.42 19.5 112.5 5.02 2.0 70 5.75 2.1 4.9 450 20.3 12.6 0.95 23.5 21.4 1.3 24.8 1.49 19.9 121.0 4.88 2.3 70 5.75 2.1 4.9 530 20.7 13.5 0.97 24.0 21.3 1.4 25.2 1.43 20.4 114.0 5.16 2.0 70 7.00 3.0 6.9 450 20.5 12.7 0.93 23.6 22.0 1.2 25.1 1.49 20.0 121.6 4.94 2.2 70 7.00 3.0 6.9 530 20.9 13.6 0.95 24.1 22.0 1.2 25.5 1.43 20.6 114.5 5.23 1.9 80 3.50 0.8 1.8 450 18.1 11.9 1.18 22.1 15.3 1.8 26.6 1.52 21.4 124.7 5.13 2.4 80 3.50 0.8 1.8 530 18.5 12.7 1.20 22.5 15.4 1.8 27.0 1.46 22.0 117.2 5.42 2.1 80 5.75 2.0 4.6 450 18.8 12.1 1.10 22.6 17.1 1.6 27.7 1.53 22.4 127.0 5.31 2.4 80 5.75 2.0 4.6 530 19.2 13.0 1.12 23.0 17.1 1.7 28.1 1.47 23.0 119.1 5.60 2.1 80 7.00 2.8 6.5 450 19.0 12.2 1.08 22.7 17.6 1.5 28.0 1.54 22.7 127.6 5.33 2.4 80 7.00 2.8 6.5 530 19.4 13.1 1.10 23.1 17.6 1.5 28.4 1.48 23.3 119.6 5.62 2.1 85 3.50 0.8 1.8 450 17.4 11.6 1.26 21.7 13.8 2.0 28.0 1.55 22.7 127.6 5.29 2.5 85 3.50 0.8 1.8 530 17.7 12.4 1.28 22.1 13.8 2.0 28.4 1.49 23.3 119.6 5.59 2.2 85 5.75 1.9 4.4 450 18.1 11.9 1.18 22.1 15.3 1.8 29.1 1.56 23.7 129.9 5.47 2.5 85 5.75 1.9 4.4 530 18.4 12.7 1.20 22.5 15.3 1.9 29.5 1.50 24.4 121.5 5.76 2.2 85 7.00 2.7 6.2 450 18.2 12.0 1.15 22.2 15.8 1.7 29.4 1.56 24.0 130.5 5.52 2.5 85 7.00 2.7 6.2 530 18.6 12.8 1.17 22.6 15.9 1.7 29.8 1.50 24.7 122.1 5.82 2.2 90 3.50 0.8 1.8 450 16.7 11.4 1.34 21.3 12.5 2.4 29.4 1.57 23.9 130.5 5.49 2.6 90 3.50 0.8 1.8 530 17.0 12.2 1.36 21.7 12.5 2.5 29.8 1.51 24.6 122.1 5.78 2.2 90 5.75 1.9 4.4 450 17.2 11.6 1.26 21.5 13.7 1.9 30.6 1.60 25.1 133.0 5.61 2.6 90 5.75 1.9 4.4 530 17.5 12.4 1.28 21.9 13.7 2.0 31.0 1.53 25.8 124.2 5.94 2.2 90 7.00 2.7 6.2 450 17.4 11.7 1.23 21.6 14.1 1.8 30.9 1.60 25.4 133.6 5.66 2.5 90 7.00 2.7 6.2 530 17.7 12.5 1.25 22.0 14.2 1.8 31.3 1.53 26.1 124.7 6.00 2.2 100 3.50 0.8 1.8 450 15.1 10.8 1.50 20.3 10.1 2.4 0 100 3.50 0.8 1.8 530 15.4 11.6 1.53 20.7 10.1 2.5 0 100 5.75 1.8 4.2 450 15.6 11.0 1.43 20.5 10.9 2.2 0 100 5.75 1.8 4.2 530 15.9 11.8 1.46 20.9 10.9 2.3 0 100 7.00 2.6 6.0 450 15.8 11.0 1.40 20.6 11.3 2.0 100 7.00 2.6 6.0 530 16.1 11.8 1.43 21.0 11.3 2.0 110 3.50 0.7 1.6 450 13.9 10.7 1.70 19.8 8.2 2.7 0 110 3.50 0.7 1.6 530 14.2 11.4 1.73 20.2 8.2 2.8 0 110 5.75 1.7 3.9 450 14.2 10.6 1.63 19.8 8.7 2.5 0 110 5.75 1.7 3.9 530 14.5 11.3 1.66 20.2 8.7 2.5 0 110 7.00 2.5 5.8 450 14.4 10.7 1.60 19.9 9.0 2.2 0 110 7.00 2.5 5.8 530 14.7 11.4 1.63 20.3 9.0 2.3 0 120 3.50 0.7 1.6 450 12.9 10.6 1.95 19.6 6.6 3.0 120 3.50 0.7 1.6 530 13.2 11.3 1.99 20.0 6.6 3.0 120 5.75 1.7 3.9 450 13.2 10.5 1.85 19.5 7.1 2.7 0 120 5.75 1.7 3.9 530 13.5 11.2 1.88 19.9 7.2 2.7 0 120 7.00 2.4 5.5 450 13.2 10.5 1.82 19.5 7.3 2.4 0 120 7.00 2.4 5.5 530 13.5 11.2 1.85 19.9 7.3 2.5 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 22 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
22ページ · クリックして拡大
22ページ

GT-PX

50YDS026 Full Load With FV4003

850 CFM Nominal (Rated) Airfl ow Cooling, 850 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 8.00 5.6 12.9 750 14.9 1.54 9.8 88.4 2.84 2.4 20 8.00 5.6 12.9 880 15.1 1.49 10.1 85.9 2.97 2.1 30 4.00 1.5 3.5 750 29.4 18.4 1.09 32.6 27.0 - 17.6 1.60 12.4 91.7 3.22 2.4 30 4.00 1.5 3.5 880 29.9 19.8 1.15 33.8 26.0 - 17.9 1.55 12.7 88.8 3.38 2.1 30 6.00 3.1 7.2 750 29.6 18.4 1.04 32.6 28.5 - 18.5 1.61 13.2 92.8 3.37 2.4 30 6.00 3.1 7.2 880 30.1 19.8 1.10 33.8 27.4 - 18.8 1.56 13.5 89.8 3.53 2.1 30 8.00 5.1 11.8 750 29.8 18.5 1.01 32.7 29.5 - 18.9 1.62 13.5 93.3 3.42 2.4 30 8.00 5.1 11.8 880 30.3 19.9 1.07 33.9 28.3 - 19.2 1.57 13.9 90.2 3.58 2.1 40 4.00 1.4 3.2 750 29.2 19.0 1.18 32.7 24.7 - 21.1 1.67 15.5 96.0 3.70 2.5 40 4.00 1.4 3.2 880 29.7 20.4 1.25 33.9 23.8 - 21.4 1.62 15.9 92.5 3.87 2.2 40 6.00 2.8 6.5 750 29.4 19.0 1.13 32.8 26.0 - 22.1 1.69 16.4 97.3 3.83 2.5 40 6.00 2.8 6.5 880 29.9 20.4 1.19 34.0 25.1 - 22.4 1.64 16.8 93.6 4.00 2.2 40 8.00 4.6 10.6 750 29.5 19.0 1.10 32.8 26.8 - 22.6 1.71 16.9 97.9 3.87 2.4 40 8.00 4.6 10.6 880 30.0 20.4 1.16 34.0 25.9 - 22.9 1.66 17.3 94.1 4.04 2.1 50 4.00 1.3 3.0 750 28.4 19.2 1.30 32.3 21.8 1.1 24.2 1.74 18.3 99.9 4.08 2.6 50 4.00 1.3 3.0 880 28.9 20.6 1.37 33.5 21.1 1.1 24.6 1.69 18.8 95.9 4.27 2.3 50 6.00 2.6 6.0 750 28.9 19.2 1.23 32.6 23.5 1.0 25.2 1.78 19.3 101.1 4.15 2.6 50 6.00 2.6 6.0 880 29.4 20.7 1.30 33.8 22.6 1.0 25.6 1.72 19.8 96.9 4.36 2.3 50 8.00 4.3 9.9 750 29.1 19.2 1.19 32.7 24.5 0.9 25.8 1.80 19.7 101.9 4.20 2.6 50 8.00 4.3 9.9 880 29.6 20.7 1.26 33.9 23.5 0.9 26.2 1.74 20.2 97.6 4.41 2.2 60 4.00 1.2 2.8 750 27.2 18.9 1.42 31.7 19.2 1.5 27.1 1.83 20.9 103.5 4.34 2.8 60 4.00 1.2 2.8 880 27.7 20.3 1.50 32.9 18.5 1.6 27.5 1.77 21.5 98.9 4.55 2.5 60 6.00 2.5 5.8 750 27.9 19.2 1.34 32.1 20.8 1.3 28.1 1.86 21.8 104.7 4.43 2.8 60 6.00 2.5 5.8 880 28.4 20.6 1.42 33.3 20.0 1.4 28.5 1.80 22.4 100.0 4.64 2.4 60 8.00 4.0 9.2 750 28.2 19.2 1.32 32.2 21.4 1.1 28.7 1.87 22.3 105.4 4.50 2.7 60 8.00 4.0 9.2 880 28.7 20.7 1.39 33.4 20.6 1.2 29.1 1.81 22.9 100.6 4.71 2.4 70 4.00 1.1 2.5 750 25.8 18.4 1.56 30.9 16.5 2.0 29.8 1.90 23.3 106.8 4.60 3.1 70 4.00 1.1 2.5 880 26.3 19.8 1.65 32.0 15.9 2.1 30.2 1.84 23.9 101.8 4.81 2.7 70 6.00 2.3 5.3 750 26.6 18.8 1.49 31.4 17.9 1.8 30.7 1.93 24.2 107.9 4.66 3.0 70 6.00 2.3 5.3 880 27.1 20.2 1.57 32.5 17.3 1.8 31.2 1.87 24.8 102.8 4.89 2.6 70 8.00 3.8 8.8 750 27.0 19.0 1.44 31.6 18.8 1.5 31.3 1.95 24.6 108.6 4.70 3.0 70 8.00 3.8 8.8 880 27.5 20.4 1.52 32.7 18.1 1.5 31.8 1.89 25.3 103.5 4.93 2.6 80 4.00 1.0 2.3 750 24.4 17.9 1.72 29.9 14.2 2.6 32.1 1.97 25.4 109.6 4.78 3.4 80 4.00 1.0 2.3 880 24.8 19.2 1.82 31.0 13.6 2.6 32.6 1.91 26.1 104.3 5.00 2.9 80 6.00 2.2 5.1 750 25.2 18.2 1.64 30.4 15.4 2.2 33.3 2.01 26.4 111.1 4.86 3.3 80 6.00 2.2 5.1 880 25.6 19.6 1.73 31.5 14.8 2.3 33.8 1.95 27.1 105.6 5.08 2.9 80 8.00 3.5 8.1 750 25.5 18.4 1.59 30.6 16.0 1.9 33.8 2.03 26.9 111.7 4.88 3.3 80 8.00 3.5 8.1 880 26.0 19.8 1.68 31.7 15.5 1.9 34.3 1.97 27.6 106.1 5.10 2.8 85 4.00 1.0 2.3 750 23.5 17.5 1.82 29.4 12.9 2.9 33.3 2.01 26.5 111.1 4.86 3.6 85 4.00 1.0 2.3 880 23.9 18.8 1.92 30.5 12.4 3.0 33.8 1.95 27.2 105.6 5.08 3.1 85 6.00 2.1 4.9 750 24.4 17.9 1.72 29.9 14.2 2.5 34.5 2.04 27.5 112.6 4.96 3.5 85 6.00 2.1 4.9 880 24.8 19.2 1.82 31.0 13.6 2.6 35.0 1.98 28.2 106.8 5.18 3.1 85 8.00 3.4 7.9 750 24.8 18.0 1.68 30.1 14.8 2.1 35.1 2.06 28.0 113.3 4.99 3.5 85 8.00 3.4 7.9 880 25.2 19.4 1.77 31.2 14.2 2.1 35.6 2.00 28.7 107.5 5.22 3.0 90 4.00 1.0 2.3 750 22.7 17.1 1.90 29.0 11.9 3.2 34.5 2.04 27.6 112.6 4.96 3.7 90 4.00 1.0 2.3 880 23.1 18.4 2.01 30.0 11.5 3.3 35.0 1.98 28.3 106.8 5.18 3.3 90 6.00 2.1 4.9 750 23.6 17.6 1.81 29.4 13.0 2.8 35.7 2.08 28.5 114.1 5.03 3.7 90 6.00 2.1 4.9 880 24.0 18.9 1.91 30.5 12.6 2.8 36.2 2.02 29.3 108.1 5.25 3.2 90 8.00 3.4 7.9 750 24.0 17.8 1.76 29.6 13.6 2.3 36.3 2.11 29.0 114.8 5.04 3.6 90 8.00 3.4 7.9 880 24.4 19.1 1.86 30.7 13.1 2.3 36.8 2.04 29.8 108.7 5.29 3.1 100 4.00 1.0 2.3 750 21.1 16.5 2.11 28.1 10.0 3.9 0 100 4.00 1.0 2.3 880 21.5 17.7 2.23 29.1 9.6 4.0 100 6.00 2.0 4.6 750 21.9 16.8 2.00 28.5 11.0 3.4 0 100 6.00 2.0 4.6 880 22.3 18.1 2.11 29.5 10.6 3.4 0 100 8.00 3.2 7.4 750 22.3 17.0 1.95 28.7 11.4 2.8 0 100 8.00 3.2 7.4 880 22.7 18.3 2.06 29.7 11.0 2.8 0 110 4.00 0.9 2.1 750 19.7 15.9 2.34 27.4 8.4 4.7 0 110 4.00 0.9 2.1 880 20.0 17.1 2.47 28.4 8.1 4.8 0 110 6.00 1.9 4.4 750 20.3 16.2 2.21 27.7 9.2 4.0 110 6.00 1.9 4.4 880 20.7 17.4 2.34 28.7 8.8 4.1 0 110 8.00 3.1 7.2 750 20.6 16.4 2.16 27.8 9.5 3.3 0 110 8.00 3.1 7.2 880 21.0 17.6 2.28 28.8 9.2 3.4 0 120 4.00 0.9 2.1 750 18.3 15.5 2.59 27.0 7.1 5.6 0 120 4.00 0.9 2.1 880 18.6 16.7 2.74 28.0 6.8 5.7 0 120 6.00 1.8 4.2 750 18.9 15.7 2.46 27.1 7.7 4.7 0 120 6.00 1.8 4.2 880 19.2 16.9 2.60 28.1 7.4 4.8 0 120 8.00 3.0 6.9 750 19.2 15.8 2.40 27.2 8.0 3.9 0 120 8.00 3.0 6.9 880 19.5 17.0 2.54 28.2 7.7 4.0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 23 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
23ページ · クリックして拡大
23ページ

Two-Stage Indoor Split

50YDS038 Part Load With FV4005

Puron ® Systems

700 CFM Nominal (Rated) Airfl ow Cooling, 700 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 8.00 4.7 10.9 600 16.5 1.64 11.1 95.5 2.95 2.4 20 8.00 4.7 10.9 700 16.7 1.57 11.4 92.1 3.12 2.1 30 4.00 1.2 2.8 600 27.5 17.0 0.90 30.5 30.6 - 18.1 1.66 12.8 97.9 3.20 2.4 30 4.00 1.2 2.8 700 28.0 18.2 0.92 31.1 30.4 - 18.4 1.59 13.1 94.3 3.39 2.1 30 6.00 2.6 6.0 600 27.8 17.0 0.85 30.6 32.7 - 18.8 1.66 13.3 99.0 3.32 2.4 30 6.00 2.6 6.0 700 28.3 18.2 0.87 31.2 32.5 - 19.1 1.59 13.7 95.3 3.52 2.1 30 8.00 4.5 10.4 600 28.0 17.1 0.83 30.7 33.7 - 19.1 1.67 13.7 99.5 3.35 2.4 30 8.00 4.5 10.4 700 28.5 18.3 0.85 31.3 33.5 - 19.4 1.60 14.1 95.7 3.55 2.1 40 4.00 1.1 2.5 600 28.2 18.4 1.01 31.6 27.9 - 20.7 1.69 15.2 101.9 3.59 2.5 40 4.00 1.1 2.5 700 28.7 19.7 1.03 32.2 27.9 - 21.0 1.62 15.6 97.8 3.80 2.2 40 6.00 2.6 6.0 600 28.4 18.4 0.93 31.6 30.5 - 21.5 1.69 16.0 103.2 3.73 2.5 40 6.00 2.6 6.0 700 28.9 19.7 0.95 32.2 30.4 - 21.8 1.62 16.4 98.8 3.94 2.1 40 8.00 4.4 10.2 600 28.5 18.4 0.90 31.6 31.7 - 22.0 1.69 16.4 104.0 3.82 2.4 40 8.00 4.4 10.2 700 29.1 19.7 0.92 32.2 31.6 - 22.3 1.62 16.8 99.5 4.03 2.1 50 4.00 1.0 2.3 600 28.0 19.0 1.14 31.8 24.6 0.8 23.4 1.72 17.7 106.1 3.99 2.6 50 4.00 1.0 2.3 700 28.5 20.3 1.16 32.4 24.6 0.8 23.7 1.65 18.2 101.3 4.21 2.2 50 6.00 2.5 5.8 600 28.3 19.1 1.05 31.8 27.0 0.7 24.3 1.72 18.6 107.5 4.14 2.6 50 6.00 2.5 5.8 700 28.8 20.4 1.07 32.4 26.9 0.8 24.7 1.65 19.1 102.7 4.39 2.2 50 8.00 4.2 9.7 600 28.4 19.1 1.01 31.9 28.1 0.7 24.9 1.73 19.1 108.4 4.22 2.5 50 8.00 4.2 9.7 700 29.0 20.4 1.03 32.5 28.2 0.7 25.3 1.66 19.6 103.5 4.47 2.2 60 4.00 0.9 2.1 600 26.9 19.1 1.29 31.3 20.9 1.3 26.6 1.75 20.7 111.0 4.45 2.7 60 4.00 0.9 2.1 700 27.4 20.4 1.31 31.9 20.9 1.3 27.0 1.68 21.3 105.7 4.71 2.3 60 6.00 2.4 5.5 600 27.6 19.2 1.19 31.6 23.2 1.2 27.8 1.76 21.8 112.9 4.63 2.7 60 6.00 2.4 5.5 700 28.1 20.5 1.21 32.2 23.2 1.2 28.2 1.69 22.4 107.3 4.89 2.3 60 8.00 4.1 9.5 600 27.9 19.2 1.14 31.7 24.5 1.1 28.4 1.76 22.4 113.8 4.73 2.6 60 8.00 4.1 9.5 700 28.4 20.5 1.16 32.3 24.5 1.1 28.8 1.69 23.0 108.1 4.99 2.3 70 4.00 0.8 1.8 600 25.5 18.5 1.45 30.5 17.6 1.8 29.9 1.78 23.7 116.1 4.92 2.8 70 4.00 0.8 1.8 700 26.0 19.8 1.48 31.1 17.6 1.8 30.3 1.71 24.4 110.1 5.19 2.5 70 6.00 2.3 5.3 600 26.3 18.8 1.35 30.9 19.5 1.7 31.2 1.79 25.1 118.1 5.11 2.8 70 6.00 2.3 5.3 700 26.8 20.1 1.37 31.5 19.6 1.7 31.7 1.72 25.8 111.9 5.40 2.4 70 8.00 4.0 9.2 600 26.7 19.0 1.30 31.1 20.5 1.5 31.9 1.80 25.8 119.2 5.19 2.8 70 8.00 4.0 9.2 700 27.2 20.3 1.32 31.7 20.6 1.5 32.4 1.73 26.5 112.9 5.49 2.4 80 4.00 0.7 1.6 600 23.9 17.8 1.64 29.5 14.6 2.3 33.2 1.83 27.1 121.2 5.32 3.0 80 4.00 0.7 1.6 700 24.4 19.0 1.67 30.1 14.6 2.3 33.7 1.75 27.8 114.6 5.64 2.6 80 6.00 2.3 5.3 600 24.8 18.2 1.52 30.0 16.3 2.1 34.9 1.84 28.6 123.9 5.56 3.0 80 6.00 2.3 5.3 700 25.3 19.5 1.55 30.6 16.3 2.1 35.4 1.76 29.4 116.8 5.89 2.6 80 8.00 3.9 9.0 600 25.2 18.4 1.46 30.2 17.3 1.9 35.8 1.84 29.5 125.2 5.70 2.9 80 8.00 3.9 9.0 700 25.7 19.7 1.49 30.8 17.2 1.9 36.3 1.76 30.3 118.0 6.04 2.6 85 4.00 0.7 1.6 600 23.2 17.5 1.74 29.0 13.3 2.5 35.0 1.84 28.7 124.0 5.57 3.2 85 4.00 0.7 1.6 700 23.6 18.7 1.77 29.6 13.3 2.6 35.5 1.76 29.5 117.0 5.91 2.7 85 6.00 2.2 5.1 600 23.9 17.8 1.62 29.5 14.8 2.3 36.8 1.86 30.4 126.8 5.80 3.2 85 6.00 2.2 5.1 700 24.4 19.1 1.65 30.1 14.8 2.3 37.3 1.78 31.2 119.3 6.14 2.7 85 8.00 3.8 8.8 600 24.4 18.0 1.56 29.7 15.6 2.1 37.8 1.86 31.3 128.3 5.96 3.0 85 8.00 3.8 8.8 700 24.9 19.3 1.59 30.3 15.7 2.1 38.3 1.78 32.2 120.7 6.31 2.65 90 4.00 0.7 1.6 600 22.4 17.1 1.84 28.6 12.2 2.7 36.9 1.86 30.5 126.9 5.81 3.2 90 4.00 0.7 1.6 700 22.8 18.3 1.87 29.1 12.2 2.8 37.4 1.78 31.3 119.5 6.16 2.8 90 6.00 2.1 4.9 600 23.2 17.5 1.71 29.0 13.6 2.5 38.7 1.88 32.2 129.7 6.03 3.2 90 6.00 2.1 4.9 700 23.6 18.7 1.74 29.6 13.6 2.5 39.3 1.80 33.1 122.0 6.40 2.8 90 8.00 3.7 8.5 600 23.5 17.7 1.65 29.2 14.2 2.2 39.8 1.88 33.3 131.4 6.20 3.1 90 8.00 3.7 8.5 700 24.0 18.9 1.68 29.8 14.3 2.3 40.4 1.80 34.2 123.4 6.58 2.7 100 4.00 0.6 1.4 600 20.9 16.6 2.05 27.9 10.2 3.1 0 100 4.00 0.6 1.4 700 21.3 17.8 2.09 28.4 10.2 3.2 0 100 6.00 2.1 4.9 600 21.6 16.8 1.92 28.2 11.3 2.8 0 100 6.00 2.1 4.9 700 22.0 18.0 1.96 28.7 11.2 2.9 0 100 8.00 3.6 8.3 600 22.0 17.0 1.86 28.4 11.8 2.5 0 100 8.00 3.6 8.3 700 22.4 18.2 1.89 28.9 11.9 2.6 0 110 4.00 0.6 1.4 600 19.8 16.4 2.29 27.6 8.6 3.5 0 110 4.00 0.6 1.4 700 20.2 17.6 2.33 28.1 8.7 3.5 0 110 6.00 2.0 4.6 600 20.3 16.4 2.15 27.7 9.4 3.1 0 110 6.00 2.0 4.6 700 20.7 17.6 2.19 28.2 9.5 3.2 0 110 8.00 3.4 7.9 600 20.6 16.5 2.08 27.7 9.9 2.8 0 110 8.00 3.4 7.9 700 21.0 17.7 2.12 28.2 9.9 2.9 0 120 4.00 0.5 1.2 600 19.0 16.2 2.51 27.7 7.6 3.8 0 120 4.00 0.5 1.2 700 19.4 17.3 2.56 28.2 7.6 3.9 0 120 6.00 1.9 4.4 600 19.4 16.4 2.39 27.7 8.1 3.4 0 120 6.00 1.9 4.4 700 19.8 17.6 2.43 28.2 8.1 3.5 0 120 8.00 3.3 7.6 600 19.6 16.5 2.35 27.7 8.3 3.1 0 120 8.00 3.3 7.6 700 20.0 17.7 2.39 28.2 8.4 3.1 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 24 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
24ページ · クリックして拡大
24ページ

GT-PX

50YDS038 Full Load With FV4005

1200 CFM Nominal (Rated) Airfl ow Cooling, 1200 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 9.00 5.9 13.6 1000 23.3 2.25 15.9 91.6 3.04 2.9 20 9.00 5.9 13.6 1200 23.6 2.18 16.3 88.2 3.17 2.5 30 4.50 1.7 3.9 1000 41.8 21.7 1.66 46.7 25.2 - 25.7 2.32 18.0 93.8 3.25 3.0 30 4.50 1.7 3.9 1200 42.5 23.3 1.75 48.4 24.3 - 26.1 2.25 18.5 90.1 3.40 2.6 30 6.75 3.3 7.6 1000 41.9 21.7 1.54 46.5 27.2 - 26.9 2.34 19.1 94.9 3.37 3.0 30 6.75 3.3 7.6 1200 42.6 23.3 1.63 48.2 26.1 - 27.3 2.27 19.6 91.1 3.52 2.6 30 9.00 5.7 13.2 1000 42.1 21.7 1.50 46.4 28.1 - 27.6 2.36 19.7 95.6 3.43 2.9 30 9.00 5.7 13.2 1200 42.8 23.3 1.58 48.1 27.1 - 28.0 2.29 20.2 91.6 3.58 2.5 40 4.50 1.5 3.5 1000 41.0 23.0 1.81 46.5 22.7 - 29.9 2.44 21.7 97.7 3.59 3.1 40 4.50 1.5 3.5 1200 41.7 24.7 1.91 48.2 21.8 - 30.3 2.36 22.3 93.4 3.76 2.7 40 6.75 3.2 7.4 1000 41.6 23.1 1.69 46.7 24.6 - 31.2 2.47 23.0 98.9 3.70 3.0 40 6.75 3.2 7.4 1200 42.3 24.8 1.79 48.4 23.6 - 31.7 2.39 23.6 94.5 3.89 2.6 40 9.00 5.4 12.5 1000 41.8 23.1 1.64 46.7 25.5 - 32.0 2.49 23.8 99.6 3.77 3.0 40 9.00 5.4 12.5 1200 42.5 24.8 1.73 48.4 24.6 - 32.5 2.41 24.4 95.1 3.95 2.6 50 4.50 1.3 3.0 1000 39.8 23.9 1.98 45.9 20.1 1.4 34.1 2.55 25.5 101.6 3.92 3.2 50 4.50 1.3 3.0 1200 40.5 25.7 2.09 47.6 19.4 1.4 34.6 2.47 26.2 96.7 4.11 2.8 50 6.75 3.1 7.2 1000 40.7 24.2 1.85 46.4 22.0 1.2 35.9 2.60 27.1 103.2 4.05 3.2 50 6.75 3.1 7.2 1200 41.4 26.0 1.96 48.1 21.1 1.2 36.4 2.52 27.8 98.1 4.23 2.8 50 9.00 5.2 12.0 1000 41.1 24.3 1.79 46.5 23.0 1.0 36.8 2.62 28.0 104.1 4.12 3.1 50 9.00 5.2 12.0 1200 41.8 26.1 1.89 48.2 22.1 1.0 37.3 2.54 28.7 98.8 4.30 2.7 60 4.50 1.2 2.8 1000 38.3 24.6 2.16 45.1 17.7 1.9 38.6 2.69 29.5 105.7 4.21 3.5 60 4.50 1.2 2.8 1200 39.0 26.5 2.28 46.7 17.1 1.9 39.2 2.61 30.3 100.2 4.40 3.0 60 6.75 3.0 6.9 1000 39.4 25.1 2.03 45.7 19.4 1.6 40.7 2.75 31.4 107.7 4.34 3.4 60 6.75 3.0 6.9 1200 40.1 27.0 2.14 47.4 18.7 1.7 41.3 2.66 32.2 101.9 4.55 3.0 60 9.00 5.0 11.6 1000 39.9 25.3 1.96 46.0 20.4 1.4 41.8 2.79 32.3 108.7 4.39 3.4 60 9.00 5.0 11.6 1200 40.6 27.2 2.07 47.7 19.6 1.4 42.4 2.70 33.2 102.7 4.60 2.9 70 4.50 1.1 2.5 1000 36.5 25.2 2.36 44.1 15.5 2.5 43.4 2.84 33.7 110.2 4.48 3.8 70 4.50 1.1 2.5 1200 37.2 27.1 2.49 45.7 14.9 2.6 44.0 2.75 34.6 104.0 4.69 3.3 70 6.75 2.9 6.7 1000 37.8 25.8 2.21 44.8 17.1 2.2 45.7 2.92 35.9 112.3 4.59 3.7 70 6.75 2.9 6.7 1200 38.5 27.7 2.34 46.4 16.5 2.2 46.4 2.83 36.8 105.8 4.81 3.2 70 9.00 4.8 11.1 1000 38.4 25.9 2.14 45.2 17.9 1.8 47.1 2.96 37.0 113.6 4.66 3.7 70 9.00 4.8 11.1 1200 39.1 27.9 2.26 46.8 17.3 1.9 47.8 2.87 38.0 106.9 4.88 3.2 80 4.50 1.0 2.3 1000 34.7 25.5 2.58 43.0 13.4 3.3 48.4 3.01 38.1 114.8 4.71 4.2 80 4.50 1.0 2.3 1200 35.3 27.4 2.73 44.6 12.9 3.3 49.1 2.92 39.1 107.9 4.93 3.6 80 6.75 2.8 6.5 1000 36.0 26.1 2.42 43.7 14.9 2.8 51.1 3.11 40.6 117.3 4.82 4.1 80 6.75 2.8 6.5 1200 36.6 28.1 2.56 45.3 14.3 2.8 51.9 3.01 41.7 110.0 5.05 3.6 80 9.00 4.5 10.4 1000 36.6 26.4 2.35 44.1 15.6 2.3 52.7 3.16 42.0 118.8 4.89 4.0 80 9.00 4.5 10.4 1200 37.3 28.4 2.48 45.7 15.0 2.4 53.5 3.06 43.1 111.3 5.12 3.5 85 4.50 1.0 2.3 1000 33.7 25.6 2.73 42.6 12.3 3.7 51.0 3.11 40.4 117.2 4.81 4.4 85 4.50 1.0 2.3 1200 34.3 27.5 2.88 44.1 11.9 3.8 51.8 3.01 41.5 110.0 5.04 3.6 85 6.75 2.8 6.5 1000 35.0 26.2 2.55 43.2 13.7 3.2 54.0 3.21 43.1 120.0 4.93 4.4 85 6.75 2.8 6.5 1200 35.6 28.2 2.69 44.8 13.2 3.2 54.8 3.11 44.2 112.3 5.16 3.6 85 9.00 4.5 10.4 1000 35.7 26.6 2.46 43.5 14.5 2.6 55.8 3.27 44.5 121.7 5.00 4.5 85 9.00 4.5 10.4 1200 36.3 28.6 2.60 45.1 14.0 2.4 56.6 3.17 45.7 113.7 5.23 3.7 90 4.50 0.9 2.1 1000 32.7 25.7 2.86 42.1 11.4 4.1 53.6 3.20 42.8 119.6 4.91 4.6 90 4.50 0.9 2.1 1200 33.3 27.6 3.02 43.6 11.0 4.2 54.4 3.10 43.9 112.0 5.14 4.0 90 6.75 2.7 6.2 1000 34.0 26.4 2.67 42.7 12.7 3.5 57.0 3.32 45.6 122.8 5.03 4.6 90 6.75 2.7 6.2 1200 34.6 28.4 2.82 44.2 12.3 3.6 57.8 3.22 46.8 114.6 5.26 4.0 90 9.00 4.4 10.2 1000 34.7 26.7 2.58 43.0 13.4 2.9 58.7 3.38 47.2 124.4 5.09 4.5 90 9.00 4.4 10.2 1200 35.3 28.7 2.73 44.6 12.9 3.0 59.6 3.28 48.4 116.0 5.33 3.9 100 4.50 0.8 1.8 1000 30.7 25.8 3.16 41.2 9.7 5.0 100 4.50 0.8 1.8 1200 31.2 27.7 3.34 42.7 9.3 5.1 0 100 6.75 2.6 6.0 1000 31.9 26.5 2.95 41.7 10.8 4.3 0 100 6.75 2.6 6.0 1200 32.5 28.5 3.12 43.2 10.4 4.3 0 100 9.00 4.2 9.7 1000 32.6 26.8 2.86 42.0 11.4 3.5 0 100 9.00 4.2 9.7 1200 33.2 28.8 3.02 43.5 11.0 3.6 0 110 4.50 0.8 1.8 1000 28.8 25.9 3.52 40.5 8.2 6.0 110 4.50 0.8 1.8 1200 29.3 27.8 3.72 42.0 7.9 6.1 0 110 6.75 2.5 5.8 1000 30.0 26.5 3.28 40.9 9.1 5.1 0 110 6.75 2.5 5.8 1200 30.5 28.5 3.47 42.4 8.8 5.2 0 110 9.00 4.0 9.2 1000 30.6 26.9 3.17 41.1 9.7 4.2 0 110 9.00 4.0 9.2 1200 31.1 28.9 3.35 42.6 9.3 4.3 0 120 4.50 0.7 1.6 1000 27.0 25.9 3.94 40.3 6.9 7.2 0 120 4.50 0.7 1.6 1200 27.5 27.9 4.16 41.8 6.6 7.3 0 120 6.75 2.5 5.8 1000 28.1 26.5 3.66 40.4 7.7 6.1 0 120 6.75 2.5 5.8 1200 28.6 28.5 3.87 41.9 7.4 6.2 0 120 9.00 3.8 8.8 1000 28.7 26.9 3.54 40.5 8.1 5.0 120 9.00 3.8 8.8 1200 29.2 28.9 3.74 42.0 7.8 5.1 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 25 of the Carrier GT-S user manual — EWT
25ページ · クリックして拡大
25ページ

Two-Stage Indoor Split

50YDS049 Part Load With FV4006

Puron ® Systems

1000 CFM Nominal (Rated) Airfl ow Cooling, 1000 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

EWT

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 11.00 4.0 9.2 850 22.3 2.16 15.3 94.3 3.03 3.3 20 11.00 4.0 9.2 1000 22.6 2.07 15.7 90.9 3.20 2.8 30 5.50 1.1 2.5 850 37.1 22.5 1.19 41.1 31.2 - 24.5 2.23 17.1 96.7 3.22 3.4 30 5.50 1.1 2.5 1000 37.8 24.1 1.21 41.9 31.2 - 24.9 2.14 17.6 93.1 3.41 2.9 30 8.25 2.3 5.3 850 37.3 22.5 1.12 41.1 33.3 - 25.3 2.24 18.0 97.6 3.31 3.3 30 8.25 2.3 5.3 1000 38.0 24.1 1.14 41.9 33.3 - 25.7 2.15 18.5 93.8 3.50 2.9 30 11.00 3.9 9.0 850 37.5 22.5 1.08 41.2 34.7 - 25.8 2.25 18.5 98.1 3.36 3.3 30 11.00 3.9 9.0 1000 38.2 24.1 1.10 42.0 34.7 - 26.2 2.16 19.0 94.3 3.55 2.9 40 5.50 1.0 2.3 850 38.8 24.6 1.35 43.4 28.7 - 28.1 2.32 20.4 100.6 3.55 3.5 40 5.50 1.0 2.3 1000 39.6 26.3 1.37 44.2 28.9 - 28.5 2.22 21.0 96.4 3.76 3.0 40 8.25 2.2 5.1 850 39.1 24.7 1.26 43.5 31.0 - 29.4 2.33 21.6 102.0 3.70 3.4 40 8.25 2.2 5.1 1000 39.9 26.4 1.28 44.3 31.2 - 29.8 2.23 22.2 97.6 3.92 3.0 40 11.00 3.7 8.5 850 39.2 24.7 1.24 43.5 31.6 - 30.0 2.34 22.3 102.7 3.76 3.4 40 11.00 3.7 8.5 1000 40.0 26.4 1.26 44.3 31.7 - 30.4 2.24 22.9 98.1 3.98 2.9 50 5.50 0.9 2.1 850 38.4 25.1 1.47 43.4 26.1 0.9 32.1 2.40 24.1 105.0 3.92 3.6 50 5.50 0.9 2.1 1000 39.1 26.9 1.50 44.2 26.1 0.9 32.6 2.30 24.8 100.2 4.15 3.1 50 8.25 2.1 4.9 850 38.7 25.2 1.39 43.5 27.8 0.8 33.6 2.41 25.6 106.6 4.09 3.5 50 8.25 2.1 4.9 1000 39.5 27.0 1.42 44.3 27.8 0.9 34.1 2.31 26.3 101.6 4.33 3.1 50 11.00 3.6 8.3 850 38.8 25.2 1.38 43.6 28.1 0.8 34.4 2.42 26.4 107.5 4.17 3.5 50 11.00 3.6 8.3 1000 39.6 27.0 1.41 44.4 28.1 0.8 34.9 2.32 27.1 102.3 4.41 3.0 60 5.50 0.8 1.8 850 37.2 25.4 1.70 43.0 21.9 1.6 36.3 2.48 27.9 109.5 4.29 3.7 60 5.50 0.8 1.8 1000 37.9 27.2 1.73 43.8 21.9 1.6 36.8 2.38 28.7 104.1 4.53 3.3 60 8.25 2.0 4.6 850 37.9 25.5 1.59 43.3 23.8 1.4 38.0 2.49 29.7 111.4 4.47 3.7 60 8.25 2.0 4.6 1000 38.6 27.3 1.62 44.1 23.8 1.5 38.6 2.39 30.5 105.7 4.73 3.2 60 11.00 3.5 8.1 850 38.1 25.6 1.54 43.4 24.7 1.3 39.0 2.50 30.6 112.5 4.57 3.7 60 11.00 3.5 8.1 1000 38.8 27.4 1.57 44.2 24.7 1.3 39.6 2.40 31.4 106.7 4.84 3.2 70 5.50 0.8 1.8 850 35.1 24.9 1.90 41.7 18.5 2.2 40.4 2.57 31.7 114.0 4.61 3.9 70 5.50 0.8 1.8 1000 35.8 26.7 1.94 42.5 18.5 2.2 41.0 2.46 32.6 108.0 4.88 3.4 70 8.25 2.0 4.6 850 36.1 25.2 1.79 42.3 20.2 2.0 42.4 2.59 33.7 116.2 4.80 3.9 70 8.25 2.0 4.6 1000 36.8 27.0 1.82 43.1 20.2 2.0 43.0 2.48 34.6 109.8 5.08 3.4 70 11.00 3.3 7.6 850 36.6 25.4 1.73 42.5 21.2 1.8 43.6 2.60 34.7 117.5 4.91 3.9 70 11.00 3.3 7.6 1000 37.3 27.2 1.76 43.3 21.2 1.8 44.2 2.49 35.7 110.9 5.20 3.4 80 5.50 0.7 1.6 850 32.7 24.1 2.14 39.9 15.3 2.8 44.5 2.66 35.4 118.5 4.90 4.2 80 5.50 0.7 1.6 1000 33.3 25.8 2.18 40.7 15.3 2.8 45.1 2.55 36.4 111.8 5.18 3.6 80 8.25 1.9 4.4 850 33.8 24.6 2.01 40.7 16.8 2.5 46.6 2.69 37.5 120.8 5.08 4.1 80 8.25 1.9 4.4 1000 34.5 26.3 2.05 41.5 16.8 2.6 47.3 2.58 38.5 113.8 5.37 3.6 80 11.00 3.2 7.4 850 34.4 24.8 1.94 41.0 17.7 2.3 47.7 2.70 38.5 122.0 5.18 4.1 80 11.00 3.2 7.4 1000 35.1 26.5 1.98 41.8 17.7 2.3 48.4 2.59 39.6 114.8 5.48 3.6 85 5.50 0.7 1.6 850 31.4 23.6 2.27 39.1 13.8 3.1 46.3 2.71 37.1 120.4 5.01 4.4 85 5.50 0.7 1.6 1000 32.0 25.3 2.31 39.8 13.9 3.1 47.0 2.60 38.1 113.5 5.30 3.8 85 8.25 1.9 4.4 850 32.6 24.1 2.13 39.8 15.3 2.8 48.5 2.74 39.1 122.8 5.19 4.3 85 8.25 1.9 4.4 1000 33.2 25.8 2.17 40.6 15.3 2.9 49.2 2.63 40.2 115.6 5.48 3.8 85 11.00 3.1 7.2 850 33.2 24.3 2.07 40.1 16.0 2.5 49.6 2.76 40.2 124.0 5.27 4.3 85 11.00 3.1 7.2 1000 33.8 26.0 2.11 40.9 16.0 2.6 50.3 2.65 41.3 116.6 5.56 3.7 90 5.50 0.7 1.6 850 30.0 23.2 2.40 38.2 12.5 3.3 48.2 2.76 38.8 122.5 5.12 4.5 90 5.50 0.7 1.6 1000 30.6 24.8 2.44 38.9 12.5 3.4 48.9 2.65 39.9 115.3 5.41 3.9 90 8.25 1.8 4.2 850 31.2 23.6 2.26 39.0 13.8 3.0 50.4 2.81 40.8 124.9 5.26 4.4 90 8.25 1.8 4.2 1000 31.8 25.3 2.30 39.7 13.8 3.1 51.1 2.69 41.9 117.3 5.57 3.9 90 11.00 3.1 7.2 850 31.8 23.9 2.19 39.3 14.5 2.7 51.5 2.83 41.9 126.1 5.33 4.4 90 11.00 3.1 7.2 1000 32.4 25.6 2.23 40.1 14.5 2.8 52.2 2.71 43.0 118.3 5.65 3.8 100 5.50 0.7 1.6 850 27.4 22.2 2.69 36.6 10.2 3.8 0 100 5.50 0.7 1.6 1000 27.9 23.8 2.74 37.3 10.2 3.9 0 100 8.25 1.8 4.2 850 28.5 22.7 2.53 37.2 11.3 3.5 0 100 8.25 1.8 4.2 1000 29.1 24.3 2.58 37.9 11.3 3.5 0 100 11.00 3.0 6.9 850 29.1 22.9 2.46 37.6 11.8 3.1 0 100 11.00 3.0 6.9 1000 29.7 24.5 2.51 38.3 11.8 3.2 0 110 5.50 0.6 1.4 850 25.0 21.5 3.01 35.3 8.3 4.3 0 110 5.50 0.6 1.4 1000 25.5 23.0 3.07 36.0 8.3 4.3 0 110 8.25 1.7 3.9 850 26.0 21.9 2.86 35.7 9.1 3.9 0 110 8.25 1.7 3.9 1000 26.5 23.4 2.91 36.4 9.1 3.9 0 110 11.00 2.8 6.5 850 26.5 22.1 2.77 36.0 9.6 3.5 0 110 11.00 2.8 6.5 1000 27.0 23.6 2.82 36.7 9.6 3.5 0 120 5.50 0.6 1.4 850 23.2 21.3 3.40 34.7 6.8 4.7 0 120 5.50 0.6 1.4 1000 23.6 22.8 3.46 35.4 6.8 4.8 0 120 8.25 1.7 3.9 850 23.8 21.3 3.21 34.8 7.4 4.2 0 120 8.25 1.7 3.9 1000 24.3 22.8 3.27 35.5 7.4 4.3 0 120 11.00 2.7 6.2 850 24.2 21.4 3.12 34.9 7.8 3.8 0 120 11.00 2.7 6.2 1000 24.7 22.9 3.18 35.6 7.8 3.9 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 26 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
26ページ · クリックして拡大
26ページ

GT-PX

50YDS049 Full Load With FV4006

1650 CFM Nominal (Rated) Airfl ow Cooling, 1650 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 12.00 4.8 11.1 1400 31.8 2.89 22.2 91.0 3.22 3.8 20 12.00 4.8 11.1 1650 32.3 2.80 22.8 88.1 3.38 3.3 30 6.00 1.3 3.0 1400 55.8 35.9 2.23 62.5 25.0 - 34.7 3.00 24.7 92.9 3.39 4.0 30 6.00 1.3 3.0 1650 56.8 38.6 2.36 64.8 24.1 - 35.2 2.91 25.4 89.8 3.55 3.5 30 9.00 2.7 6.2 1400 56.2 36.0 2.11 62.5 26.6 - 36.3 3.04 26.1 94.0 3.50 3.9 30 9.00 2.7 6.2 1650 57.2 38.7 2.23 64.8 25.7 - 36.8 2.95 26.8 90.7 3.66 3.4 30 12.00 4.6 10.6 1400 56.6 36.0 2.03 62.6 27.9 - 37.2 3.07 26.9 94.6 3.55 3.9 30 12.00 4.6 10.6 1650 57.6 38.7 2.15 64.9 26.8 - 37.7 2.97 27.6 91.2 3.72 3.3 40 6.00 1.1 2.5 1400 55.5 37.2 2.43 63.0 22.8 - 39.8 3.17 29.2 96.3 3.68 4.1 40 6.00 1.1 2.5 1650 56.5 40.0 2.57 65.3 22.0 - 40.4 3.07 30.0 92.7 3.86 3.6 40 9.00 2.6 6.0 1400 56.1 37.2 2.30 63.0 24.4 - 41.8 3.22 31.0 97.6 3.80 4.0 40 9.00 2.6 6.0 1650 57.1 40.0 2.43 65.3 23.5 - 42.4 3.12 31.8 93.8 3.98 3.5 40 12.00 4.4 10.2 1400 56.3 37.3 2.23 63.0 25.2 - 42.9 3.25 32.0 98.4 3.87 4.0 40 12.00 4.4 10.2 1650 57.3 40.1 2.36 65.3 24.3 - 43.5 3.15 32.8 94.4 4.05 3.4 50 6.00 1.1 2.5 1400 54.2 37.8 2.63 62.4 20.6 1.9 45.1 3.33 33.9 99.8 3.97 4.3 50 6.00 1.1 2.5 1650 55.2 40.6 2.78 64.7 19.9 2.0 45.8 3.23 34.8 95.7 4.16 3.7 50 9.00 2.5 5.8 1400 55.3 37.9 2.49 63.0 22.2 1.7 47.5 3.40 36.0 101.4 4.09 4.2 50 9.00 2.5 5.8 1650 56.3 40.8 2.63 65.3 21.4 1.7 48.2 3.29 37.0 97.0 4.29 3.7 50 12.00 4.2 9.7 1400 55.7 37.9 2.42 63.1 23.0 1.4 48.9 3.44 37.3 102.3 4.17 4.2 50 12.00 4.2 9.7 1650 56.7 40.8 2.56 65.4 22.1 1.4 49.6 3.33 38.3 97.8 4.37 3.6 60 6.00 1.0 2.3 1400 52.2 37.3 2.84 61.2 18.4 2.8 50.9 3.51 39.0 103.7 4.25 4.6 60 6.00 1.0 2.3 1650 53.1 40.1 3.00 63.4 17.7 2.8 51.6 3.40 40.0 99.0 4.45 4.0 60 9.00 2.4 5.5 1400 53.7 37.8 2.69 62.1 20.0 2.4 53.7 3.59 41.5 105.5 4.38 4.5 60 9.00 2.4 5.5 1650 54.7 40.7 2.84 64.4 19.3 2.4 54.5 3.48 42.6 100.6 4.59 3.9 60 12.00 4.0 9.2 1400 54.3 38.0 2.62 62.5 20.7 2.0 55.3 3.63 43.0 106.6 4.46 4.5 60 12.00 4.0 9.2 1650 55.3 40.9 2.77 64.8 20.0 2.0 56.1 3.52 44.1 101.5 4.67 3.9 70 6.00 0.9 2.1 1400 49.7 36.5 3.08 59.4 16.1 3.8 56.7 3.70 44.1 107.5 4.49 5.0 70 6.00 0.9 2.1 1650 50.6 39.3 3.25 61.6 15.6 3.8 57.5 3.59 45.3 102.3 4.69 4.4 70 9.00 2.3 5.3 1400 51.5 37.3 2.91 60.7 17.7 3.2 60.0 3.80 47.1 109.7 4.63 5.0 70 9.00 2.3 5.3 1650 52.4 40.1 3.08 62.9 17.0 3.3 60.9 3.68 48.3 104.2 4.85 4.3 70 12.00 3.8 8.8 1400 52.4 37.7 2.83 61.2 18.5 2.7 61.8 3.86 48.7 110.9 4.69 4.9 70 12.00 3.8 8.8 1650 53.3 40.5 2.99 63.4 17.8 2.7 62.7 3.74 50.0 105.2 4.91 4.2 80 6.00 0.9 2.1 1400 46.9 35.5 3.34 57.6 14.0 4.9 62.7 3.91 49.3 111.5 4.70 5.6 80 6.00 0.9 2.1 1650 47.7 38.2 3.53 59.7 13.5 5.0 63.6 3.79 50.6 105.7 4.92 4.8 80 9.00 2.3 5.3 1400 48.7 36.4 3.16 58.9 15.4 4.2 66.4 4.02 52.6 113.9 4.84 5.5 80 9.00 2.3 5.3 1650 49.6 39.1 3.34 61.0 14.9 4.3 67.4 3.90 54.0 107.8 5.07 4.8 80 12.00 3.6 8.3 1400 49.7 36.8 3.07 59.5 16.2 3.5 68.5 4.10 54.5 115.3 4.90 5.4 80 12.00 3.6 8.3 1650 50.6 39.6 3.24 61.7 15.6 3.5 69.5 3.97 55.9 109.0 5.13 4.7 85 6.00 0.9 2.1 1400 45.3 34.8 3.49 56.6 13.0 5.6 65.6 4.02 51.9 113.4 4.78 5.9 85 6.00 0.9 2.1 1650 46.1 37.4 3.69 58.7 12.5 6.3 66.6 3.90 53.3 107.4 5.00 5.1 85 9.00 2.2 5.1 1400 47.3 35.6 3.30 57.9 14.3 4.8 69.6 4.16 55.4 116.0 4.90 5.8 85 9.00 2.2 5.1 1650 48.1 38.3 3.49 60.0 13.8 4.9 70.6 4.03 56.9 109.6 5.13 5.1 85 12.00 3.6 8.3 1400 48.2 36.1 3.21 58.6 15.0 3.9 71.7 4.23 57.3 117.4 4.97 5.4 85 12.00 3.6 8.3 1650 49.1 38.8 3.39 60.7 14.5 4.0 72.8 4.10 58.8 110.9 5.20 5.0 90 6.00 0.9 2.1 1400 43.7 34.0 3.64 55.7 12.0 6.2 68.7 4.14 54.6 115.4 4.86 6.2 90 6.00 0.9 2.1 1650 44.5 36.6 3.85 57.7 11.6 6.3 69.7 4.01 56.0 109.1 5.09 5.4 90 9.00 2.2 5.1 1400 45.8 34.9 3.44 56.9 13.3 5.3 72.8 4.28 58.2 118.1 4.99 6.1 90 9.00 2.2 5.1 1650 46.6 37.5 3.63 59.0 12.8 5.4 73.9 4.15 59.7 111.5 5.22 5.3 90 12.00 3.5 8.1 1400 46.8 35.3 3.34 57.6 14.0 4.3 75.1 4.37 60.1 119.7 5.04 6.0 90 12.00 3.5 8.1 1650 47.6 38.0 3.53 59.7 13.5 4.4 76.2 4.23 61.7 112.8 5.28 5.2 100 6.00 0.8 1.8 1400 40.7 32.8 3.99 53.8 10.2 7.6 0 100 6.00 0.8 1.8 1650 41.4 35.3 4.22 55.8 9.8 7.8 0 100 9.00 2.1 4.9 1400 42.6 33.6 3.77 54.9 11.3 6.5 0 100 9.00 2.1 4.9 1650 43.4 36.1 3.98 56.9 10.9 6.6 0 100 12.00 3.3 7.6 1400 43.6 33.9 3.66 55.6 11.9 5.3 0 100 12.00 3.3 7.6 1650 44.4 36.5 3.87 57.6 11.5 5.4 0 110 6.00 0.8 1.8 1400 37.6 31.8 4.40 52.3 8.5 9.2 0 110 6.00 0.8 1.8 1650 38.3 34.2 4.65 54.2 8.2 9.4 0 110 9.00 2.0 4.6 1400 39.4 32.4 4.15 53.2 9.5 7.8 0 110 9.00 2.0 4.6 1650 40.1 34.8 4.38 55.1 9.2 7.9 0 110 12.00 3.2 7.4 1400 40.4 32.7 4.02 53.7 10.0 6.4 0 110 12.00 3.2 7.4 1650 41.1 35.2 4.25 55.6 9.7 6.5 0 120 6.00 0.8 1.8 1400 34.8 31.2 4.88 51.1 7.1 10.9 0 120 6.00 0.8 1.8 1650 35.4 33.5 5.16 53.0 6.9 11.1 0 120 9.00 2.0 4.6 1400 36.4 31.4 4.59 51.7 7.9 9.3 0 120 9.00 2.0 4.6 1650 37.0 33.8 4.85 53.6 7.6 9.4 0 120 12.00 3.0 6.9 1400 37.2 31.7 4.46 52.1 8.3 7.6 0 120 12.00 3.0 6.9 1650 37.9 34.1 4.71 54.0 8.0 7.7 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 27 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
27ページ · クリックして拡大
27ページ

Two-Stage Indoor Split

50YDS064 Part Load With FV4006

Puron ® Systems

1200 CFM Nominal (Rated) Airfl ow Cooling, 1200 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 14.00 4.1 9.5 1000 28.6 2.93 19.0 96.5 2.86 3.4 20 14.00 4.1 9.5 1200 29.0 2.81 19.5 92.4 3.02 3.0 30 7.00 0.5 1.2 1000 42.0 26.0 1.64 47.5 25.6 - 31.6 3.01 21.7 99.3 3.08 3.5 30 7.00 0.5 1.2 1200 42.8 27.8 1.67 48.4 25.6 - 32.1 2.89 22.3 94.8 3.26 3.1 30 10.50 1.9 4.4 1000 42.8 26.3 1.59 48.2 26.9 - 32.6 3.01 22.7 100.2 3.17 3.5 30 10.50 1.9 4.4 1200 43.6 28.1 1.62 49.1 26.9 - 33.1 2.89 23.3 95.5 3.36 3.0 30 14.00 3.9 9.0 1000 44.1 26.9 1.57 49.5 28.1 - 33.1 3.02 23.3 100.6 3.21 3.4 30 14.00 3.9 9.0 1200 45.0 28.8 1.60 50.4 28.1 - 33.6 2.90 23.9 95.9 3.40 3.0 40 7.00 0.4 0.9 1000 44.7 28.2 1.79 50.8 25.0 - 36.1 3.10 25.9 103.4 3.41 3.6 40 7.00 0.4 0.9 1200 45.6 30.2 1.82 51.8 25.1 - 36.6 2.97 26.6 98.2 3.61 3.1 40 10.50 1.8 4.2 1000 45.0 28.2 1.69 50.8 26.6 - 37.4 3.11 27.2 104.6 3.52 3.6 40 10.50 1.8 4.2 1200 45.9 30.2 1.72 51.8 26.7 - 37.9 2.98 27.9 99.2 3.73 3.1 40 14.00 3.7 8.5 1000 45.3 28.3 1.66 51.0 27.3 - 38.0 3.11 27.7 105.2 3.58 3.5 40 14.00 3.7 8.5 1200 46.2 30.3 1.69 52.0 27.3 - 38.6 2.98 28.5 99.8 3.80 3.1 50 7.00 0.3 0.7 1000 45.1 29.1 1.98 51.9 22.8 1.0 40.9 3.20 30.3 107.9 3.75 3.7 50 7.00 0.3 0.7 1200 46.0 31.1 2.02 52.9 22.8 1.0 41.5 3.07 31.1 102.0 3.96 3.2 50 10.50 1.8 4.2 1000 45.6 29.1 1.86 51.9 24.5 0.9 42.5 3.21 31.8 109.4 3.88 3.7 50 10.50 1.8 4.2 1200 46.5 31.1 1.89 52.9 24.6 0.9 43.1 3.08 32.7 103.3 4.10 3.2 50 14.00 3.6 8.3 1000 45.7 29.1 1.81 51.9 25.2 0.8 43.3 3.21 32.6 110.1 3.95 3.6 50 14.00 3.6 8.3 1200 46.6 31.1 1.84 52.9 25.3 0.8 43.9 3.08 33.5 103.9 4.18 3.2 60 7.00 0.3 0.7 1000 43.9 28.7 2.23 51.4 19.7 1.7 46.2 3.31 35.2 112.8 4.09 3.9 60 7.00 0.3 0.7 1200 44.7 30.7 2.27 52.4 19.7 1.7 46.9 3.17 36.2 106.2 4.34 3.4 60 10.50 1.7 3.9 1000 44.8 29.1 2.08 51.9 21.5 1.5 48.1 3.32 37.0 114.5 4.25 3.8 60 10.50 1.7 3.9 1200 45.7 31.1 2.12 52.9 21.6 1.6 48.8 3.18 38.0 107.7 4.50 3.3 60 14.00 3.4 7.9 1000 45.2 29.2 2.01 52.1 22.5 1.4 49.1 3.33 37.9 115.5 4.32 3.8 60 14.00 3.4 7.9 1200 46.1 31.3 2.05 53.1 22.5 1.4 49.8 3.19 38.9 108.4 4.58 3.3 70 7.00 0.2 0.5 1000 41.8 27.9 2.52 50.4 16.6 2.3 51.7 3.42 40.3 117.9 4.43 4.1 70 7.00 0.2 0.5 1200 42.6 29.9 2.57 51.4 16.6 2.4 52.5 3.28 41.4 110.5 4.69 3.6 70 10.50 1.7 3.9 1000 43.2 28.6 2.35 51.1 18.4 2.1 53.8 3.44 42.2 119.8 4.58 4.1 70 10.50 1.7 3.9 1200 44.0 30.6 2.39 52.1 18.4 2.2 54.6 3.30 43.4 112.1 4.85 3.5 70 14.00 3.3 7.6 1000 43.8 28.8 2.27 51.5 19.3 1.9 54.9 3.46 43.2 120.8 4.65 4.0 70 14.00 3.3 7.6 1200 44.6 30.8 2.31 52.5 19.3 2.0 55.7 3.32 44.4 113.0 4.92 3.5 80 7.00 0.2 0.5 1000 39.4 27.0 2.87 49.2 13.7 3.0 57.3 3.56 45.3 123.1 4.72 4.4 80 7.00 0.2 0.5 1200 40.2 28.9 2.92 50.1 13.8 3.0 58.1 3.41 46.5 114.8 4.99 3.8 80 10.50 1.6 3.7 1000 40.9 27.7 2.66 49.9 15.4 2.7 59.5 3.59 47.4 125.1 4.86 4.3 80 10.50 1.6 3.7 1200 41.7 29.6 2.71 50.9 15.4 2.7 60.4 3.44 48.7 116.6 5.15 3.7 80 14.00 3.1 7.2 1000 41.6 28.0 2.57 50.3 16.2 2.4 60.7 3.61 48.5 126.2 4.93 4.3 80 14.00 3.1 7.2 1200 42.4 30.0 2.62 51.3 16.2 2.5 61.6 3.46 49.8 117.5 5.22 3.7 85 7.00 0.2 0.5 1000 38.1 26.5 3.05 48.6 12.5 3.5 60.0 3.63 47.7 125.6 4.84 4.6 85 7.00 0.2 0.5 1200 38.8 28.4 3.11 49.5 12.5 3.6 60.9 3.48 49.0 117.0 5.13 4.0 85 10.50 1.6 3.7 1000 39.5 27.2 2.85 49.3 13.9 3.0 62.3 3.68 49.8 127.7 4.96 4.5 85 10.50 1.6 3.7 1200 40.3 29.1 2.90 50.2 13.9 3.0 63.2 3.53 51.2 118.8 5.25 3.9 85 14.00 3.0 6.9 1000 40.3 27.5 2.75 49.7 14.7 2.7 63.6 3.70 51.0 128.9 5.04 4.5 85 14.00 3.0 6.9 1200 41.1 29.4 2.80 50.7 14.7 2.7 64.5 3.55 52.4 119.8 5.33 3.9 90 7.00 0.1 0.2 1000 36.8 26.1 3.24 47.9 11.4 3.5 62.7 3.71 50.1 128.1 4.95 4.7 90 7.00 0.1 0.2 1200 37.5 27.9 3.30 48.8 11.4 3.6 63.6 3.56 51.5 119.1 5.24 4.1 90 10.50 1.5 3.5 1000 38.3 26.6 3.03 48.6 12.6 3.2 65.2 3.77 52.4 130.4 5.07 4.6 90 10.50 1.5 3.5 1200 39.0 28.5 3.09 49.5 12.6 3.3 66.1 3.61 53.8 121.0 5.37 4.0 90 14.00 3.0 6.9 1000 39.0 27.0 2.93 49.1 13.3 2.9 66.3 3.80 53.4 131.4 5.11 4.6 90 14.00 3.0 6.9 1200 39.8 28.9 2.98 50.0 13.4 2.9 67.3 3.64 54.9 121.9 5.42 4.0 100 7.00 0.1 0.2 1000 34.2 25.2 3.68 46.9 9.3 4.1 0 100 7.00 0.1 0.2 1200 34.9 27.0 3.75 47.8 9.3 4.2 0 100 10.50 1.5 3.5 1000 35.6 25.7 3.45 47.4 10.3 3.7 0 100 10.50 1.5 3.5 1200 36.3 27.5 3.51 48.3 10.3 3.8 0 100 14.00 2.8 6.5 1000 36.3 26.0 3.34 47.7 10.9 3.3 0 100 14.00 2.8 6.5 1200 37.0 27.8 3.40 48.6 10.9 3.4 0 110 7.00 0.1 0.2 1000 32.1 24.9 4.16 46.4 7.7 4.6 0 110 7.00 0.1 0.2 1200 32.7 26.6 4.24 47.3 7.7 4.7 0 110 10.50 1.5 3.5 1000 33.2 25.0 3.91 46.5 8.5 4.1 0 110 10.50 1.5 3.5 1200 33.8 26.8 3.98 47.4 8.5 4.2 0 110 14.00 2.7 6.2 1000 33.7 25.2 3.79 46.7 8.9 3.7 0 110 14.00 2.7 6.2 1200 34.4 27.0 3.86 47.6 8.9 3.8 0 120 7.00 0.1 0.2 1000 30.7 24.7 4.70 46.8 6.5 5.0 120 7.00 0.1 0.2 1200 31.3 26.4 4.79 47.7 6.5 5.1 0 120 10.50 1.4 3.2 1000 31.4 24.8 4.42 46.5 7.1 4.5 0 120 10.50 1.4 3.2 1200 32.0 26.5 4.50 47.4 7.1 4.6 0 120 14.00 2.6 6.0 1000 31.8 25.0 4.29 46.4 7.4 4.1 0 120 14.00 2.6 6.0 1200 32.4 26.8 4.37 47.3 7.4 4.1 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 28 of the Carrier GT-S user manual — WPD Cooling - EAT 80/67°F Heating - EAT 70°F
28ページ · クリックして拡大
28ページ

GT-PX

50YDS064 Full Load With FV4006

1850 CFM Nominal (Rated) Airfl ow Cooling, 1850 CFM Nominal (Rated) Airfl ow Heating

Performance capacities shown in thousands of Btuh

WPD Cooling - EAT 80/67°F Heating - EAT 70°F

EWT

°F GPM

PSI FT Airfl ow

CFM TC SC kW HR EER HWC HC kW HE LAT COP HWC

20 15.00 5.0 11.6 1575 0 39.4 3.90 26.5 93.2 2.96 4.0 20 15.00 5.0 11.6 1850 40.0 3.78 27.2 90.0 3.10 3.5 30 7.50 0.6 1.4 1575 61.7 37.7 3.19 71.7 19.3 - 43.5 4.06 30.0 95.6 3.14 4.1 30 7.50 0.6 1.4 1850 62.8 40.5 3.37 74.3 18.6 - 44.1 3.93 30.8 92.1 3.29 3.6 30 11.25 2.3 5.3 1575 62.6 38.1 3.05 72.1 20.5 - 45.3 4.11 31.7 96.6 3.23 4.1 30 11.25 2.3 5.3 1850 63.7 41.0 3.22 74.7 19.8 - 46.0 3.98 32.5 93.0 3.39 3.5 30 15.00 4.8 11.1 1575 63.9 38.9 2.98 73.1 21.4 - 46.2 4.14 32.5 97.2 3.27 4.0 30 15.00 4.8 11.1 1850 65.0 41.8 3.15 75.7 20.6 - 46.9 4.01 33.4 93.5 3.43 3.5 40 7.50 0.5 1.2 1575 63.0 39.2 3.40 73.7 18.5 - 50.1 4.29 35.9 99.5 3.42 4.3 40 7.50 0.5 1.2 1850 64.1 42.2 3.59 76.4 17.9 - 50.8 4.16 36.8 95.4 3.58 3.7 40 11.25 2.2 5.1 1575 63.9 39.5 3.23 73.9 19.8 - 52.2 4.36 37.7 100.7 3.51 4.2 40 11.25 2.2 5.1 1850 65.0 42.5 3.41 76.6 19.1 - 53.0 4.22 38.7 96.5 3.68 3.6 40 15.00 4.5 10.4 1575 64.1 39.5 3.14 73.9 20.4 - 53.4 4.39 38.8 101.4 3.57 4.1 40 15.00 4.5 10.4 1850 65.2 42.5 3.32 76.6 19.6 - 54.2 4.25 39.8 97.1 3.74 3.6 50 7.50 0.4 0.9 1575 62.9 40.0 3.64 74.4 17.3 2.0 57.0 4.53 41.8 103.5 3.69 4.5 50 7.50 0.4 0.9 1850 64.0 43.0 3.85 77.1 16.6 2.1 57.8 4.39 42.9 98.9 3.86 3.9 50 11.25 2.1 4.9 1575 63.6 40.1 3.44 74.4 18.5 1.8 59.5 4.60 44.1 105.0 3.79 4.4 50 11.25 2.1 4.9 1850 64.7 43.1 3.63 77.1 17.8 1.8 60.4 4.46 45.3 100.2 3.97 3.8 50 15.00 4.3 9.9 1575 63.9 40.1 3.34 74.3 19.1 1.5 61.0 4.64 45.4 105.9 3.85 4.3 50 15.00 4.3 9.9 1850 65.0 43.1 3.53 77.0 18.4 1.5 61.9 4.50 46.6 101.0 4.03 3.8 60 7.50 0.4 0.9 1575 60.7 39.7 3.92 73.3 15.5 2.9 64.2 4.78 48.1 107.7 3.94 4.8 60 7.50 0.4 0.9 1850 61.8 42.7 4.14 76.0 14.9 3.0 65.1 4.63 49.4 102.6 4.12 4.2 60 11.25 2.1 4.9 1575 62.1 40.1 3.68 73.8 16.9 2.5 67.2 4.87 50.9 109.5 4.04 4.7 60 11.25 2.1 4.9 1850 63.2 43.1 3.89 76.5 16.2 2.5 68.2 4.72 52.2 104.1 4.23 4.1 60 15.00 4.1 9.5 1575 62.6 40.2 3.58 73.9 17.5 2.1 69.0 4.93 52.3 110.6 4.10 4.7 60 15.00 4.1 9.5 1850 63.7 43.2 3.78 76.6 16.9 2.1 70.0 4.78 53.7 105.0 4.29 4.0 70 7.50 0.3 0.7 1575 58.0 39.1 4.24 71.7 13.7 4.0 71.7 5.06 54.8 112.2 4.15 5.3 70 7.50 0.3 0.7 1850 59.0 42.0 4.48 74.3 13.2 4.0 72.8 4.90 56.2 106.4 4.35 4.6 70 11.25 2.0 4.6 1575 59.7 39.6 3.97 72.5 15.0 3.4 75.4 5.17 58.0 114.3 4.27 5.2 70 11.25 2.0 4.6 1850 60.8 42.6 4.20 75.1 14.5 3.4 76.5 5.01 59.5 108.3 4.48 4.5 70 15.00 3.9 9.0 1575 60.5 39.9 3.85 72.9 15.7 2.8 77.4 5.23 59.7 115.5 4.34 5.1 70 15.00 3.9 9.0 1850 61.6 42.9 4.07 75.5 15.1 2.9 78.5 5.07 61.3 109.3 4.54 4.4 80 7.50 0.2 0.5 1575 54.6 38.1 4.61 69.8 11.8 5.2 79.8 5.35 61.8 116.9 4.37 5.8 80 7.50 0.2 0.5 1850 55.6 41.0 4.87 72.3 11.4 5.3 81.0 5.18 63.4 110.5 4.58 5.1 80 11.25 2.0 4.6 1575 56.7 38.9 4.31 70.7 13.2 4.4 84.1 5.48 65.5 119.4 4.50 5.7 80 11.25 2.0 4.6 1850 57.7 41.8 4.55 73.3 12.7 4.5 85.3 5.31 67.2 112.7 4.71 5.0 80 15.00 3.7 8.5 1575 57.8 39.2 4.16 71.2 13.9 3.6 86.4 5.56 67.6 120.8 4.55 5.6 80 15.00 3.7 8.5 1850 58.8 42.2 4.40 73.8 13.4 3.7 87.7 5.39 69.4 113.9 4.77 4.9 85 7.50 0.2 0.5 1575 52.9 37.6 4.83 68.7 11.0 5.9 84.1 5.50 65.5 119.4 4.48 6.2 85 7.50 0.2 0.5 1850 53.8 40.4 5.10 71.2 10.5 6.0 85.3 5.33 67.2 112.7 4.69 5.4 85 11.25 1.9 4.4 1575 55.0 38.4 4.50 69.8 12.2 5.0 88.7 5.66 69.5 122.1 4.59 6.1 85 11.25 1.9 4.4 1850 56.0 41.3 4.76 72.3 11.8 5.1 90.0 5.48 71.3 115.0 4.81 5.5 85 15.00 3.6 8.3 1575 56.1 38.8 4.35 70.3 12.9 4.1 91.3 5.74 71.8 123.7 4.66 6.0 85 15.00 3.6 8.3 1850 57.1 41.7 4.60 72.8 12.4 4.2 92.6 5.56 73.7 116.3 4.88 5.2 90 7.50 0.2 0.5 1575 51.1 37.0 5.03 67.7 10.2 6.5 88.3 5.66 69.2 121.9 4.57 6.5 90 7.50 0.2 0.5 1850 52.0 39.8 5.32 70.2 9.8 6.6 89.6 5.48 71.0 114.8 4.79 5.6 90 11.25 1.9 4.4 1575 53.3 37.8 4.70 68.7 11.3 5.5 93.3 5.82 73.6 124.9 4.70 6.4 90 11.25 1.9 4.4 1850 54.2 40.7 4.97 71.2 10.9 5.6 94.7 5.64 75.5 117.4 4.92 5.5 90 15.00 3.5 8.1 1575 54.4 38.3 4.54 69.2 12.0 4.6 96.1 5.91 76.0 126.5 4.77 6.3 90 15.00 3.5 8.1 1850 55.4 41.2 4.80 71.7 11.5 4.6 97.5 5.73 78.0 118.8 4.99 5.4 100 7.50 0.1 0.2 1575 47.4 35.7 5.53 65.8 8.6 8.0 100 7.50 0.1 0.2 1850 48.2 38.4 5.84 68.2 8.3 8.2 0 100 11.25 1.8 4.2 1575 49.6 36.6 5.15 66.7 9.6 6.8 0 100 11.25 1.8 4.2 1850 50.5 39.4 5.44 69.1 9.3 6.9 0 100 15.00 3.3 7.6 1575 50.7 37.1 4.97 67.2 10.2 5.6 0 100 15.00 3.3 7.6 1850 51.6 39.9 5.25 69.6 9.8 5.7 0 110 7.50 0.1 0.2 1575 43.6 34.4 6.09 64.1 7.2 9.7 0 110 7.50 0.1 0.2 1850 44.4 37.0 6.43 66.4 6.9 9.9 0 110 11.25 1.8 4.2 1575 45.8 35.3 5.67 64.8 8.1 8.2 0 110 11.25 1.8 4.2 1850 46.6 38.0 5.99 67.1 7.8 8.4 0 110 15.00 3.1 7.2 1575 47.0 35.8 5.47 65.1 8.6 6.7 0 110 15.00 3.1 7.2 1850 47.8 38.5 5.78 67.5 8.3 6.9 0 120 7.50 0.1 0.2 1575 40.1 33.2 6.73 62.9 6.0 11.5 0 120 7.50 0.1 0.2 1850 40.8 35.7 7.11 65.2 5.7 11.7 0 120 11.25 1.7 3.9 1575 42.1 34.0 6.26 63.2 6.7 9.8 0 120 11.25 1.7 3.9 1850 42.9 36.6 6.61 65.5 6.5 9.9 0 120 15.00 2.9 6.7 1575 43.2 34.5 6.04 63.5 7.2 8.0 120 15.00 2.9 6.7 1850 44.0 37.1 6.38 65.8 6.9 8.1 0

20 Operation not recommended

Operation not recommended 110

Interpolation is permissible; extrapolation is not. All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40°F EWT is based upon a 15% antifreeze solution. Operation below 60°F EWT requires optional insulated water/refrigerant circuit (standard on residential models). See performance correction tables for operating conditions other than those listed above. “-” HWG operation is limited by a discharge temperature switch.

Page 29 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
29ページ · クリックして拡大
29ページ

Indoor & Outdoor Split Geothermal Comfort Systems

50YCS018 / 38WQS018 With GAH018

° °

°

! "# $ ! % %

&& '( )& *+( ,'' $ -( )& &+ *+( $ ,'' *( ). *& *+( )). ))/ ++ /&/ &./ )- ,'' )&) ))& .& .., -)+ )& && '( )& *+( )&/ )&& .+ /(& -)' )( &'+ )&/ '.' &-* &,' '( ,'' )-& ))* /- /'* -*' )- &&) )*+ '.' &*/ &+( '( -( )) &, *+( )-( )&- /- /,* -&& ), &'/ )&/ '+( &-( &+/ ', ,'' )-/ )), // /)* -(& )- &&- )*+ '+, &*/ &/( '( *( ). *) *+( )-. )&* /, /,/ -&, ), &'/ )&/ '+* &-( &.- ', ,'' )*) )), )'& /). -(+ )* &&* )*+ '+( &*/ -'' '( && '( )) *+( )*. )&, )'( /./ -** ). &'- )&/ '.+ &-& &-& )' ,'' )(& )). ))& /-* -++ )( &)+ )*+ '.. &*+ &*, '/ -( )) &( *+( )(, )&. ))- )''( -(. ). &', )&/ '.) &-* &(, '/ ,'' ),' )&' ))/ /*+ -/& ), &&) )*+ '.) &*. &+) '. *( )+ -/ *+( ),' )&/ )), )')) -,- )/ &'. )&/ '+/ &-* &,* '. ,'' ),* )&) )&& /(& -/. )+ &&& )*+ '+/ &*/ &+/ '. && '( )) *+( ),. )-) )&* )'&. -+. &' )/+ )&+ '/+ &-' &'- )* ,'' )+& )&& )-) /,, *)- ). &)' )*, '/. &*- &)* )- -( )) &( *+( )+. )-- )-- )'*+ -/- &) &'& )&. './ &-& &&+ )& ,'' ).& )&* )*' /.) *-) ). &), )*+ '/' &*, &*' )& *( )+ -. *+( ).& )-- )-, )'(( *'' && &'- )&/ '., &-- &-+ )' ,'' )., )&( )** /.. *-. )/ &)+ )*+ '.+ &*+ &(' )) && '( )' *+( )./ )-( )*- )',. *)' &- )./ )&( )'. &&, )+* )+ ,'' )/- )&, )(' /// **/ &' &'& )*- )'/ &-/ ).* ), -( )' &* *+( &'' )-+ )(- )'/' *&. &* )/( )&+ '// &&/ )/+ )( ,'' &'( )&. ),) )'), *,/ &) &'/ )*( )'' &*- &'/ )( *( ), -+ *+( &'( )-. )(. )'// *-( &* )/+ )&. '/, &-' &', )- ,'' &)' )&/ ),, )'&* *++ && &)) )*, '/+ &** &). )* && '* )' *+( &)' )-/ ),& ))'. **- &, ).' )&& )&) &&& )*/ &' ,'' &)( )-' )+' )'-) *.* && )/- )-/ )&& &-* )(. &' -( )' &- *+( &&- )*) )+* ))-* *,& &, ).+ )&( ))) &&( ),/ ). ,'' &&. )-& ).- )'(& (', &- &'' )*& ))& &-. )+/ ). *( )( -, *+( &&. )*& )+/ ))** *+' &+ )/' )&, )'+ &&, )++ ), ,'' &-* )-- ).. )',' ()* &* &'- )*- )'. &*' ).. )+ && '* )' *+( &-) )*- ).& ))*/ *+* &/ )+) )). )-* &)+ )&+ && ,'' &-, )-* )/) )',( (). &* ).- )-( )-, &&/ )-( &- -( )' && *+( &*( )*( )/( ))+. */* -' )+. )&) )&* &&) )** &) ,'' &() )-, &'( )'.. (*) &( )/) )-. )&( &-- )(- && *( )( -( *+( &() )*, &') ))./ ('- -) ).) )&& )&' &&& )() )/ ,'' &(+ )-+ &)) )'/+ (() &+ )/* )*' )&) &-( ),' &' && '* '/ *+( &() )*, &'& ))/' ('* -) ),) ))- )*. &)) )'/ &( ,'' &(. )-+ &)) )'/. (() &+ )+& )&/ )*/ &&- ))( &, -( '/ &) *+( &,+ )*/ &), )&&) (&, -- ),. ))+ )-+ &)( )&- &* ,'' &+* )*' &&, ))&- (+, &. ).' )-- )-/ &&+ )-' &( *( )* -- *+( &+* )(' &&- )&-* (-( -* )+) )). )-- &)+ )&. &- ,'' &.) )*' &-- ))-- (.( &/ ).- )-( )-( &&/ )-, &- && '* '/ *+( )(' )'+ ),& &'( /- &/ ,'' ),) )&& ),- &), /. -' -( '/ &) *+( )(. ))) )(& &)' )'* &+ ,'' ),/ )&+ )(- &&) ))' &. *( )* -& *+( ),) ))- )*. &)) )'/ &( ,'' $ )+& )&/ )*/ &&- )), &, && '* '/ *+( )*' )') )+( &'' .' -& ,'' )*/ ))( )++ &)' .* -- -( '/ &' *+( )*+ )'( ),, &'* ./ -' ,'' )(+ )&' ),+ &)( /* -) *( )- -) *+( )(' )'+ ),& &', /- &. ,'' ),) )&& ),- &), /. &/

3 238 9 3 #33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736

$ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

· ·

Page 30 of the Carrier GT-S user manual — 50YCS024 / 38WQS024 With GAH024
30ページ · クリックして拡大
30ページ

50YCS024 / 38WQS024 With GAH024

° °

°

! "# $ ! % %

-' '* )' ,(' .'' $ *( )' && ,(' $ .'' ,' )+ -/ ,(' ),' ),& )'( /&. &./ &) .'' ),& )(/ )'. ..+ &// ). -' '* '/ ,(' )./ ),/ )-& /+' -&/ &* &/* )/- '/& -&, -&) '/ .'' )/& ),& )-+ /&- -*. &' -)' &)& '/* -*& --' '. *( '/ &) ,(' )/) ),/ )-* /+& --& &( -'' )/, './ --' --. )' .'' )/* ),* )-. /&* -*+ &) -)' &)& '/) -*) -*- '. ,' ), -. ,(' )/- ),/ )-( /+( --( &, -', )// '., --( -(, )' .'' )/( ),( )-/ /&, -*+ && -)) &)& '.+ -*) -(, '. -' '* '/ ,(' &)( )+( )(, )''+ -,' &. &.+ ).+ ))' -&* &,& ), .'' &)/ ),/ ),) /(- -.' &* -'& &', ))& -*' &,/ )* *( '/ &) ,(' &)/ )++ )(/ )')& -,- &/ &/& )/' )', -&. &+, )( .'' &&& )+' ),- /(, -.) &( -'& &', )'. --/ &.' )* ,' ), -+ ,(' &&- )+. ),& )'). -,+ -' &/+ )/- )'& --) &/) )- .'' &&( )+& ),, /,' -.& &, -'& &', )'* --. &/& )- -' '* '/ ,(' &*) ).& )+/ )'** -.. -& &+/ ).& )&. -&- &)/ && .'' &*( )+( ).( /.- *)' &. &/* &'' )-) --. &&( &) *( '/ &' ,(' &*+ ).( ).* )'(& -/& -- &.* ).* )&- -&( &-) &' .'' &*/ )++ )./ /./ *)- &/ &/- &'' )&( --, &-* &' ,' ), -, ,(' &(- ).+ )./ )',) -/, -* &.. ).+ )). -&. &** )+ .'' &(* )+/ )/- //* *), -' &/- &'' )&' --* &** ). -' '* '/ ,(' &,, )/' &') )'+/ *'/ -, &+' ).' )*& -)/ )/' &+ .'' &+) ).& &'/ )')* *-. -& &.* )/, )*, --* )/( &+ *( '. )/ ,(' &+( )/- &'/ )'/) *), -. &+& ).) )-, -)/ &'' &* .'' &+/ ).* &), )'&- **- -- &.& )/, )-/ -&/ &'- &( ,' )( -( ,(' &.* )/, &)+ ))'* *&- -/ &+* ).- )-' -)/ &)& && .'' &.+ ).+ &&- )'-& **/ -* &.' )/+ )-& -&( &)& &- -' '* '. ,(' &/' )/. &&- )))- *&/ *) &,) )+. )(+ -)( ),+ -& .'' &/+ ).. &-- )'** *,- -( &+( )/- ),) --' )+) -& *( '. )/ ,(' -'& &'& &-- ))-' *-. *& &,) )+/ )*/ -)& )+( &/ .'' -'. )/& &*- )'(+ *+& -+ &+' )/- )(- -&- )++ -' ,' )( -* ,(' -)* &', &** ))*+ **+ *- &,) ).' )*) -'/ ).* &+ .'' -&' )/( &(- )'+' *.' -. &,, )/* )** -)( ).* &. -' '- '. ,(' -), &'( &*, ))(' *() *( &(* )+) )++ -)( )** -, .'' -&* )/( &(+ )'+* *.+ -/ &,. ).( ).) -&/ )*. -+ *( '. ). ,(' -&/ &'/ &(. )),/ *,' *+ &(* )+& ),. -)) )() -* .'' --, )// &,. )'./ */, *' &,- )., )+& -&& )(- -( ,' )* -& ,(' -*- &)* &+' )).. *,/ *. &(* )+& )(/ -'. ),' -) .'' -*/ &'- &.' ))'* ('* *& &(/ )., ),& -)* )(/ -& -' '- '. ,(' -*& &)& &,/ ))., *+& (' &*+ ),* )/, -)* )&, *) .'' -(' &') &.) ))'( ()' *& &,' )++ &') -&/ )&/ *- *( '. )+ ,(' -(, &)+ &.& )&'. *.) (& &*+ ),* )., -)) )-- -/ .'' -,* &', &/* ))&) (). ** &(, )+. )/) -&) )-* *' ,' )* -) ,(' -+) &&& &/( )&&/ *./ (* &*+ ),( )++ -'+ )*' -, .'' -+. &)) -', ))-. (&( *, &(& )+/ ).' -)- )*' -+ -' '- '+ ,(' &-* )(/ &&' -'/ )', *, .'' &*, )+& &&, -&- )'/ *. *( '+ )+ ,(' &-- ),' &'/ -'( ))& ** .'' &*& )+- &)* -)( ))- *( ,' )- -' ,(' &-- ),' )/. -') )). *) .'' $ &-. )+- &'& -'+ )). *& -' '- '+ ,(' &&' )(* &** -'- /' () .'' &-& ),+ &(' -)+ /- (- *( '+ ), ,(' &&' )(( &-& &// /( *. .'' &&. ),+ &-+ -'/ /, (' ,' )- &/ ,(' &)/ )(( &&' &/* )'' *, .'' &&* ),. &&* -'' )'' *+

3 238 9 3 #33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736

$ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

· ·

Page 31 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
31ページ · クリックして拡大
31ページ

Indoor & Outdoor Split Geothermal Comfort Systems

50YCS030 / 38WQS030 With GAH030

° °

°

! "# $ ! % %

-+ ', )( .'' )''' $ (( )* -- .'' $ )''' +( &+ ,& .'' ).* )/& ))/ /)- &.& &, )''' )., ).. )&& .+& &/) && -+ ', )* .'' &', )/+ )-/ /-. -', &/ -*( &&, )'/ -.& -), )) )''' &'+ )/& )*) ./) -)( &( -,' &(& )'* -/( -** '/ (( )* -& .'' &)( )/, )*. /*/ -&' -' -*, &&* )'+ -.- -&* )) )''' &), )/& )() /'' --' &, -,' &*+ )'/ -/+ --) )' +( &, ,' .'' &&* )/, )(+ /(/ --( -& -*. &&& )'( -.* --& )& )''' &&, )/& ),) /'/ -*( &+ -,) &*) ))* *'' -). )' -+ ', )* .'' &*' &'- )+) /+. -*. -* --( &&- )-) -+/ &(( )/ )''' &*) )/. )+* /&* -(. -' -*/ &(' )&( -/& &+. ). (( )- -) .'' &*/ &'* ).' /./ -(. -, --, &&& )&, -+/ &,+ ). )''' &*/ )/. ).& /-) -,. -) -*/ &** )&. -/- &+- )+ +( &( (. .'' &(. &', ).. /// -,. -+ --+ &&) )&' -+. &.' ), )''' &(+ )// )./ /-. -+. -& -(' &-/ )-) -/( &,. ), -+ ', )- .'' &+( &'. &'* )'). -.+ *' -&* &&) )(- -++ &)& &+ )''' &+, &'- &'+ /(, -// -* --. &*+ )*+ -.. &-) &, (( )- -' .'' &.* &)& &)& )'&. -/- *) -&, &&' )*( -+( &&( &* )''' &.& &'( &)& /,) *'* -, --/ &*& )*+ -./ &-' &* +( &* (, .'' &/- &), &)/ )'-/ -/. *& -&+ &)/ )-, -+- &*' &) )''' &.. &', &). /,, *'/ -+ --/ &-. )*. -/' &-' && -+ ', )- .'' -)' &)+ &-, )'(. *)/ *( -)& &)* ),, -,/ ).. -- )''' -)) &'/ &*' /.. *-+ -/ -&+ &-. ),+ -.- )/, -- (( )- &/ .'' -). &&) &*- )',. *&& *, -)& &)) )(/ -,+ )/+ -' )''' -&' &)) &*. //, **( *) -&+ &-( ),& -.- &'& -' +( &* (* .'' -&+ &&( &(' )'+/ *&( *. -)& &'. )(& -,* &', &+ )''' -&/ &)- &(, )''* *(& *& -&. &-) )(. -.& &'+ &. -+ '( )- .'' -** &&( &,. )'// **. (' -'' &'+ )+/ -,& ),. -/ )''' -*, &)* &+- )'&' *+- ** -)( &-' ).+ -+/ ),/ -/ (( )& &. .'' -(- &-' &+* ))'. *(' (& &// &'& )+- -(. )+- -, )''' -(. &)+ &.* )'-) *.- *( -), &&. )+. -++ )+. -+ +( &- (- .'' -,) &-( &.) ))). *() (- &/+ )/+ ),+ -(( )+. -- )''' -+' &&' &/( )'*& */& *+ -)+ &&( ),/ -+( ).. -* -+ '( )& .'' -+/ &-) -'' ))-/ *.) (, &/' &'+ &'' -(/ )*( *( )''' -.' &&' -'( )'(& ('. *. -'( &-' &'. -+, )*+ *, (( )& &+ .'' -., &-+ -'( ))*+ *++ (. &./ &'& )/- -(( )(' *& )''' -/) &&* -)( )',& ()& (' -', &&+ )/. -+- )(* *- +( && () .'' -/- &** -)' ))(( *+- ,' &.+ )/+ ).+ -() )(* -/ )''' *'& &&. -&* )'+& ()+ (& -', &&( )./ -+) ),- *' -+ '( )& .'' *)* &-+ --- ))+/ ()& ,& &.' &'+ &&' -(( )&+ () )''' *)( &&( --. )'.* (*) (& &/* &-' &-' -+- )&. (- (( )) &, .'' *)/ &** --, )).( ('- ,* &+/ &'& &)- -(& )-) *. )''' *&( &-) -*, )'/- (*' (( &/( &&+ &)/ -+' )-( */ +( &) */ .'' *&( &(& --/ ))/& */* ,+ &++ )/+ &', -*. )-( *( )''' *-( &-, -(* ))'- (*' (+ &/, &&( &'. -,+ )*& *, -+ '( )) .'' &,* )/, &-/ -*, ))' (. )''' &++ &). &*/ -,& ))) ,' (( )) &( .'' &,- )/& &-& -*& ))* (* )''' &+. &), &-. -(/ ))+ (, +( &' *+ .'' &,& ).+ &&* --. ))+ () )''' $ &+/ &)- &&, -(, )&- (& -+ '( )) .'' &*. )., &(. --, /, ,* )''' &,' &', &,/ -(& /+ ,+ (( )) &* .'' &*+ ).) &(' --& // ,' )''' &,) &'* &(+ -*/ )'& ,& +( &' *( .'' &*, )++ &*& -&. )'& (+ )''' &,& &'& &** -*( )'+ (.

3 238 9 3 #33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736

$ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

· ·

Page 32 of the Carrier GT-S user manual — 50YCS036 / 38WQS036 With GAH036
32ページ · クリックして拡大
32ページ

50YCS036 / 38WQS036 With GAH036

° °

°

! "# $ ! % %

*( ), -. /+( )&'' $ +' -- +, /+( $ )&'' /' */ ))& /+( &-) &)( )(+ /)/ -)* -& )&'' &&/ &&- )(- .++ -') &+ *( ), -+ /+( &(, &-. )+( /*- -)* -, *). &+) )-& *,- -), )& )&'' &(/ &-' ).) /'' --' -' *&& &/) )-. *,/ -'( )) +' -& +- /+( &,& &-) ).- /*/ --& -+ *)+ &+- )&+ *,) -&/ )- )&'' &,- &-) ).* /'- --- -& *&' &/* )-- *,( -)+ )) /' *+ )'/ /+( &,. &&* )/& /(( -() -/ *), &+( )&& *(. -*& )- )&'' &,, &-& ).+ /'( --, -- *)/ &/. )&+ *,& -&/ )& *( )( -( /+( &/& &*, &'. /++ -*. *& *'* &,( )(- *(, &,( && )&'' &/, &-+ &)( /&. -,( -, *'+ &.( ),' *,) &(( &) +' -) +) /+( &/. &*& &), /.- -,) ** *'* &,+ )*+ *(* &+( &) )&'' &// &-/ &). /-) -,+ -+ *', &.. )(* *(/ &,* &' /' *, )', /+( -'* &-. &&- /./ -+( *( *'* &,/ )*) *(& &.( )/ )&'' -'- &*) &&) /-* -,/ -/ *', &/' )*. *(, &+( )/ *( )( -* /+( -&. &(- &*& )')) -.' *. -./ &,' )+- **. &&( -& )&'' --& &** &*/ /(, -// *& -/& &+/ ).) *(* &)+ -) +' -' ,/ /+( --* &(- &*. )')+ -.. (' -/' &,) ),+ **+ &-* &. )&'' --, &*+ &(& /(/ -// *- -/- &.) )+( *(& &&( &. /' ** )'& /+( -*) &(& &(( )'&- -/, (& -/) &,& ),) **, &*- &* )&'' -*' &*/ &(( /,& *'' *( -/- &.- ),. *(' &-* &, *( )* -- /+( -,& &,( &+& )'** *') (( -,/ &(+ )/' *-- )/* -/ )&'' -,/ &(* &.& /.* *&( *+ -+* &.& )/. **) )./ -/ +' &/ ,+ /+( -,/ &,( &+/ )'() *'. (, -+- &(/ ).* *-, &'- -, )&'' -+( &(+ &.+ /./ *&. */ -+. &.& )/) **- )/. -, /' *- // /+( -++ &,, &., )'(. *)( (. -++ &,& )+. *-. &)& -& )&'' -.& &(/ &/- //* *-& () -.& &.- ).( **( &'+ -- *( )* -& /+( -/, &+, -'& )'+, *&' ,) -*. &(* &'+ *)/ ),. *+ )&'' *'( &,* -)( )')- **/ (- -(( &.* &)( *&. ),( *+ +' &. ,( /+( *'( &+. -)' )'.* *&, ,- -(, &(. &') *&* )++ *- )&'' *)* &,+ -&- )')/ *(( (( -,- &.- &'. *-* )+( ** /' *) /, /+( *)- &.' -)+ )'/& *-& ,( -,- &,& )/, *-' )., -/ )&'' *&- &,/ --) )'&, *,) (+ -+) &.& &') **' ).( *) *( )- -) /+( *-& &., --* )))' **& ,. --( &*( &-' *)* )*, (* )&'' **& &+* -*. )'*) *+& (. -*& &+* &-/ *&- )*- (( +' &+ ,& /+( **' &.. -*& ))). **+ +' -*- &*/ &&- *)/ )(* (' )&'' *(' &+, -(, )'*+ *+. ,) -(' &+- &-) *&/ )(& () /' *' /- /+( **. &/' -*/ ))&, *(- +- -(' &(& &)+ *&* ),) *, )&'' *(/ &+/ -,* )'(* *.- ,- -(. &+& &&- *-* ),' *. *( )- -' /+( *,+ &/+ -,, ))** *,) +( -&- &-, &(& *'/ )&. ,) )&'' *+. &.* -.) )',/ */- ,- -&/ &,* &,& *)/ )&, ,- +' &, ,' /+( *+( &/. -+* ))() *,+ +. --' &*' &*( *)* )-* (+ )&'' *.+ &., -./ )'+( */. ,, --+ &,- &(* *&- )-- (/ /' -/ ./ /+( *.- -'' -.) ))(/ *+& .) --+ &*- &-. *). )*) (* )&'' */( &.. -/+ )'.& ('* ,/ -** &,& &*( *&. )*' (( *( )- &/ /+( -'- &-+ &.- -// )'+ ,/ )&'' -'/ &,( &/* *'/ )'( +& +' &( (. /+( -'/ &*) &+( *'- ))& ,( )&'' -), &,* &.( *)- ))) ,+ /' -+ ., /+( -), &** &,+ *'+ )). ,) )&'' $ -&- &,- &+( *), ))+ ,& *( )& &. /+( &.& &-/ -)* -./ /' ++ )&'' &.. &,+ -&, -// .. .' +' &* (, /+( &./ &*& -'( -/- /( +& )&'' &/( &,, -), *'& /- +( /' -, .- /+( &/( &*, &/+ -/, // ,. )&'' -') &,( -'( *'( // +'

#33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736

$ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

· ·

Page 33 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
33ページ · クリックして拡大
33ページ

Indoor & Outdoor Split Geothermal Comfort Systems

50YCS042 / 38WQS042 With GAH042

° °

°

! "# $ ! % %

(& &' *+ ))(' )*'' $ /' */ ))& ))(' $ )*'' )'( ,& )*- ))(' &,( &,& )+( /)- &/, -, )*'' &+& &,' ).* ..' -'+ -) (& &' *, ))(' -)- &+) &&' /(& --. *) ('( --) ),+ (,& -'- ), )*'' -)- &,( &&- /'+ -*, -( (&* -,* )+- (.- -'- )- /' *+ )'/ ))(' -)* &+) &&& /(- -*' *- *// -&, ),& ((* -'/ ), )*'' -)/ &,+ &&. /)) -() -, (&( -,, ),. (.& -)- )* )'( ,' )-/ ))(' -), &+) &&* /(* -*& ** */- -&& )(+ (*, -)* )+ )*'' -&( &,. &-- /)( -(( -. (&, -,/ ),- (.& -&* )( (& )/ *( ))(' -(. &.' &,- /./ -+( *. *., -&& )/* ((& &() &+ )*'' -(/ &+- &,, /-+ -.( *& ('* -(* &') (+& &() &( /' *, )', ))(' -,) &.) &,( //) -+, (' *.' -)+ ).+ (** &(, &( )*'' -,/ &++ &+* /** -/' *- ('( -(, )/* (+) &,' &* )'( (. )-( ))(' -,- &.& &,+ //- -++ (& *+- -)- ).) (-( &,) &- )*'' -+. &.' &.- /(' -/, *( ('( -(/ ).. (+' &,/ &- (& )/ *- ))(' *'* &.. -', )'&( *)) (, *,+ -)- &&) (*& &)) -. )*'' *'* &.& -'. /,+ *&) *. *.* -*- &&/ (,& &)) -, /' ** )'& ))(' *'+ &/) -'. )'&. *)' (. *,' -'. &)- (-- &), -* )*'' *). &.+ -&' /++ *&+ (' *.* -*, &&) (,' &)/ -* )'( (, )-' ))(' *)) &/* -)) )'-) *)' ,' *(* -'* &'( (&* &&) &/ )*'' *-& &/& --& /., *-* (& *.( -*/ &)- ((. &&. -) (& ). *& ))(' **( &/. -*- )'(. *-+ ,- *(- -)' &** (-, )., *, )*'' *(' &/' -() //+ *(( (( *,/ --- &(& ((( )., *, /' *- // ))(' *(& -'& -*/ )',* *-. ,( *(* -'* &-, (-* )/- *& )*'' *,* &/* -,- )''+ *,) (+ *+' --+ &*& ((& )/* *& )'( (( )&, ))(' *(/ -', -(* )',/ **' ,+ *(( &// &&+ (-& &'' -. )*'' *+. &// -+, )'), *,. (/ *+' -*) &-) (*/ &'- -/ (& ). *' ))(' *., -'. -.) )'/) *,& +' *-/ -'. &,+ (-' ),* (( )*'' */( &/. -/* )'&. *.+ ,& *(( -&- &+( (*. ),( (( /' *) /, ))(' */, -)- -./ )'// *,( +- **+ -'' &(. (-( )+- (' )*'' ('/ -'& *', )'-+ */* ,* *(( -&+ &,- (** )+- () )'( (- )&& ))(' (', -)+ -/. ))'. *,+ +( *(( &/- &*/ (*' ).& *, )*'' (&- -'+ *)/ )'*, ('' ,, *(( --& &(' (*' ).& *. (& )+ -/ ))(' (-' -), *&& ))&+ */) +/ *)+ &/. &/+ (). )*' ,- )*'' (*) -', *-, )'(. ()+ ,+ *-& -)& -', (-, )*) ,* /' *' /- ))(' (*- -&- *-& ))-+ */& .) *&( &/) &.+ (&- )*. (. )*'' ((+ -)- *() )',/ (&& +' *-& -)+ &/& (-& )*. ,' )'( () )). ))(' ((( --' **& ))*+ */- .* *-& &.* &++ (&+ )(, (* )*'' (+* -)/ *,( )'.' (&+ +- *-& -&& &+. (&+ )(, (, (& ), -. ))(' (+( -&( *,* )),- ()/ .+ -/( &.. -&+ ('+ )&) +) )*'' (., -)( *+/ )'.. (*, +- *'/ -'& --+ (&* )&) +* /' -/ ./ ))(' (./ --* *+( ))+( ()+ /' *'& &.) -), ()' )&+ ,+ )*'' ,'( -&- */( ))'' (*/ ++ *'/ -'+ -&) ()/ )&+ ,/ )'( */ ))* ))(' ,'* -*- *.+ ))., (), /* *)' &+* -'( ()* )-* ,- )*'' ,&( --) ()& )))- ((- .' *'/ -)) -', ()* )-* ,* (& ), -, ))(' -+( &.& -,( ('' )'- .' )*'' -./ &/, -+, ()+ )'- .- /' -+ ., ))(' -.& &+, -(- ('- )'. +( )*'' -./ -'' -(/ ()) )'. +. )'( *+ ))' ))(' -./ &,/ -*) (', ))* +) )*'' $ -./ -'( -*& (', ))* +& (& )( -( ))(' -(, &+, *'* */* .. ./ )*'' -,. &/' *), ()' .. /& /' -, .- ))(' -,& &+' -/) */, /- .* )*'' -,. &/* -/+ ('* /- ., )'( *, )'( ))(' -,/ &,- -++ */+ /. +/ )*'' -,/ &// -+. */. /. .)

3 238 9 3 #33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736 $ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

·

Page 34 of the Carrier GT-S user manual — 50YCS048 / 38WQS048 With GAH048
34ページ · クリックして拡大
34ページ

50YCS048 / 38WQS048 With GAH048

° °

°

! "# $ ! % %

,' &, (/ )-'' ),'' $ /' */ ))& )-'' $ ),'' )&' +, )+, )-'' -') -') )/. /)* &/- *& ),'' -)* &/( &)- ..& -)& -, ,' &( (. )-'' -*& &// &*' /*- --( *. (*/ -(( )/) ,)* &.+ )+ ),'' -,+ &/. &,( /)& -,) *' (,+ -./ &'' ,-( &.- )* /' *+ )'/ )-'' -*. -'* &** /*. --( (' (*/ -(+ ).* ,)) &// )+ ),'' -,. -') &,( /)- -(. *& (,( -.+ )/- ,-) &/* )( )&' +* )+) )-'' -(* -)' &*. /(& --( () (*. -(/ )+, ,'/ -)) ). ),'' -,/ -'* &,( /)* -(, ** (,* -.( ).( ,&+ -'( ), ,' &* (, )-'' -+/ -'+ &+* /+' -,) (, (-* -*/ &)/ ,'/ &** -' ),'' *'+ -'+ -'& /-, -./ *. (() -.& &-' ,-' &*' &. /' *, )', )-'' -/) -)- &.* /+. -,, (. (-- -() &)) ,'( &(- &. ),'' *)- -'/ -'+ /-/ -/& (' (*/ -.' &&) ,&* &*/ &, )&' +& ),, )-'' *'- -)/ &/* /.+ -+) ,' (-& -(& &'- ,') &,- &, ),'' *)/ -)) -)- /*& -/( (& (*+ -+. &)& ,)/ &(. &( ,' &- (* )-'' *), -), -'. //, -., ,* ()/ -*& &*+ ,'- &)' *- ),'' **+ -)( --/ /(/ *)( (, (-, -+( &(/ ,&* &'+ *) /' ** )'& )-'' *-* -&) -&* )''/ -/( ,+ ()+ -** &-. (// &). -. ),'' *(. -), -(' /,( *&* (. (-- -+- &*/ ,). &)* -. )&' +' ),) )-'' *(& -&+ -*' )'&& *'( ,/ (), -*, &&/ (/* &&, -- ),'' *,. -)+ -,' /+) *-- ,' (-' -+) &*' ,)& &&) -( ,' &- (& )-'' *,/ -&, -(. )'-* *&) +- (') --, &+) (/* ).( (- ),'' *.+ -&* -+, /.& **' ,- (&+ -+& &.- ,&* )., (& /' *- // )-'' *.( --) -+& )'*( *&/ +( (') --, &,& (/) )/& *. ),'' ('- -&( -/& //) *(- ,, (&* -+' &+- ,)+ )/& *. )&' ,+ )(, )-'' (') --, -., )'(+ *-+ ++ (') --, &(& (.. )// *- ),'' (&' -&+ *'. )'') *,, ,. (&' -,/ &,& ,'/ )/. *( ,' && () )-'' (&& --, *'+ )'+& *(( .) *.* -&/ &/, (.( ),* ,- ),'' (&, --& *)- )''( *,* +) ()/ -,/ -'+ ,&* ),/ ,- /' *) /, )-'' (-, -*' *&' )'.) *,& .* *.( -&. &., (.- )+' (. ),'' (*/ --( *-( )'). *.) +- ()* -,. &/, ,)( )+* (/ )&' ,( )() )-'' (*/ -** *-& )'/) *,. ., *.+ -&+ &+, (.) )++ (- ),'' (+) --+ *(, )'-' */+ +, ('/ -,, &.( ,', )+/ (( ,' &) */ )-'' (,) -*( **- ))'' *++ /' *,, -&) -&, (++ )*- +& ),'' (,, -*) *(' )'&. *.+ +. ('' -,' --/ ,)( )*+ +* /' *' /- )-'' (+& -*. *(* ))'. *.& /* *,+ -&' -)( (+( )*. ,+ ),'' (., -*- *+' )'-/ (') .) */( -(. -&, ,', )(& ,/ )&' ,- )*, )-'' (.* -(& *,* ))), *., /+ *,/ -)/ -'* (+& )(* ,- ),'' ,'+ -** *./ )'() (), .* */' -(+ -)* (/+ )(, ,* ,' &' *+ )-'' ,') -(- *.' ))&. */. )'' **. -)- -(+ (+' )&, .& ),'' ,', -*/ *.+ )'() ('. .* *.' -(' -+) ,'+ )-' .( /' -/ ./ )-'' ,'/ -(, *.. ))-* (') )'* **/ -)& -*( (,+ )-' ++ ),'' ,&* -() ('* )',) (&) .. *+, -*/ -(+ (/+ )-- .' )&' ,) )*' )-'' ,). -,' */( ))*' ('* )'. *() -)) --- (,* )-, +& ),'' ,*& -(& (&& )'+& (-( /& *+) -*. -*- (.. )-+ +* ,' &' *( )-'' *-) -'/ -// (,+ )'. /- ),'' *,- -*, *)* ,'* ))& /, /' -+ ., )-'' *-- -'. -.( (,* ))& .+ ),'' *(. -*( -// (/* ))( /' )&' (/ )-( )-'' *-* -'+ -+& (,) ))+ .& ),'' $ *(* -** -.* (.* )). .* ,' )/ ** )-'' *)( -', **) (,( /* )'- ),'' **( -*& *(. ,') /+ )'+ /' -, .- )-'' *), -'( *&, (,) /. /+ ),'' **) -*) **) (/) )'' )'' )&' (, )-' )-'' *)+ -'* *)) ((. )'& /& ),'' *-, -*' *&* (.) )'- /*

3 238 9 3 #33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736 $ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

·

Page 35 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
35ページ · クリックして拡大
35ページ

Indoor & Outdoor Split Geothermal Comfort Systems

50YCS060 / 38WQS060 With GAH060

° °

°

! "# $ ! % %

+( ), -+ ),(' &''' $ ))- -& +* ),(' $ &''' )(' () )). ),(' *)) *'* &+- /-' &/. (- &''' *)( -// &+/ ./& -'( *( +( ), -, ),(' *-) *'/ &/& /*& -'/ ,' ,+( **& &,* +,( &(( && &''' *-. *'( -'' /'- -)+ (' ,/) *+& &+- +.( &(- ). ))- -) +) ),(' *(( *)- -)* /(( -&- ,& ,+, *-/ &(. +,* &,& &- &''' *,) *'/ -&& /)* --' (- ,.. *,+ &,. ++/ &(+ )/ )(' */ ))* ),(' *+/ *). --, /,/ --, ,* ,+, *-, &(& +,& &,/ &- &''' *.( *)- -** /&* -** (( ,.* *,) &,- ++* &,' &' +( )( -( ),(' ('* *&/ -(. /.- -*( +' ,(- *-( -'( +(+ &)* -. &''' ()- *&( -,. /-+ -(* ,' ,,. *,( -)( ++, &)& -( ))- -' ,/ ),(' (-' *-( -.& //. -(+ +- ,(* *-- &/, +(( &&) -( &''' (-- *&. -.+ /*+ -,( ,& ,,( *,' -'+ ++' &)+ -* )(' *. ))) ),(' ((+ **& *', )')- -,/ +( ,(( *-' &., +(& &&/ -& &''' ((- *-& *', /(, -+( ,( ,,- *(( &// +,( &&) -& +( )( -* ),(' (++ **. *&* )'&* -++ .' ,-) *&/ -*, +*/ ).& (* &''' (.+ *** *-( /+& -.+ +' ,*, *(. -(. +,. ).) (& ))- &/ ,+ ),(' ,', *(+ *(' )'*' -.. .- ,-& *&, --* +*, )./ *. &''' ,'* **. *(& /.' -/, +& ,*- *(- -*+ +,) )., *. )(' *, )'+ ),(' ,-( *,, *+, )'(, -// ., ,-- *&* -&) +*& )/+ *) &''' ,&& *() *,. /.. *'* +( ,*) **. --, +(( )/) ** +( )* -- ),(' ,*/ *,. *./ )',* *', /) ,), *)/ -+. +*, ),- ,, &''' ,,) *,* ('- )'', *)+ +/ ,-) *(* -/' +,* ),& ,( ))- &. ,( ),(' ,.) *+/ ()+ )'.& *), /* ,)/ *)+ -,) +*& )+) ,' &''' ,.( *,+ (&, )')+ *-' .& ,-& *(' -+* +(/ ),/ ,) )(' *( )'* ),(' +)- */' (*( ))'' *&, /+ ,&) *)* -*( +-/ ).' (* &''' +)' *+) (*/ )'&/ **& .( ,-& **, -(. +(* )++ (, +( )* -& ),(' +&& *.. ((( ))'( *-- )') ,'& *)' *)) +*& )*+ +. &''' +-( *.- (+' )'*' **( ./ ,)+ *(' *&- +,) )*, +/ ))- &+ ,- ),(' +(, (') (.( ))&* **& )'* ,', *'+ -./ +-/ )(, +& &''' +,, *.+ ,'' )'(( *,) /& ,&' **+ *'& +(+ )(* +- )(' *- )'' ),(' +/' ()( ,)( ))** *(' )'. ,)' *'* -,. +-( ),, ,, &''' +/+ */' ,-' )',/ *++ /( ,&* **- -.' +(* ),* ,. +( )- -) ),(' +/* ('. ,&) ))*, *(. ))- (+, *'& *(, +-& )&, /' &''' .'/ ('- ,-+ )'+( *+) /+ (/' **& *+' +(' )&( /& ))- &, ,) ),(' .&+ (&' ,*/ )),* *,, ))+ (.' *'' *-& +&+ )-* .* &''' .-. ('( ,,, )'.. *., )') (/- *-. **, +*( )-- ., )(' *& /+ ),(' .,' (-- ,+. )).& *+- )&) (.- -/+ *'/ +&- )*- +. &''' .,+ ('+ ,/* ))') (') )'( (/+ *-( *&& +*) )*) .' +( )- -' ),(' .,+ (&. ,.+ )).+ *.) )&( ((' -/( ('& +&) ))' )'& &''' ..- (&- +'( ))'/ */( )'( (,- *-* ()+ +-/ )'/ )', ))- &( (/ ),(' ./. (-/ +)* )&'* *.. )-' ((- -/& *+, +)( )), /, &''' /)' (&* +-) ))&) ('/ ))' (,, *-' */' +-- ))( // )(' *) /* ),(' /&/ (() +*) )&&) */* )-( ((, -/' **/ +)' )&* /' &''' /-+ (&( +(. ))-* (&- ))( (,/ *&+ *,* +&. )&- /& +( )& &/ ),(' (-- -/) ((, +&- /, ))( &''' (*, *&/ (+& +*) /( ))/ ))- &* (, ),(' (-+ -.. (&+ +), )'& )'. &''' (*/ *&, (*- +-( )') ))& )(' -/ /' ),(' (*' -.( */. +)' )'. )'& &''' $ ((- *&& ()* +&. )'+ )'* +( )& &. ),(' ()+ -., ,)' +&( .( )&. &''' (&/ *&( ,&. +** .* )-- ))- &* (* ),(' (&' -.* (+. +). /' )&) &''' (-- *&) (/, +-, ./ )&( )(' -. .+ ),(' (&* -.) (*, +)' /, ))* &''' (-, *). (,* +&. /( )),

3 238 9 3 #33 6 .'° ,+° 3 6 +'° 6 #33 2 3 736 3 736 $ 23 *'° 2 )(4 5 3 23 6 3 27 23 3 $

·

Page 36 of the Carrier GT-S user manual — Water Connection Size
36ページ · クリックして拡大
36ページ

Physical Data

GT-PX (50YDS) Physical Data

Model 026 038 049 064

Compressor [1 Each) Copeland UltraTech Two-Stage Scroll

Factory Charge R410A (oz) [kg] 90 [2.55] 104 [2.95] 126 [3.57] 168 [4.76]

Water Connection Size

IPT (in) 1

HWG Connection Size

IPT (in) 1

Line Set Connection Size

Suction Line Sweat Connection (in.) 3/4 7/8 7/8 1-1/8

Liquid Line Sweat Connection (in.) 3/8 3/8 3/8 1/2

Weight - Operating, (lbs) [kg] 203 [92] 221 [100] 250 [113] 265 [120]

Weight - Packaged, (lbs) [kg] 218 [99] 236 [107] 265 [120] 280 [127]

All units have spring compressor mountings, TXV expansion devices, and 1/2” [12.2mm] & 3/4” [19.1mm] electrical knockouts.

GT-GS (50YCS) Physical Data

Model 018 024 030 036 042 048 060

Compressor [1 Each) Scroll

Factory Charge R410A (oz) [kg] 90 [2.55] 104 [2.95] 108 [3.06] 117 [3.32] 122 [3.46] 130 [3.69] 136 [3.86]

Water Connection Size

IPT (in) 1

HWG Connection Size

IPT (in) 1

Line Set Connection Size

Suction Line Sweat Connection (in.) 3/4 7/8 1-1/8

Liquid Line Sweat Connection (in.) 3/8 1/2

Weight - Operating, (lbs) [kg] 165 [75] 203 [92] 205 [93] 217 [98] 221 [100] 229 [104] 235 [107]

Weight - Packaged, (lbs) [kg] 180 [82] 218 [99] 220 [100] 232 [105] 236 [107] 244 [111] 250 [113]

All units have spring compressor mountings, TXV expansion devices, and 1/2” [12.2mm] & 3/4” [19.1mm] electrical knockouts.

GT-S (38WQS) Physical Data

Model 018 024 030 036 042 048 060

Compressor [1 Each) Rotary Scroll

Factory Charge R410A (oz) [kg] 70 [1.98] 74 [2.10] 86 [2.52] 101 [2.86] 122 [3.46] 130 [3.69] 136 [3.86]

Water Connection Size

Line Set Connection Size

Suction Line Sweat Connection (in.) 3/4 3/4 7/8 1-1/8

Liquid Line Sweat Connection (in.) 3/8 1/2

Weight - Operating, (lbs) [kg] 165 [75] 203 [92] 205 [93] 217 [98] 221 [100] 229 [104] 235 [107]

Weight - Packaged, (lbs) [kg] 180 [82] 218 [99] 220 [100] 232 [105] 236 [107] 244 [111] 250 [113]

All units have spring compressor mountings, TXV expansion devices, weather resistant cabinet, and 1/2” [12.2mm] & 3/4” [19.1mm] electrical knockouts. Hot Water Generator with factory installed hot gas service ports.

EPT (in) 1-1/4

Page 37 of the Carrier GT-S user manual — A
37ページ · クリックして拡大
37ページ

Indoor & Outdoor Split Geothermal Comfort Systems

GT-PX Dimensional Data

GT-PX (50YDS) Dimensional Data

Overall Cabinet Water Connections Refrigerant Connection Electrical Knockouts

1 Water In/Out

2 HWG In/Out

Model

D1 Water

D2 Water

E Water

F HWG

G HWG

A Width

B Height

C Depth

3 Suction

4 Liquid H I J K L M

026 in 22.4 19.3 25.6 1 1 1.6 2.1 11.0 13.9 16.9 3/4 3/8 7.3 5.1 3.6 6.1 8.6 1.4

cm 56.9 49.0 65.0 - - 4.1 5.3 27.9 35.3 42.9 - - 18.5 13.0 9.1 15.5 21.8 3.6

038 in 25.4 21.3 30.6 1 1 1.7 3.4 12.1 15.6 18.9 7/8 3/8 8.4 6.1 3.6 6.1 8.6 1.7

cm 64.5 54.1 77.7 - - 4.3 8.6 30.7 39.6 48.0 - - 21.3 15.5 9.1 15.5 21.8 4.3

049 in 25.4 21.3 30.6 1 1 1.7 3.4 12.1 15.6 18.9 7/8 3/8 8.4 6.1 3.6 6.1 8.6 1.7

cm 64.5 54.1 77.7 - - 4.3 8.6 30.7 39.6 48.0 - - 21.3 15.5 9.1 15.5 21.8 4.3

064 in 25.4 21.3 30.6 1 1 1.7 3.4 12.1 15.6 18.9 1-1/8 1/2 8.4 6.1 3.6 6.1 8.6 1.7

cm 64.5 54.1 77.7 - - 4.3 8.6 30.7 39.6 48.0 - - 21.3 15.5 9.1 15.5 21.8 4.3

Isometric

View

Top View

A

HWG Out

1-1/8" [28.6mm] Knockout 7/8" [22.2mm] Knockout

HWG In

B

G

Water Out

F

Suction Liq. Line

E

H

K J

Water

In

D2

Front View Left Side View

M D1

1.177 [29.9mm]

Show 6 more labels / short text on this page
In · In · Out · In · Out · Swivel
Page 38 of the Carrier GT-S user manual — 3/4" HV Knockout
38ページ · クリックして拡大
38ページ

GT-GS Dimensional Data

GT-GS (50YCS) Dimensional Data

Overall Cabinet Water Connections Refrigerant Connections Electrical Knockouts

Model A B C 1 - Water In & Out 2 - HWG In & Out D E F G 3-Size 4-Size H I J K L Width Height Depth Swivel Swivel In Out HWG In HWG Out Suction Liquid Suction Liquid

018 22.4 19.3 25.6 1" 1" 2.4 5.4 13.9 16.9 3/4" 3/8" 5.7 9.7 12.2

in. cm.

[56.9] [49.0] [65.0] [6.1] [13.7] [35.3] [42.9] [14.5] [24.6] [31.0]

[20.6]

[28.3]

024 22.4 19.3 25.6 1" 1" 2.4 5.4 13.9 16.9 3/4" 3/8" 5.7 9.7 12.2

in. cm.

[56.9] [49.0] [65.0] [6.1] [13.7] [35.3] [42.9] [14.5] [24.6] [31.0]

[20.6]

[28.3]

030 22.4 19.3 25.6 1" 1" 2.4 5.4 13.9 16.9 7/8" 3/8" 5.7 9.7 12.2

in. cm.

[56.9] [49.0] [65.0] [6.1] [13.7] [35.3] [42.9] [14.5] [24.6] [31.0]

[20.6]

[28.3]

036 22.4 19.3 25.6 1" 1" 2.4 5.4 13.9 16.9 7/8" 3/8" 5.7 9.7 12.2

in. cm.

[56.9] [49.0] [65.0] [6.1] [13.7] [35.3] [42.9] [14.5] [24.6] [31.0]

[20.6]

[28.3]

042 25.4 21.3 30.6 1" 1" 2.4 5.4 15.9 18.9 7/8" 3/8" 8.1 11.7 14.2

in. cm.

[64.5] [54.1] [77.7] [6.1] [13.7] [40.4] [48.0] [20.6] [29.7] [36.1]

[23.2]

[30.8]

048 25.4 21.3 30.6 1" 1" 2.4 5.4 15.9 18.9 7/8" 3/8" 8.1 11.7 14.2

in. cm.

[64.5] [54.1] [77.7] [6.1] [13.7] [40.4] [48.0] [20.6] [29.7] [36.1]

[23.2]

[30.8]

060 25.4 21.3 30.6 1" 1" 2.4 5.4 15.9 18.9 1-1/8" 1/2" 8.1 11.7 14.2

in. cm.

[64.5] [54.1] [77.7] [6.1] [13.7] [40.4] [48.0]

[23.2] [20.6] [29.7] [36.1]

[30.8]

Rev.: 08/10/05D

Carrier GT-S — GT-GS Dimensional Data diagram (page 38)
図 47 · GT-GS Dimensional Data
Carrier GT-S — GT-GS Dimensional Data diagram (page 38)
図 48 · GT-GS Dimensional Data

3/4" HV Knockout

3/4" HV Knockout

1/2" LV Knockout

1/2" LV Knockout

Page 39 of the Carrier GT-S user manual — GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Units
39ページ · クリックして拡大
39ページ
Carrier GT-S — GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Units diagram (page 39)
図 49 · GT-GS (50YCS) & GT-S (38WQS) Performance Data - Engl…
Page 40 of the Carrier GT-S user manual — Compressor HWG Pump
40ページ · クリックして拡大
40ページ

Electrical Data

GT-PX (50YDS) Electrical Data

Compressor HWG Pump

External

Total

Min Circuit

Max Fuse/ HACR

Max Wire Ft.

Min AWG

Model

Pump

Unit FLA

(m) RLA LRA Qty

FLA

FLA

Amps

026 10.3 52 1 0.4 4.0 14.7 17.2 25 10 110 (33.5)

038 16.7 82 1 0.4 4.0 21.0 25.2 40 8 120 (36.5)

049 21.2 96 1 0.4 4.0 25.5 30.8 50 6 160 (48.5)

064 25.6 118 1 0.4 4.0 30.0 36.4 60 6 135 (41.0)

Rated Voltage of 208/230/60/1 Min/Max Voltage of 197/254 HACR circuit breaker in USA only All fuses Class RK-5 Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor

GT-GS (50YCS) Electrical Data

Compressor HWG Pump

External

Total

Min Circuit

Max Fuse/ HACR

Max Wire Ft

Min AWG

Model

Pump

Unit FLA

(m) RLA LRA Qty

FLA

FLA

Amps

018 9.0 42.0 1 0.40 4.0 13.4 15.7 20 12 80 (24.4)

024 10.3 56.0 1 0.40 4.0 14.6 17.2 25 10 110 (33.5)

030 12.2 67.0 1 0.40 4.0 16.5 19.6 30 10 100 (30.5)

036 13.5 73.0 1 0.40 4.0 17.8 21.2 30 10 90 (27.4)

042 16.5 95.0 1 0.40 4.0 20.9 25.0 40 8 120 (36.6)

048 18.3 109.0 1 0.40 4.0 22.7 27.3 45 6 180 (54.9)

060 25.0 169.0 1 0.40 4.0 29.3 35.6 60 6 140 (42.7)

Rated Voltage of 208/230/60/1 Min/Max Voltage of 197/254 HACR circuit breaker in USA only All fuses Class RK-5 Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor

GT-S (38WQS) Electrical Data

Compressor HWG Pump

Ext Loop

Total

Min Circuit

Max Fuse/ HACR

Max Wire Ft

Min AWG

Model

Pump

Unit FLA

(m) RLA LRA Qty Crank-

FLA

FLA

Amps

case

018 7.1 38.0 1 N/A 0.40 4.0 11.2 12.9 20 12 90 (27.4)

024 10.3 56.0 1 0.17 0.40 4.0 14.4 17.0 25 10 120 (36.6)

030 12.2 67.0 1 0.17 0.40 4.0 16.4 19.4 30 10 100 (30.5)

036 13.5 73.0 1 0.17 0.40 4.0 17.6 21.0 30 10 90 (27.4)

042 16.5 95.0 1 0.17 0.40 4.0 20.7 24.8 40 8 120 (36.6)

048 18.3 109.0 1 0.17 0.40 4.0 22.5 27.1 45 8 110 (33.5)

060 28.9 169.0 1 0.29 0.40 4.0 33.1 40.4 60 6 120 (36.6)

Rated Voltage of 208/230/60/1 Min/Max Voltage of 197/254 HACR circuit breaker in USA only All fuses Class RK-5 Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C copper conductor

Page 41 of the Carrier GT-S user manual — Typical Thermostat Wiring, Infi nity / Evolution Controls
41ページ · クリックして拡大
41ページ

Indoor & Outdoor Split Geothermal Comfort Systems

Thermostat Wiring

Thermostat Installation The thermostat should be located on an interior wall in a larger room, away from supply duct drafts. DO NOT locate the thermostat in areas subject to sunlight, drafts or on external walls. The wire access hole behind the thermostat may in certain cases need to be sealed to prevent erroneous temperature measurement. Position the thermostat back plate against the wall so that it appears level and so the thermostat wires protrude through the middle of the back plate. Mark the position of the back plate mounting holes and drill holes with a 3/16” (5mm) bit. Install supplied anchors and secure plate to the wall. Thermostat wire must be 18 AWG wire. Wire the appropriate thermostat as shown in Figures 28a through 28c to the low voltage terminal strip on the CXM control board. Practically any heat pump thermostat will work with these units, provided it has the correct number of heating and cooling stages.

Typical Thermostat Wiring, Single-Stage Units (2 Heat / 1 Cool)

Carrier GT-S — Typical Thermostat Wiring, Single-Stage Units (2 Heat / 1 Cool) diagram (page 41)
図 50 · Typical Thermostat Wiring, Single-Stage Units (2 Hea…

Typical Thermostat Wiring, Two-Stage Units (3 Heat / 2 Cool)

Carrier GT-S — Typical Thermostat Wiring, Two-Stage Units (3 Heat / 2 Cool) diagram (page 41)
図 51 · Typical Thermostat Wiring, Two-Stage Units (3 Heat /…

Typical Thermostat Wiring, Infi nity / Evolution Controls

Carrier GT-S — Typical Thermostat Wiring, Infi nity / Evolution Controls diagram (page 41)
図 52 · Typical Thermostat Wiring, Infi nity / Evolution Cont…
Page 42 of the Carrier GT-S user manual — CXM LED And Alarm Relay Operations
42ページ · クリックして拡大
42ページ

CXM Controls

CXM Control For detailed control information, see CXM/DXM Application, Operation and Maintenance (AOM) manual (part #97B0003N08).

2, the compressor will have a 3 second delay before energizing. Also, if set for stage 2, the alarm relay will NOT cycle during test mode. On = Stage 1. Off = Stage 2 DIP switch 3: Not Used. DIP switch 4: DDC Output at EH2 - provides selection for DDC operation. If set to “DDC Output at EH2,” the EH2 terminal will continuously output the last fault code of the controller. If set to “EH2 normal,” EH2 will operate as standard electric heat output. On = EH2 Normal. Off = DDC Output at EH2. NOTE: Some CXM controls only have a 2 position DIP switch package. If this is the case, this option can be selected by clipping the jumper which is in position 4 of SW1. Jumper not clipped = EH2 Normal. Jumper clipped = DDC Output at EH2. DIP switch 5: Factory Setting - Normal position is “On.” Do not change selection unless instructed to do so by the factory.

Field Selectable Inputs Test mode: Test mode allows the service technician to check the operation of the control in a timely manner. By momentarily shorting the test terminals, the CXM control enters a 20 minute test mode period in which all time delays are sped up 15 times. Upon entering test mode, the status LED will fl ash a code representing the last fault. For diagnostic ease at the thermostat, the alarm relay will also cycle during test mode. The alarm relay will cycle on and off similar to the status LED to indicate a code representing the last fault, at the thermostat. Test mode can be exited by shorting the test terminals for 3 seconds. Retry Mode: If the control is attempting a retry of a fault, the status LED will slow fl ash (slow fl ash = one fl ash every 2 seconds) to indicate the control is in the process of retrying.

CXM LED And Alarm Relay Operations

Field Confi guration Options Note: In the following fi eld confi guration options, jumper wires should be clipped ONLY when power is removed from the CXM control.

Description of Operation LED Alarm Relay

Normal Mode On Open Normal Mode with UPS Warning On Cycle (closed 5 sec., Open 25 sec.) CXM is non-functional Off Open Fault Retry Slow Flash Open Lockout Fast Flash Closed Over/Under Voltage Shutdown Slow Flash Open (Closed after 15 minutes)

Water coil low temperature limit setting: Jumper 3 (JW3- FP1 Low Temp) provides fi eld selection of temperature limit setting for FP1 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C]. Air coil low temperature limit setting: Jumper 2 (JW2- FP2 Low Temp) provides fi eld selection of temperature limit setting for FP2 of 30°F or 10°F [-1°F or -12°C] (refrigerant temperature). Note: This jumper should only be clipped under extenuating circumstances, as recommended by the factory. Not Clipped = 30°F [-1°C]. Clipped = 10°F [-12°C]. Alarm relay setting: Jumper 1 (JW1-AL2 Dry) provides fi eld selection of the alarm relay terminal AL2 to be jumpered to 24VAC or to be a dry contact (no connection). Not Clipped = AL2 connected to R. Clipped = AL2 dry contact (no connection).

Test Mode - No fault in memory Flashing Code 1 Cycling Code 1

Test Mode - HP Fault in memory Flashing Code 2 Cycling Code 2

Test Mode - LP Fault in memory Flashing Code 3 Cycling Code 3

Test Mode - FP1 Fault in memory Flashing Code 4 Cycling Code 4

Test Mode - FP2 Fault in memory Flashing Code 5 Cycling Code 5

Test Mode - CO Fault in memory Flashing Code 6 Cycling Code 6

Test Mode - Over/Under shutdown in memory Flashing Code 7 Cycling Code 7

Test Mode - UPS in memory Flashing Code 8 Cycling Code 8

Test Mode - Swapped Thermistor Flashing Code 9 Cycling Code 9

-Slow Flash = 1 fl ash every 2 seconds -Fast Flash = 2 fl ashes every 1 second -Flash code 2 = 2 quick fl ashes, 10 second pause, 2 quick

fl ashes, 10 second pause, etc. -On pulse 1/3 second; off pulse 1/3 second

DIP Switches Note: In the following fi eld confi guration options, DIP switches should only be changed when power is removed from the CXM control. DIP switch 1: Unit Performance Sentinel Disable - provides fi eld selection to disable the UPS feature. On = Enabled. Off = Disabled. DIP switch 2: Stage 2 Selection - provides selection of whether compressor has an “on” delay. If set to stage

Page 43 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
43ページ · クリックして拡大
43ページ

Indoor & Outdoor Split Geothermal Comfort Systems

CXM Controls

Safety Features – CXM Control The safety features below are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions. Anti-short cycle protection: The control features a 5 minute anti-short cycle protection for the compressor. Note: The 5 minute anti-short cycle also occurs at power up. Random start: The control features a random start upon power up of 5-80 seconds. Fault Retry: In Fault Retry mode, the Status LED begins slowly fl ashing to signal that the control is trying to recover from a fault input. The control will stage off the outputs and then “try again” to satisfy the thermostat input call. Once the thermostat input call is satisfi ed, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat input call, the control will go into “lockout” mode. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Note: FP1/FP2 faults are factory set at only one try. Lockout: In lockout mode, the status LED will begin fast fl ashing. The compressor relay is turned off immediately. Lockout mode can be “soft” reset by turning off the thermostat (or satisfying the call). A “soft” reset keeps the fault in memory but resets the control. A “hard” reset (disconnecting power to the control) resets the control and erases fault memory. Lockout with emergency heat: While in lockout mode, if W becomes active (CXM), emergency heat mode will occur. High pressure switch: When the high pressure switch opens due to high refrigerant pressures, the compressor relay is de-energized immediately since the high pressure switch is in series with the compressor contactor coil. The high pressure fault recognition is immediate (does not delay for 30 continuous seconds before de-energizing the compressor). High pressure lockout code = 2 Example: 2 quick fl ashes, 10 sec pause, 2 quick fl ashes, 10 sec. pause, etc. Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during “on” cycle to be recognized as a low pressure fault. If the low pressure switch is open for 30 seconds prior to compressor power up it will be considered a low pressure (loss of charge) fault. The low pressure switch input is bypassed for the initial 60 seconds of a compressor run cycle. Low pressure lockout code = 3 Water coil low temperature (FP1): The FP1 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a FP1 fault. The FP1 input is bypassed for the initial 60 seconds of a compressor run cycle. FP1 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP1 fault has occurred. FP1 lockout code = 4

Air coil low temperature (FP2): The FP2 thermistor temperature must be below the selected low temperature limit setting for 30 continuous seconds during a compressor run cycle to be recognized as a FP2 fault. The FP2 input is bypassed for the initial 60 seconds of a compressor run cycle. FP2 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP2 fault has occurred. FP2 lockout code = 5 Condensate overfl ow: The condensate overfl ow sensor must sense overfl ow level for 30 continuous seconds to be recognized as a CO fault. Condensate overfl ow will be monitored at all times. CO lockout code = 6 Over/under voltage shutdown: An over/under voltage condition exists when the control voltage is outside the range of 19VAC to 30VAC. Over/under voltage shut down is a self-resetting safety. If the voltage comes back within range for at least 0.5 seconds, normal operation is restored. This is not considered a fault or lockout. If the CXM is in over/under voltage shutdown for 15 minutes, the alarm relay will close. Over/under voltage shut down code = 7 Unit Performance Sentinel-UPS (patent pending): The UPS feature indicates when the heat pump is operating ineffi ciently. A UPS condition exists when: a) In heating mode with compressor energized, FP2

is greater than 125°F [52°C] for 30 continuous seconds, or: b) In cooling mode with compressor energized, FP1

is greater than 125°F [52°C] for 30 continuous seconds, or: c) In cooling mode with compressor energized, FP2 is

less than 40°F [4.5°C] for 30 continuous seconds. If a UPS condition occurs, the control will immediately go to UPS warning. The status LED will remain on as if the control is in normal mode. Outputs of the control, excluding LED and alarm relay, will NOT be affected by UPS. The UPS condition cannot occur during a compressor off cycle. During UPS warning, the alarm relay will cycle on and off. The cycle rate will be “on” for 5 seconds, “off” for 25 seconds, “on” for 5 seconds, “off” for 25 seconds, etc. UPS warning code = 8 Swapped FP1/FP2 thermistors: During test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate places. If the control is in test mode, the control will lockout, with code 9, after 30 seconds if: a) The compressor is on in the cooling mode and the

FP1 sensor is colder than the FP2 sensor, or: b) The compressor is on in the heating mode and the

FP2 sensor is colder than the FP1 sensor. Swapped FP1/FP2 thermistor code = 9.

Page 44 of the Carrier GT-S user manual — GT-PX GT-GS / GT-S GT-GS / GT-S
44ページ · クリックして拡大
44ページ

CXM Controls

Diagnostic Features The LED on the CXM board advises the technician of the current status of the CXM control. The LED can display either the current CXM mode or the last fault in memory if in test mode. If there is no fault in memory, the LED will fl ash Code 1 (when in test mode). CXM Control Start-up Operation The control will not operate until all inputs and safety controls are checked for normal conditions. The compressor will have a 5 minute anti-short cycle delay at power-up. The fi rst time after power-up that there is a call for compressor, the compressor will follow a 5 to 80 second random start delay. After the random start delay and anti-short cycle delay, the compressor relay will be energized. On all subsequent compressor calls, the random start delay is omitted.

Unit Operation

GT-PX GT-GS / GT-S GT-GS / GT-S

TTS GSS/PDW GSS/PDW

T-stat signal

Variable Speed

Variable Speed

PSC Air Handler

Air Handler

Air Handler

G Fan only Fan only Fan only

1 Stage 1 heating

3 Stage 1 heating

G, Y or Y1 Stage 1 heating

1 Stage 2 heating

3 Stage 2 heating

G, Y1, Y2 Stage 2 heating

G, Y1, Y2, W Stage 3 heating

1 Stage 3 heating

3 N/A

G, W Emergency heat Emergency heat Emergency heat

G, Y or Y1, O Stage 1 cooling

2 Stage 1 cooling

4 Cooling

G, Y1, Y2, O Stage 2 cooling

2 Stage 2 cooling

4 N/A

1 Stage 1 = 1st stage compressor, 1st stage fan operation Stage 2 = 2nd stage compressor, 2nd stage fan operation Stage 3 = 2nd stage compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings) 2 Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve 3 Stage 1 = compressor, 1st stage fan operation Stage 2 = compressor, 2nd stage fan operation Stage 3 = compressor, auxiliary electric heat, 2nd or 3rd stage fan operation (depending on fan settings) 4 Stage 1 = compressor, 1st stage fan operation, reversing valve Stage 2 = compressor, 2nd stage fan operation, reversing valve 5 Stage 1 = compressor, fan Stage 2 = compressor, auxiliary electric heat, fan 6 Cooling = compressor, fan, reversing valve

Page 45 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
45ページ · クリックして拡大
45ページ

Indoor & Outdoor Split Geothermal Comfort Systems

GT-PX Split Wiring Diagram

Carrier GT-S — Indoor & Outdoor Split Geothermal Comfort Systems diagram (page 45)
図 53 · Indoor & Outdoor Split Geothermal Comfort Systems
Page 46 of the Carrier GT-S user manual — GT-GS Split Wiring Diagram
46ページ · クリックして拡大
46ページ

GT-GS Split Wiring Diagram

Carrier GT-S — GT-GS Split Wiring Diagram diagram (page 46)
図 54 · GT-GS Split Wiring Diagram
Page 47 of the Carrier GT-S user manual — Indoor & Outdoor Split Geothermal Comfort Systems
47ページ · クリックして拡大
47ページ

Indoor & Outdoor Split Geothermal Comfort Systems

GT-S Split Wiring Diagram

Carrier GT-S — Indoor & Outdoor Split Geothermal Comfort Systems diagram (page 47)
図 55 · Indoor & Outdoor Split Geothermal Comfort Systems
Page 48 of the Carrier GT-S user manual — Compressor Section 026 038 049 064
48ページ · クリックして拡大
48ページ

Equipment Selection

The installation of geothermal heat pump units and all associated components, parts, and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the installing contractor to determine and comply with ALL applicable codes and regulations.

Indoor Coil Selection - GT-PX (50YDS) Puron® Geothermal Split System Geothermal split system heat pumps are rated in the ARI directory with a specifi c indoor coil match. GT- PX Puron split system (50YDS) models are rated with Carrier/Bryant FV4 or FE4 series variable speed air handlers as shown in Table 1a. Other combinations (e.g. variable speed furnace with cased coil) may attain the same ARI ratings providing that the specifi cations meet or exceed those listed in Table 1a AND Table 1b. An ECM motor and TXV is required. Cap tubes and fi xed orifi ces are not acceptable. PSC fans may be used if matched to Table 1b, but will not meet ARI ratings. If using PSC fan, compressor section must be operated as a single stage unit (i.e. wired for either 1st stage or 2nd stage). Without the ability to vary the airfl ow, supply air temperatures may not be acceptable if the compressor is allowed to change stages when used with a PSC fan motor.

General Proper indoor coil selection is critical to system effi ciency. Using an older-model coil can affect effi ciency and may not provide the customer with rated or advertised EER and COP. Coil design and technology have dramatically improved operating effi ciency and capacity in the past 20 years. Homeowners using an older coil are not reaping these cost savings and comfort benefi ts. NEVER MATCH AN R-22 INDOOR COIL WITH AN R-410A COMPRESSOR SECTION.

Newer indoor coils have a larger surface area, enhanced fi n design, and grooved tubing. These features provide a larger area for heat transfer, improving effi ciency and expanding capacity. Typical older coils may only have one-third to one-half the face area of these redesigned coils.

Table 1aGT-PX (50YDS) Puron® Geothermal Split System Air Handler Matches for ARI Ratings

GT-PX Air Handler Matches for ARI Ratings

Compressor Section 026 038 049 064

Air Handler Model FV4 or FE4 003 005 006 006

Refrigerant R-410A

Metering Device TXV (required)

Air Coil Type Rows - Fins/in. Face Area (sq. ft.)

Slope 3 - 14.5 3.46

A 3 - 14.5 5.93

A 3 - 14.5 7.42

A 3 - 14.5 7.42

Cabinet Confi guration Upfl ow / Downfl ow / Horizontal (Multipoise)

AC/HP size: 036

AC/HP size: 036

AC/HP size: 048

AC/HP size: 060

ECM Settings for ARI Ratings (FV4 Fan Coil)

System Type: Comfort AC/HP CFM Adjust: Nom

System Type: HP-Effi c AC/HP CFM Adjust: High

System Type: Comfort AC/HP CFM Adjust: High

System Type: Comfort AC/HP CFM Adjust: High

Fan Motor Type - HP ECM - 1/2 ECM - 1/2 ECM - 3/4 ECM - 3/4

Page 49 of the Carrier GT-S user manual — Nominal
49ページ · クリックして拡大
49ページ

Indoor & Outdoor Split Geothermal Comfort Systems

Equipment Selection

Table 1bSelection of Coils other than Above Models for Puron® Geothermal Split Systems

GT-PX Air Handler Characteristics for Brands other than Above Models

Add-on CK5P

FX4 PSC

Model* Nominal

Evaporator

Temp (ºF) CFM Capacity (MBtuh)**

Coil with TXV

Fan Coil (not an ARI rated

Tons*

AND Vspd

furn.

combination)

26. Part Load 1.5 50 530 19.2 - 22.4 A/T/W 036 018
26. Full Load 2.0 52 880 24.2 - 28.2 A/T/W 036 030
38. Part Load 2.5 51 700 25.2 - 29.2 A/T/W 048 036
38. Full Load 3.0 50 1200 34.5 - 40.1 A/T 060 036
49. Part Load 3.5 47 1000 34.3 - 39.9 A/T 060 042

049 - Full Load 4.0 48 1650 46.3 - 53.8 X060 048

64. Full Load 5.0 48 1850 54.5 - 63.3 2 - A/T/W 036 060

* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. Two-stage units may be operated in single-stage mode if desired, where smaller capacity is required. For example, a model 026 may be used as a 1-1/2 ton unit if “locked” into 1st stage operation only. If PSC fan is used, unit must be “locked” into either 1st or 2nd stage. An ECM fan is required for two-stage operation and for ARI ratings. Size air handler for “Full Load” if operating in two-stage mode. **When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature, CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in order for the ARI rating condition to be valid. See Figure 1 for an example selection.

Indoor Coil Selection - R-22 Units Geothermal split system heat pumps with R-22 refrigerant are rated in the ARI directory with a “generic” indoor coil match and PSC fan. Selection of air handlers that attain the published ARI ratings must meet or exceed the specifi cations listed in Table 2. A TXV is required. Cap tubes and fi xed orifi ces are not acceptable.

Table 2: R-22 Air Handler Characteristics

R-22 Air Handler Characteristics

Nominal

Evaporator

Capacity (MBtuh)**

Model*

Tons*

Temp (ºF) CFM

018 1.5 50 600 18.5 - 21.3

024 2.0 47 800 25.5 - 29.3

030 2.5 49 1000 31.5 - 36.2

036 3.0 48 1200 37.0 - 42.5

042 3.5 45 1400 42.2 - 48.5

048 4.0 46 1600 50.0 - 57.5

060 5.0 45 2000 58.0 - 66.7

* Nominal tons are at ARI/ISO 13256-1 GLHP conditions. **When selecting an air handler based upon the above conditions, choose entering WB temperature of 67ºF. Use evaporator temperature, CFM and capacity requirements as listed above. The air handler capacity must be at least at the minimum capacity shown in the table in order for the ARI rating condition to be valid. See Figure 1 for an example selection.

Page 50 of the Carrier GT-S user manual — Selecting Air Handler
50ページ · クリックして拡大
50ページ

Equipment Selection

Air Handler Selection Example Figure 1 shows a typical peformance table for a heat pump air handler. Suppose the evaporator temperature required is 50ºF, the capacity required is 35,000 Btuh and the airfl ow required is 1,200 CFM. Each evaporator temperature listed in the table shows three wet bulb temperatures. As recommended in the table notes above, select the 67ºF WB column. At 1,200 CFM, the model 003 capacity is 36 MBtuh, which is higher than the minimum capacity required of 35,000 Btuh. In this example, model 003 would be the appropriate match.

Selecting Air Handler

Figure 1: Selecting Air Handler

Carrier GT-S — Selecting Air Handler diagram (page 50)
図 56 · Selecting Air Handler
  • Utilizing the Existing Air Handler or Coil (R22 units only) It is recommended that a new coil or air handler be installed with any geothermal split system compressor section due to the low initial cost of the additional equipment versus the reliability and benefi t of new technology, increased reliability and warranty. However, if the existing air handler must be used (R22 systems only), the following conditions apply:
  • If the existing coil currently uses an orifi ce, the orifi ce must be removed and replaced with a TXV. If the coil utilizes capillary tubes, it will not operate properly with the geothermal split system and should be replaced.
  • If life expectancy of indoor coil (and associated components - fan, cabinet, etc.) is less than 7-10 years, indoor section should be replaced.
Page 51 of the Carrier GT-S user manual — Two-Stage Indoor Split
51ページ · クリックして拡大
51ページ

Two-Stage Indoor Split

GT-PX Split (50YDS) Series

Puron ® Systems

General The liquid source heating/cooling split condensing units shall be ARI/ISO/ASHRAE 13256-1 (ground- source closed-loop) performance certifi ed and listed by a nationally recognized safety-testing laboratory or agency, such as the Canadian Standards Association (CSA US). Each unit shall be water run-tested at the factory. Each unit shall be pallet mounted and shipped with appropriate protective packaging to help avoid damage in transportation. The units shall be warranted by the manufacturer against defects in materials and workmanship for a period of fi ve years on all parts, and ten years on the compressor and refrigerant circuit parts with a service labor allowance during the fi rst 30 days. An optional extended warranty is available for the GT-PX Series units, which adds a labor allowance and trip charge. The water source units shall be designed to operate with entering fl uid temperature between 20°F and 120°F.

Electrical CXM Control - A microprocessor-based compressor controller shall be provided to monitor and control unit operation. The control shall provide compressor sequencing, high and low pressure monitoring, fi eld selectable low water temperature sensing, over/under voltage monitoring, and unit performance sentinel (UPS). The control shall also provide for water valve connection, a test mode, short cycle protection, random start-up, as well as fault LED, fault memory, and intelligent fault retry.

The control shall employ quick attach harness assemblies for low voltage connections to the control board to aid in troubleshooting or replacement. An integral terminal block with screw terminals shall be provided on the control for fi eld low voltage connections. A circuit breaker protected 75VA transformer shall be employed. Line voltage box lugs shall be provided for unit wiring. Units shall have knockouts for entrance of low and line voltage wiring. The control box shall be harness plug-connected for easy removal. Residential models shall have a dual circut-breaker protected power block for the connection of external Flow Controller pump module.

Casing & Cabinet The cabinet shall be fabricated from heavy-gauge galvanized steel and painted with an epoxy powder coating. The interior shall be insulated with 1/2” thick, multi-density, coated glass fi ber. Three compressor compartment access panels shall be provided and shall be removable with linesets and water piping in place. The internal component layout shall provide for major service with the unit in-place for restricted access installations.

Piping Supply and return water connections, as well as Hot Water Generator (desuperheater) connections shall be 1” FPT brass swivel fi ttings which provide a union and eliminate the need for pipe wrenches and sealants when making fi eld connections. A thread by sweat fi tting shall be provided for connection to the water heater. All water piping shall be insulated to prevent condensation at low liquid temperatures.

Refrigerant Circuit All units shall contain Puron® (HFC 410A) sealed refrigerant circuit employing a hermetic motor compressor, bidirectional thermal expansion valve, reversing valve, coaxial tube water-to-refrigerant heat exchanger and service ports. An optional Hot Water Generator (desuperheater) coil shall be provided. Compressors shall be Copeland UltraTech™ Two- Stage scroll type designed for heat pump duty and mounted on spring vibration isolators. Compressor motors shall be single phase PSC with internal over load protection. A factory provided bidirectional fi lter drier shall be included in all models. The coaxial water- to-refrigerant heat exchangers shall be designed for close approach temperatures and be construct ed of a convoluted copper (optional cupronickel) inner tube and a steel outer tube. The thermal expansion valve shall provide proper superheat over the entire fl uid temperature range with minimal “hunting”. The valve shall operate only in the heating mode with the use of an internal check valve. The water-to-refrigerant heat exchanger, optional desuperheater coil and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures.

Page 52 of the Carrier GT-S user manual — GT-GS
52ページ · クリックして拡大
52ページ

GT-GS

GT-GS Indoor Split (50YCS) Series

General The liquid source heating/cooling split con dens ing units shall be ARI/ASHRAE/ISO 13256-1 loop per for mance certifi ed and listed by a nationally recognized safety- testing laboratory or agency, such as Un der writ er’s Lab o ra to ry (UL), or Canadian Stan dards Association (CSA-US). Each unit shall be water run-tested at the factory. Each unit shall be pallet mounted and shipped in clear shrink wrap for visual shipping damage inspection. The units shall be war rant ed by the man u fac tur er against defects in materials and workmanship for a period of fi ve years on all parts, and ten years on the compressor and refrigerant circuit parts with a service labor allowance during the fi rst 30 days. An optional extended war ran ty is available for the GT-GS Split Series units, which adds a labor allowance and trip charge. The liquid source units shall be designed to operate with entering liquid temperature between 20°F and 120°F.

Electrical CXM Control - A microprocessor-based compressor controller (CXM) shall be provided to monitor and control unit operation. The control shall provide high and low pressure monitoring, fi eld selectable water and air coil low water temperature sensing, over/under voltage monitoring, and unit performance sentinel (UPS). The control shall also provide for water valve connection, a test mode, short cycle protection, random start-up, as well as fault LED, fault mem o ry, and intelligent fault retry.

The control shall employ quick attach harness as sem blies for low voltage connections to the control board to aid in troubleshooting or replacement. An integral terminal block with screw ter mi nals shall be provided on the control for all fi eld low voltage connections. Line voltage lugs shall be provided for unit wiring. Units shall have knockouts for entrance of low and line voltage wiring. The control box shall be harness plug-connected for easy removal.

Casing & Cabinet The cabinet shall be designed for indoor installations. The cabinet shall be fabricated from heavy-gauge galvanized steel painted with a epoxy powder coat paint with a 1000 hr. salt spray test rating. The interior shall be insulated with 1/2" thick, multi-density, coated glass fi ber with edges sealed or tucked under fl anges. Three compressor com part ment access panels shall be provided and shall be removable with linesets and water piping in place. The internal com po nent layout shall provide for major service with the unit in-place for restricted access installations.

Piping Supply and return water connections shall be 1" swivel fi ttings. All water piping shall be insulated to prevent con den sa tion at low liquid temperatures.

Refrigerant Circuit All units shall contain split refrigerant circuits employing a hermetically sealed com pres sor, thermal expansion valve, reversing valve, coaxial tube water-to-refrigerant heat exchanger, service ports, and backseating service valves. Compressors shall be high-effi ciency advanced scroll type designed for heat pump duty and mounted on spring vibration isolators. Compressor motors shall be single phase PSC with internal overload pro tec tion. A factory installed bidirectional fi lter drier shall be provided. The coaxial water-to-refrigerant heat exchanger shall be designed for close approach temperatures and be con struct ed of a convoluted copper (optional cupronickel) inner tube and a steel outer tube. The thermal expansion valve shall provide proper superheat over the entire liquid temperature range with min i mal “hunting”. The valve shall operate only in the heating mode with the use of an internal check valve. The water-to-refrigerant heat exchanger and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures. Air coil con nec tions shall be made through brass backseating service valves with built-in Schrader ports.

Page 53 of the Carrier GT-S user manual — Single-Stage Outdoor Split
53ページ · クリックして拡大
53ページ

Single-Stage Outdoor Split

GT-S Outdoor Split (38WQS) Series

R22 Systems

General The liquid source heating/cooling split con dens ing units shall be ARI/ASHRAE/ISO 13256-1 loop per for mance certifi ed and listed by a nationally recognized safety- testing laboratory or agency, such as Un der writ er’s Lab o ra to ry (UL), or Canadian Stan dards Association (CSA-US). Each unit shall be water run-tested at the factory. Each unit shall be pallet mounted and shipped in clear shrink wrap for visual shipping damage inspection. The units shall be war rant ed by the man u fac tur er against defects in materials and workmanship for a period of fi ve years on all parts, and ten years on the compressor and refrigerant circuit parts with a service labor allowance during the fi rst 30 days. An optional extended war ran ty is available for the GT-S Split Series units, which adds a labor allowance and trip charge. The liquid source units shall be designed to operate with entering liquid temperature between 20°F and 120°F.

be made through brass backseating service valves with built-in Schrader ports. Hot Water Generator (desuperheater) connections shall be accomplished with 1/2” backseating service valves.

Electrical CXM Control - A microprocessor-based compressor controller (CXM) shall be provided to monitor and control unit operation. The control shall provide high and low pressure monitoring, fi eld selectable low water temperature sensing, over/under voltage monitoring, and unit performance sentinel (UPS). The control shall also provide for water valve connection, a test mode, short cycle protection, random start-up, as well as fault LED, fault mem o ry, and intelligent fault retry.

The control shall employ quick attach harness as sem blies for low voltage connections to the control board to aid in troubleshooting or replacement. An integral terminal block with screw ter mi nals shall be provided on the control for all fi eld low voltage connections. Line voltage lugs shall be provided for unit wiring. Units shall have knockouts for entrance of low and line voltage wiring. The control box shall be harness plug-connected for easy removal.

Casing & Cabinet The cabinet shall be weather resistant and designed for outdoor installations. The cabinet shall be fabricated from heavy-gauge galvanized steel painted with a epoxy powder coat paint with a 1000 hr. salt spray test rating. The interior shall be insulated with 1/2" thick, multi-density, coated glass fi ber with edges sealed or tucked under fl anges. Two compressor com part ment access panels shall be provided and shall be removable with linesets and water piping in place. The internal com po nent layout shall provide for major service with the unit in-place for restricted access installations. The cabinet shall provide adequate space to house the one or two pump Flow Controller pumping module within the cabinet.

Piping Supply and return water connections shall be 1-1/4" MPT fi ttings. All water piping shall be insulated to prevent con den sa tion at low liquid temperatures.

Refrigerant Circuit All units shall contain split refrigerant circuits employing a hermetically sealed com pres sor, thermal expansion valve, reversing valve, coaxial tube water-to-refrigerant heat exchanger, service ports, and backseating service valves. Compressors shall be high-effi ciency advanced scroll or rotary type designed for heat pump duty and mounted on vibration isolators. Compressor motors shall be single phase PSC with internal overload pro tec tion. A factory installed bidirectional fi lter drier shall be provided. The coaxial water-to-refrigerant heat exchanger shall be designed for close approach temperatures and be con struct ed of a convoluted copper (optional cupronickel) inner tube and a steel outer tube. The thermal expansion valve shall provide proper superheat over the entire liquid temperature range with min i mal “hunting”. The valve shall operate only in the heating mode with the use of an internal check valve. The water-to-refrigerant heat exchanger and refrigerant suction lines shall be insulated to prevent condensation at low liquid temperatures. Air coil con nec tions shall

Page 54 of the Carrier GT-S user manual — GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Units
54ページ · クリックして拡大
54ページ

Accessories & Options Hot Water Generator (internal) - GT-PX & GT-GS units only An optional heat reclaiming desuperheater coil of vented double-wall copper construction suitable for potable water shall be provided. The coil and hot water circulating pump shall be factory mounted inside the unit. A high limit (GT-PX/GT-GS units) and low compressor discharge line temperature switch (GT-PX units) shall be provided to disable the pump when these conditions occur.

Cooling TXV Kit (fi eld installed) - R-22 GT-GS & GT-S units only A cooling ther mo stat ic expansion valve kit shall be provided to be fi eld installed on the A-Coil or at the air handler.

Warranty Information The Carrier residential warranty refl ects the reliability built in to every unit and includes fi ve years on all parts, and ten years on the compressor and refrigerant circuit parts with a service labor allowance during the fi rst 30 days. An optional extended warranty is available for residential units, which adds a labor allowance and trip charge. See extended warranty certifi cate (CA186) for details.

Hot Water Generator (fi eld installed) - GT-S units only An optional heat reclaiming Hot Water Generator (desuperheater) Remote Module with vented double-wall copper con struc tion suitable for potable water shall be provided as a fi eld installed accessory. A high limit shut-off switch shall be provided. The HWG Remote Module shall be located remote from the compressor section, near the water heater, and shall include an internal pump and water coil.

Cupro-Nickel Heat Exchanger An optional corrosion resistant CuNi coaxial heat exchanger shall be factory installed in lieu of standard copper construction.

Thermostat (fi eld in stalled) A multistage auto-changeover electronic digital ther mo stat shall be pro vid ed. The thermostat shall offer 2 heating and 1 cooling stages (GT-GS/GT-S units) or 3 heating and 2 cooling stages (GT-PX units) with precise temperature control. An OFF-HEAT-AUTO-COOL- EMERG system switch, OFF-AUTO fan switch, and in di cat ing LED’s shall be provided. The thermostat shall read out in °F or °C and be calibratable.

Flow Controller (fi eld installed) A self-contained module shall provide all fl uid pumping, fi ll and connection requirements for ground-source closed loop systems up to 20 GPM. The Flow Controller shall provide 1” pump isolation valves and 3-way service valves. Pump heads shall be removable from the volute for easy replacement. The Flow Controller shall be enclosed in a galvanized steel or plastic case and fully insulated with urethane foam to prevent condensation. The Flow Controller shall have a 5-year warranty on all parts.

Hose Kits (fi eld installed) - GT-PX & GT-GS only A rubber hose kit shall provide connections between the unit and Flow Controller. Rubber 1” hose allows fl exible connection and absorbs vibration transmission between unit and Flow Controller. Brass elbows with MPT fi ttings for unit connection, barbed fi ttings for hose connection and FPT fi ttings for Pressure/Temperature ports shall be included to allow service and troubleshooting of the unit. Hose clamps shall be used to connect the hose to the brass elbows and Flow Controller.

Page 55 of the Carrier GT-S user manual — GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Units
55ページ · クリックして拡大
55ページ
Page 55 of the Carrier GT-S user manual — GT-GS (50YCS) & GT-S (38WQS) Performance Data - English (IP) Units
Page 56 of the Carrier GT-S user manual — Revision Log
56ページ · クリックして拡大
56ページ

7300 S.W. 44th Street Oklahoma City, OK 73179

Phone: 405-745-2920

Fax: 405-745-6620

Carrier works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may

not be as described herein. Please contact Carrier’s Customer Service Department at 1-405-745-2920 for specifi c information on the current design and spec i fi ca tions.

Statements and other in for ma tion contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely Carrier’s

CA204 Rev.: 08/10/05D

© Carrier, Inc. 2005

08/10/05 All First Published

Date Page Description

opinion or com men da tion of its products.

Revision Log

Carrier GT-Sについて質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Carrier GT-Sに関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

Carrier GT-S 取扱説明書(PDF)

56 ページ·2.1 MB·ヒートポンプ·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…