Page 1 of 2 7 3/8" Triple Tube Horizontal Lamp
7 3/4" (197 mm)
11 3/8" (289 mm)
5 3/4" (146 mm)
1" (25 mm) min.- 2 1/8" (54 mm) max. (Ceiling Runner)
1 1/8" (29 mm) max. Ceiling Thickness
7 3/8" (187 mm) Dia.
7 7/8" Trimless (200 mm)
8 5/8" Self-Flanged Trim (209 mm)
Ceiling Cutout: 8" (203 mm) Dia.
Features 1. Reflector: 16 ga. Alzak® aluminum, 55° visual cutoff to lamp and lamp image, wide distribution. Iridescence Free finish. Self-flanged or flangeless with molded white trim ring (field paintable). 2. Socket Cup: Snaps onto reflector neck to assure consistently correct optical alignment without tools. 4. Retaining Springs: Precision-tooled steel friction springs secure reflector to mounting frame for quick, tool-less installation. 5. Mounting Brackets: 16 ga. steel. Adjust from inside of fixture. Use 3/4” or 1 1/2” lathing channel, 1/2” EMT, or optional mounting bars. 6. Ballast/J-Box: Outboard mounted to reduce heat transfer and maintain lamp efficacy and life. Service from below without tools.
Options and Accessories (continued) Emergency Add suffix EM* Chicago Plenum Add suffix LC Existing/Thk. Ceiling FA EC7* Emergency Ltg. Kit FA EM3E* FA EM4E* Fuse (Slow Blow) Add Suffix F *See Spec. Sheets: FAEC, FAEM
Mounting Bars & Accessories; see Specification Sheet MBA. Sloped Ceiling Adapters; see Specification Sheet SCA.
Labels UL listed for damp locations, I.B.E.W.
Electrical Note: Note: For ballast electrical data and latest lamp/ballast compatibility refer to “Ballast” specification sheet for complete electrical data.
Alzak® is a registered trademark of ALCOA

UL Listed for through branch circuit wiring with max of (8) No 12 AWG, 90 degree C supply conductors.
Options and Accessories Comfort Clear™ Finishes1 Other Finishes Clear CCL White WH Diffuse CCD Multigroove MG Champagne Bronze CCZ
1Specify desired flange W White, P Polished Blank - Molded Ring

Page 2 of 2 7 3/8" Triple Tube Horizontal Lamp


ROOM SURFACE REFLECTANCES: 80% Ceiling; 50% Wall; 20% Floor 3200 Lumens Per Lamp RCR= 1 (Rm. Width= 10xMtg. Ht. above work plane) RCR= 5 (Rm. Width= 2xMtg. Ht. above work plane) RCR=10 (Rm. Width= Mtg. Ht. above work plane)
AREA PER FIXTURE IN SQUARE FEET 3 4 5 6 7 8 9 10 11 12 13 14
CENTER TO CENTER DISTANCE OF FIXTURES IN FEET This quick calculator chart determines the number and spacing of 1 It.- 42W PL-T units with clear reflector, for any level of illumination.
Spacing Ratio = 1.3 Report No.: LRL 796-1G PREPARED BY: LIGHTING RESEARCH LABORATORY, INC PREPARED FOR: LIGHTOLIER DESCRIP.: 7-3/8" dia. x 7" Ht. recessed downlight
Spacing Ratio = 1.4 Report No.: LRL 796-1F PREPARED BY: LIGHTING RESEARCH LABORATORY, INC PREPARED FOR: LIGHTOLIER DESCRIP.: 7-3/8" dia. x 7" Ht. recessed downlight
- open bottom spun semispecular reflector; tilted horizontal lamp BALLAST: LIGHTOLIER GLT423-120I. LAMPS: 1 PLT-32W rated at 2400 LUMENS.
- open bottom spun semispecular reflector; tilted horizontal lamp BALLAST: LIGHTOLIER GLT423-120I. LAMPS: 1 PLT-42W rated at 3200 LUMENS.
CANDLEPOWER ZONE 0 22 45 67 90 DEG. CANDELAS 90 85 0 0 1 1 1 80 1 75 1 2 70 2 2 3 3 3 65 4 60 9 9 10 11 10 55 70 67 71 73 69 50 235 247 270 282 282 45 328 333 377 430 462 40 437 461 534 572 604 35 598 585 632 654 683 30 701 656 665 728 760 25 746 728 748 784 788 20 759 802 807 811 808 15 841 893 894 892 890 10 897 921 919 916 915 5 889 892 895 899 902 0 883
CANDLEPOWER ZONE 0 22 45 67 90 DEG. CANDELAS 90 85 1 80 1 75 3 70 3 65 4 60 9 55 93 99 80 77 78 50 436 409 436 398 413 45 634 622 634 663 680 40 737 758 800 850 850 35 866 905 920 951 948 30 975 964 923 1022 1049 25 1045 1050 1030 1066 1103 20 1053 1070 1077 1117 1148 15 1074 1097 1148 1141 1176 10 1046 1076 1091 1099 1121 5 1004 1009 1017 1021 1020 0 1002
75 ϒ
60 ϒ
65 ϒ
55 ϒ
45 ϒ
25ϒ 35ϒ 15ϒ 5ϒ 0ϒ
ZONE LUMENS %BARE LAMP %LUMINAIRE
ZONE LUMENS %BARE LAMP %LUMINAIRE 0-30 896 28.0 42.8 0-40 1465 45.8 70.0 0-60 2084 65.1 99.6 0-90 2092 65.4 100.0 40-90 627 19.6 30.0 60-90 8 0.3 0.4 90-120 0 0.0 0.0 90-150 0 0.0 0.0 90-180 0 0.0 0.0 0-180 2092 65.4 100.0
0-30 681 28.4 46.3 0-40 1069 44.6 72.7 0-60 1463 61.0 99.5 0-90 1470 61.3 100.0 40-90 401 16.7 27.3 60-90 7 0.3 0.5 90-120 0 0.0 0.0 90-150 0 0.0 0.0 90-180 0 0.0 0.0 0-180 1470 61.3 100.0
Coefficients Of Utilization
Coefficients Of Utilization
% EFFECTIVE CEILING CAVITY REFLECTANCE 80 70 50 30 10 0 % WALL REFLECTANCE 50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0
1 .67 .65 .63 .65 .64 .62 .63 .61 .60 .60 .59 .58 .58 .58 .57 .56 2 .61 .58 .55 .60 .57 .55 .58 .55 .54 .56 .54 .52 .54 .53 .51 .50 3 .55 .52 .49 .55 .51 .49 .53 .50 .48 .51 .49 .47 .50 .48 .46 .45 4 .51 .47 .44 .50 .46 .43 .49 .45 .43 .47 .45 .42 .46 .44 .42 .41 5 .47 .42 .39 .46 .42 .39 .45 .41 .39 .44 .41 .38 .43 .40 38 .37 6 .43 .38 .35 .42 .38 .35 .41 .38 .35 .40 .37 .35 .39 .37 .34 .33 7 .39 .35 .39 .35 .32 .38 .34 .32 .37 .34 .31 .37 .34 .31 .30 .25 8 .36 .32 .29 .36 .32 .29 .35 .32 .29 .35 .31 .29 .34 .31 .29 .28 9 .34 .30 .27 .33 .29 .27 .33 .29 .27 .32 .29 .26 .32 .29 .26 .25 10 .31 .27 .25 .31 .27 .24 .31 .27 .24 .30 .27 .24 .30 .26 .24 .23
ROOM CAVITY RATIO
20% FLOOR CAVITY REFLECTANCE
20% FLOOR CAVITY REFLECTANCE