Page 1 of 2 6" Aperture Triple Tube Cross Blade Louver

1" (25 mm) min.- 2-1/8" (54 mm) max. 1-1/8" (29 mm) max. Ceiling Thickness

Features 1. Reflector: 16 ga. Die-formed aluminum, Anobrite® finish. 2. Socket Cup: Effectively dissipates heat and positions lamp holder. Snaps onto reflector neck to assure consistently correct optical alignment without tools. 3. Mounting Frame: Galvanized steel for dry or plaster ceilings. Accepts other 6” Triple Tube reflectors (see S6132BU Spec Sheet). 4. Retaining Springs: Precision-tooled steel friction springs secure reflector to mounting frame for quick, tool-less installation. 5. Mounting Brackets: 16 ga. steel. Adjust from inside of fixture. Use 3/4" or 1 1/2" lathing channel, 1/2" EMT, or optional mounting bars. 6. Ballast/J-Box: Electronic 120V-277V. UL listed for through branch circuit wiring with max of (8) No. 12AWG, 90°c supply conductors. Outboard- mounted to reduce heat transfer and maintain lamp efficacy and life. Service from below without tools. 7. Cross Blade Louver: Die-formed, 16 ga. aluminum, matte white or painted aluminum finish. Accepts lens (consult factory). 50° cutoff to lamp, medium beam. Keyed for orientation.
Options and Accessories Other Louver Finishes Consult Factory Emergency Add suffix EM* Chicago Plenum Use 6132BULC Existing/Thk. Ceiling FA EC6* Emergency Ltg. Kit FA EM3E* Fuse (Slow Blow) Add Suffix F *See Spec. Sheets: FAEC, FAEM
Mounting Bars & Accessories; see Specification Sheet MBA. Sloped Ceiling Adapters; see Specification Sheet SCA.
IC Frame available; see C6CFL32 specification sheet.
Labels UL listed for damp locations.

Electrical Note: For ballast electrical data and latest lamp/ballast compatibility refer to “Ballast” specification sheet for complete electrical data.
UL Listed for through branch circuit wiring with max of (8) No 12 AWG, 90 degree C supply conductors.
10" (254mm) · 4 5/8" (117mm) · 12 3/4" (324mm)

Page 2 of 2 6" Aperture Triple Tube Cross Blade Louver
ROOM SURFACE REFLECTANCES: 80% Ceiling; 50% Wall; 20% Floor 2400 Lumens Per Lamp RCR= 1 (Rm. Width= 10xMtg. Ht. above work plane) RCR= 5 (Rm. Width= 2xMtg. Ht. above work plane) RCR=10 (Rm. Width= Mtg. Ht. above work plane)
10 20 30 40 50 60 70 AREA PER FIXTURE IN SQUARE FEET 2 3 4 5 6 7 8
CENTER TO CENTER DISTANCE OF FIXTURES IN FEET This quick calculator chart determines the number and spacing of 1 It.- 32W PL-T units with white cross blade, for any level of illumination. Conversion Factors: 32W PLT with Aluminum Cross Blade, f.c. x 0.7; 26W PLT with white cross blade, f.c. x 0.8; 26W with Aluminum Cross Blade, f.c. x 0.6.
CERTIFIED TEST REPORT NO. 0194FR COMPUTED BY LSI PROGRAM **TEST-LITE** CALCULITE 5 3/4" DIA. APERTURE RECESSED FLUORESCENT CROSS BLADE DOWNLIGHT WITH WHITE CROSS BLADE 1-32W PL-T COMPACT FLUORESCENT LAMP. LUMEN RATING = 2400 LMS. TESTED ACCORDING TO IES PROCEDURES. TEST DISTANCE EXCEEDS FIVE TIMES THE GREATEST LUMINOUS OPENING OF LUMINAIRE.
CANDLEPOWER ANGLE ALONG 22.5 45 67.5 ACROSS LUMENS 0 593 5 575 575 580 584 585 55 10 536 538 541 549 558 15 487 485 491 522 542 142 20 436 427 439 478 506 25 377 366 388 425 460 184 30 309 301 325 366 402 35 228 233 254 279 308 163 40 166 178 185 192 214 45 128 133 126 129 146 105 50 93 93 92 97 104 55 73 73 74 79 84 69 60 58 58 59 64 68 65 45 45 47 51 53 48 70 34 35 36 39 40 75 24 24 26 28 29 28 80 15 16 17 18 20 85 7 7 8 10 11 10 90 3 2 3 4 4 ZONAL LUMENS AND PERCENTAGES ZONE LUMENS % LAMP %LUMINAIRE 0-30 380 15.86 47.31 0-40 544 22.67 67.61 0-60 718 29.93 89.28 0-90 804 33.53 100.00 40-90 260 10.86 32.39 60-90 86 3.59 10.72 90-180 0 .00 .00 0-180 804 33.53 100.00
** EFFICIENCY = 33.5% ** ** EFFICIENCY = 33.5% ** ** EFFICIENCY = 33.5% ** ** EFFICIENCY = 33.5% ** ** EFFICIENCY = 33.5% **
20% FLOOR CAVITY REFLECTANCE Conversion Factors: 32W PLT with Aluminum Cross Blade, C.U. x 0.7; 26W PLT with White Cross Blade, C.U. x 1.1; Aluminum Cross Blade, C.U. x 0.8.