Page 1 of 2 6" Width, 48" Nominal Length 1 or 2 Lamp T5 or T8





4" (102mm) 6" (152mm) 24" (610mm)
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:

Page 2 of 2 6" Width, 48" Nominal Length 1 or 2 Lamp T5 or T8
LER = FP - 58.6 IW - 53.1 BF - 0.88 Comparative yearly lighting energy cost per

1000 lumens = $4.10

0.0 45.0 90.0 FLUX 0 465 465 465 5 479 455 455 44 15 531 425 420 126 25 581 375 368 190 35 615 311 301 237 45 630 241 228 261 55 623 168 153 254 65 589 108 95 235 75 548 55 48 203 85 504 14 10 172 90 496 12 0 95 514 32 13 184 105 558 77 55 223 115 598 132 107 257 125 623 195 170 278 135 630 261 237 278 145 615 326 304 252 155 581 384 365 201 165 531 425 412 128 175 470 446 442 43 180 448 448 448
15 35 52 35 15
Two Color Co-extruded Lens Ballast: B232IUNVHP-B Report is based on 2950 Lumens per lamp. Efficiency: 60.4% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg 180-Deg. Spacing Criteria: 1.9 1.1 1.1 Shielding Angles: 55 65 Luminous Length: 48.000 2.400 Height of Side 6.000 6.000
15 25 31 35 15
5'
12 14 16 14 12
7'
9 10 10 10 9
9'
8 8 8 8 7
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
7 7 7 7 7
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
01 58 54 52 42 40 38 34 33 32 02 52 47 43 36 33 31 29 27 25 03 47 41 36 31 28 25 26 23 21 04 43 36 31 28 24 21 23 20 18 05 39 32 27 25 21 18 20 17 15 06 36 28 23 22 18 16 18 15 13 07 33 26 21 20 16 14 16 14 12 08 31 23 18 18 15 12 15 12 10 09 29 21 16 17 13 11 14 11 99 10 27 19 15 15 12 10 13 10 88 ZONE LUMENS % LAMP % FIXT 00-030 359 6.1 10.1 00-040 596 10.1 16.7 00-060 1112 18.8 31.2 00-090 1723 29.2 48.3 90-120 664 11.3 18.6 90-130 942 16.0 26.4 90-150 1472 25.0 41.3 90-180 1843 31.2 51.7 00-180 3566 60.4 100.0

35 to 40 fc reading plane (60° from horizontal)
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 10652. 1310. 3855. 55 12396. 862. 3044. 65 014783. 540. 2384. 75 019419. 277. 1701. 85 032024. 73. 635.
DL
Fixture Length:
X = Up/Down Light R = Independent
Up or Down Light . (2 lamp only)
Ballast Type:
Options/Accessories Fusing: Internal fast blow fusing: SUFFIX: GLR.
Internal slow blow fusing: SUFFIX: GMF. Radio Interference Filter: 120 or 277 volt, 50 or 60 Hz. One per fixture. SUFFIX: R. One per Ballast, SUFFIX: B. Electronic (Low Voltage) Sequential Switch: Switch factory mounted for Up and Down Light operation from pillow switch. Includes phone jack type receptacle. SUFFIX: SW. Momentary Button Cordset: Traditional "Winged" Pendant design ESD protection to 15,000 volts. Heavy duty 7' cable with phone plug and security clip. Consult factory: Part number 7800W-7 CSP. (Button Cordset can only be used with SW Sequential Switch option) 4-Way Pull Switch: SUFFIX: 4P. Electrical Wiring Options: Consult factory.
Specifications (continued) Electrical: Thermally protected class “P” ballast CBM approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. Labels: I.B.E.W./UL and ULc Listed.
Specifications Materials: Chassis parts are die-formed code rolled steel. End Caps–20 gauge cold rolled steel. Refractor–1/8" thick DR acrylic, unique co-extrusion, white opaque center, linear prisms to spread up/down light. Finish: exterior white baked acrylic enamel. End Caps and Cover–Post painted baked white enamel, 86% reflectance. Phospate undercoating.