Page 1 of 2 Direct/Indirect – 2' x 2' with Acrylic Linear Prismatic Lens




Exposed T-bar by o hers
Exposed T-bar by o hers
1-1/2" max.
Acoustical material by others
1-7/8" max.
Acoustical material by others

* For flush mounting when using 9/16" Exposed T-Grid ceiling system consult factory
exposed slot t-grid ceiling


2" x 2-1/2" Access Plate with (2) 7/8" dia. K.O.
fully enclosed lamp compartment
* If emergency pack or 2nd ballast are used access is gained through the adjacent ceiling tile.
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:

Page 2 of 2 Direct/Indirect – 2' x 2' with Acrylic Linear Prismatic Lens
Model No. H9S2GLR117120SO LER = FP - 48.7 IW - 17.96 BF - 0.88 Comparative yearly lighting ene gy cost per
Model No. H9S2GLR217120SO LER = FP - 56.6 IW - 31.9 BF - 0.88 Comparative yearly lighting ene gy cost per
CANDELA DISTRIBUTION
1000 lumens = $4.92
1000 lumens = $4.24


Report Number: G2007124 Catalog Number: H9S2GLR117120SO Lamps: (1) F17 T8 Luminaire: HP90 2' x 2' with linear
Report Number: G2007120 Catalog Number: H9S2GLR217120SO Lamps: (2) F17 T8 Luminaire: HP90 2' x 2' with linear
0 316 316 316
0 615 615 615
5 314 315 317 30
5 612 615 617 59
prismatic lens. Ballast: REL1P-32-SC (Advance) Report is based on 1375 Lumens per lamp. Efficiency: 72.5% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.4 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 22.800 22.800
15 298 307 314 87
prismatic lens. Ballast: B232I120RH-A (Universal) Report is based on 1375 Lumens per lamp. Efficiency: 74.6% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.5 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 22.800 22.800
15 586 605 618 171
25 271 290 307 134
25 539 580 616 267
35 233 265 292 165
35 470 538 603 337
45 186 231 269 177
45 382 482 563 368
55 133 190 237 168
55 276 405 491 353
65 80 143 199 140
65 164 309 407 294
75 37 89 114 85
75 73 193 230 177
85 8 8 7 12
85 16 17 14 26
90 2 2 1
90 3 2 2
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
ZONAL LUMEN SUMMARY
ZONAL LUMEN SUMMARY
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
ZONE LUMENS % LAMP % FIXT 0- 30 250 18 2 25 1 0- 40 416 30 2 41 7 0- 60 760 55 3 76 3 0- 90 997 72 5 100 0 90-180-180 997 72 5 100 0
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
ZONE LUMENS % LAMP % FIXT 0- 30 496 18 1 24 2 0- 40 833 30 3 40 6 0- 60 1555 56 5 75 8 0- 90 2052 74 6 100 0 90-180-180 2052 74 6 100 0
1 79 75 72 70 68 66 68 66 64 2 71 65 60 61 57 54 59 55 52 3 65 57 51 53 48 44 51 47 44 4 59 50 43 47 42 38 45 41 37 5 54 44 38 42 36 32 41 36 32 6 50 40 33 38 32 28 37 32 28 7 46 36 30 34 29 25 33 28 24 8 43 33 27 31 26 22 30 25 22 9 40 30 24 29 23 20 28 23 20 10 38 28 22 27 21 18 26 21 18
1 81 77 74 72 70 67 69 67 65 2 73 67 61 63 58 55 60 57 54 3 66 58 52 55 49 45 52 48 45 4 60 51 44 48 43 38 46 42 38 5 55 45 38 43 37 33 41 36 32 6 51 41 34 39 33 28 37 32 28 7 47 37 30 35 29 25 34 29 25 8 44 33 27 32 26 22 31 26 22 9 41 31 24 29 24 20 28 23 20 10 38 28 22 27 22 18 26 21 18
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 708. 879. 1023. 55 624. 891. 1112. 65 509. 910. 1267. 75 385. 925. 1185. 85 247. 247. 216.
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 1453. 1834. 2142. 55 1294. 1899. 2303. 65 1044. 1967. 2591. 75 759. 2006. 2390. 85 494. 525. 432.
S
G
R
Body Style:
Ceiling Type:
Reflector:
Lamp Quantity 1=1 Lamp 2=2 Lamp
Fits both Standard Grid
Ballast Type:
HY For NYC Code – I B.E.W. Manufactured
HN For NYC Code – Local 3 Manufactu ed
Options/Accessories Fusing: Internal fast blow fusing: SUFFIX: GLR.
Specifications (continued) Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed. This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org
Internal slow blow fusing: SUFFIX: GMF. Drywall Kit: Order Catalog Number: FK92X2. Electrical Wiring Options: Consult factory. For motion or light sensor. See Folio OA20-10.
Specifications Performance: In an installation of 2 lamp 17W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .89. To reduce glare the average brightness at 65° shall not exceed 2591 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 75.8%. Materials: Chassis parts are die-formed code gauge steel. Lamp Shield: Linear prismatic translucent DR acrylic lens. Finish: Chassis exterior – baked white polyester enamel. Cavity – baked white polyester enamel. Rust preventative undercoating. Reflector – low irides- cence specular aluminum .95% reflectance.