Page 1 of 2 Direct/Indirect Surface Mounted Fluorescent 2' x 4' with Acrylic Linear Prismatic Lens, 1 or 2 Lamp T5


Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
11/08

Page 2 of 2 Direct/Indirect Surface Mounted Fluorescent 2' x 4' with Acrylic Linear Prismatic Lens, 1 or 2 Lamp T5
Model No. HDB2SLW154UNVPG LER = FP - 60.5 IW - 60.8 BF - 1.0 Comparative yearly lighting energy cost per
Model No. HDB2SLW254UNVPG LER = FP - 65.9 IW - 101.8 BF - 1.02 Comparative yearly lighting energy cost per
1000 lumens = $3.97
1000 lumens = $3.64


Report Number: G2008213A Catalog Number: HDB2SLW154UNVPG Lamps: (1) F54 T5 HO Luminaire: HP90 Surface 2' x 4' with linear
Report Number: G2008216A Catalog Number: HDB2SLW254UNVPG Lamps: (2) F54 T5 HO Luminaire: HP90 Surface 2' x 4' with linear
0 1053 1053 1053
0 1891 1891 1891
5 1046 1047 1051 100
5 1879 1881 1888 179
prismatic lens. Ballast: QT1X54/120PHO Report is based on 4400 Lumens per lamp. Efficiency: 83.6% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.4 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 47.880 23.040 Height of Side: 2.280 2.280
15 997 1015 1033 287
prismatic lens. Ballast: B254UNV-D Report is based on 4400 Lumens per lamp. Efficiency: 74.8% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.4 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 47.880 23.040 Height of Side: 2.280 2.280
15 1794 1825 1852 516
25 906 955 996 440
25 1635 1713 1779 789
35 781 868 937 541
35 1410 1556 1679 972
45 626 760 864 581
45 1135 1367 1553 1047
55 452 641 777 562
55 822 1155 1397 1014
65 272 516 677 492
65 502 928 1204 885
75 121 392 568 391
75 230 699 992 695
85 26 282 469 284
85 50 494 782 486
90 5 179 338
90 9 302 547
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
ZONE LUMENS % LAMP % FIXT 00-030 827 18.8 22.5 00-040 1368 31.1 37.2 00-060 2511 57.1 68.3 00-090 3678 83.6 100.0 90-180 0000 0.0 000.0 00-180 3678 83.6 100.0
ZONE LUMENS % LAMP % FIXT 00-030 1484 16.9 22.5 00-040 2456 27.9 37.3 00-060 4517 51.3 68.6 00-090 6583 74.8 100.0 90-180 0000 00.0 000.0 00-180 6583 74.8 100.0
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
01 88 83 79 78 74 71 74 71 69 02 79 71 65 67 61 57 64 59 55 03 72 62 54 58 52 47 56 50 46 04 66 54 46 51 44 39 49 43 39 05 60 48 40 46 39 34 44 38 33 06 55 43 35 41 34 29 40 34 29 07 51 39 31 37 31 26 36 30 25 08 48 36 28 34 28 23 33 27 23 09 45 33 26 31 25 21 30 25 20 10 42 30 23 29 23 19 28 22 18
01 79 75 71 70 67 64 67 64 62 02 71 64 58 60 55 51 57 53 50 03 64 56 49 52 46 42 50 45 41 04 59 49 42 46 40 35 44 39 35 05 54 43 36 41 35 30 39 34 30 06 50 39 32 37 31 26 36 30 26 07 46 35 28 33 27 23 32 27 23 08 43 32 25 31 25 21 30 24 20 09 40 29 23 28 22 18 27 22 18 10 37 27 21 26 20 17 25 20 17
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 1187. 1407. 1562. 55 1036. 1421. 1667. 65 820. 1482. 1856. 75 558. 1670. 2251. 85 271. 2473. 3547.
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 2152. 2530. 2807. 55 1885. 2560. 2997. 65 1514. 2665. 3301. 75 1060. 2979. 3931. 85 522. 4332. 5914.
HD
B
S
W
UNV
Body Style:
Ceiling Type:
Reflector:
Lamp Quantity 1=1 Lamp 2=2 Lamp
Ballast Type:
Options/Accessories Fusing: Internal fast blow fusing: SUFFIX: A.
Internal slow blow fusing: SUFFIX: C. Electrical Wiring Options: Consult factory. For motion or light sensor: See Folio OA20-10.
Specifications (continued) Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed. This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org
Specifications Performance: In an installation of 2 lamp 54W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .75. To reduce glare the average brightness at 65° shall not exceed 3301 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 77.5%. Materials: Chassis parts are die-formed code gauge steel. Lamp Shield: Linear prismatic translucent DR acrylic lens. Finish: Chassis exterior – Soft white post painted polyester powder.. Cavity – Soft white post painted polyester powder. Rust preventative undercoating. Reflector – Soft white post painted polyester powder.