Page 1 of 2 6 Volt or 12 Volt, 28 to 180 Watts NEMA-Rated
The IE Series is ideal for locations where oil-water-and dust resistant equipment is required. The housing meets NEMA 3, 4x and 12 classifications.


21.4” (54.4 cm)
19.4” (49.4 cm)
21.4” (54.4 cm)
13.2” (33.6 cm)
19.4” (49.2 cm)
15.2” (38.6 cm)
11.2” (28.5 cm)
6.8” (17.3 cm)
7.3” (18.7 cm)
13.2” (33.6 cm)
Complete Fixture consists of unit and two lamp heads. Select options and accessories below.
IE
1 = 6V 2 = 12V IE = NEMA-Rated Emergency Lighting Unit
6V, Lead Calcium 28L = 28W Unit1 50L = 50W Unit 75L = 75W Unit 10L = 100W Unit 1,2
12V, Nickel Cadmium 25N = 25W Unit 50N = 50W Unit 10N = 100W Unit 12N = 125W Unit 2
6V, Tungsten IT8 = 8W IT18 = 18W IT25 = 25W IT30 = 30W 6V, Halogen IH6 = 6W IH8 = 8W IH12 = 12W
12V, Tungsten IT12 = 12W IT18 = 18W IT25 = 25W IT30 = 30W 12V, Halogen IH8 = 8W IH12 = 12W IH50 = 50W
12L = 125W Unit 1,2
15L = 150W Unit 1,2
18L = 180W Unit 1,2
15N = 150W Unit
12V, Pure Lead 12P = 120W Unit 2
Features 1. Illumination: Illumination is accomplished with lamp heads mounted on the top of the unit. The NEMA-rated lamp head is available in a variety of wattages, and is constructed of gray polycarbonate to match the IE Series housing. 2. Housing: Constructed of impact resistant, fiberglass reinforced polyester. Housing color is gray and includes stainless steel hardware. View-through window allows easy monitoring of AC indicator and optional voltmeter and ammeter. 3. Electronics: 120/277 VAC dual voltage input with surge-protected, solid- state circuitry. Select units include a temperature-compensated charger. Charging system is complete with low voltage disconnect, AC lockout, brownout protection, AC indicator lamp and test switch. 4. Battery: Maintenance free, sealed lead calcium battery has an estimated service life of 5 years, and an operating temperature range of 65°F (19°C) to 85°F (30°C). Maintenance free, sealed nickel cadmium battery has an esti- mated service life of 10 years, and an operating temperature range of 20°F (-7°C) to 95°F (35°C). 5. Input Power Requirements: 120 VAC - 0.42 amps, 50.4 watts; 277 VAC - 0.20 amps, 50.4 watts
Options (continued) LCK1 = Line Cord (6’, 120 VAC field installed) F1 = 120 VAC Fuse F2 = 277 VAC Fuse P1 = 120 VAC Power Switch P2 = 277 VAC Power Switch DC = DC Power Switch ST = Special Input Transformer (specify voltage and frequency) HTR1 = 120 VAC Heater (Not UL listed) HTR2 = 277 VAC Heater (Not UL listed) S = Shatter Resistant Lamp Head Shield
Multiple option configurations may void UL listing. Consult factory for specifics.
Accessories WG5 = Wire Guard (25-75w units) WG = Wire Guard (100w units) NSF = NSF/ANSI Standard 2 Food Equipment
Code Compliance UL 924 listed. NSF/ANSI Standard 2 Food Equipment optional
Cat. No.:
Lamp(s):
Options SD = Self-Diagnostics SA = Self-Diagnostics with Alarm SDTD = Self-Diagnostics with Time Delay V = Voltmeter 3
T1 = 120 VAC Time Delay (15 minute) T2 = 277 VAC Time Delay (15 minute)

Page 2 of 2 6 Volt or 12 Volt, 28 to 180 Watts NEMA-Rated
IT18 - 6 Volt, 18 Watt, Tungsten IT25 - 6 Volt, 25 Watt, Tungsten IT8 - 6 Volt, 8 Watt, Tungsten



.1 .2 .3 .5 1
.1 .2 .3 .5 1
.1 .2 .3 .5 1
0 10 20 30 40 50 60 70
0 20 40 80 60 100


0 10 20 30 40 50 60 70 80
.1 .2 .3 .5 1

.1 .2 .3 .5 1
20 40 80 60 100 120
0 10 20 30 40 50 60 70
.1 .2 .3 .5 1
0 10 20 30 40 50 60 70 80
IH8 - 6 Volt, 8 Watt, Halogen IT30 - 6 Volt, 30 Watt, Tungsten


.1 .2 .3 .5 1
.1 .2 .3 .5 1
0 100 200 300 400 500 600 700

0 10 20 30 40 50 60 70 80

.1 .2 .3 .5 1
.1 .2 .3 .5 1
100 0 100 200 300 400 500 600 700
0 10 20 30 40 50 60 70
Unit Battery Capacity

.1 .2 .3 .5 1
0 10 20 30 40 50 60 70 80

* Per NEC Specifications
Warranty Electronics: 3 years Battery: 1 year full, 4 years pro-rata (lead calcium); 5 year full, 5 years pro-rata (nickel cadmium)
.1 .2 .3 .5 1
0 10 20 30 40 50 60 70 80