Lightolier LCS8G12PR232
目次 6セクション Lytecel Recessed Fluorescent LCS8G12PR232 · Job Information Type: · Static, 2 Lamp T8, IES RP1 For VDT · Photometry Model No. LCS8G12PR232120SO · … 表示非表示
Page 1 of the Lightolier LCS8G12PR232 user manual — Job Information Type:
1ページ · クリックして拡大
1ページ

Lytecel Recessed Fluorescent LCS8G12PR232

Page 1 of 2 For Continuous Row Mounting – 6-1/2" wide, 12 Cell (1 Row) Parabolic Louver,

  • Static, 2 Lamp T8, IES RP1 For VDT Areas Features
  • 48" long louver gives an uninterrupted louver appearance when row mounted.
  • Meets IES RP1 for lighting VDT areas.
  • 61.0% efficient (T8).
  • 1.4 spacing mounting ratio.
  • Specular, low iridescence, pre-anodized aluminum louver.
  • Vertical grain on cross blades eliminates reflected lamp image.
  • Spring loaded latches (self centering).
  • Reversible louver hinging.
  • Louver has protective dust guard.
  • Only 6-1/8" deep body.
  • Black housing exterior for cooler ballast operating temperature.
  • Turned-in edges for safe handling.
  • UL-Listed twin knockout access plate.
  • Construction to meet NYC Code or Chicago Plenum is available.
  • Optional DALI ballast accepts digital dimming commands from computers, scene controllers and automatic control devices.
Lightolier LCS8G12PR232 — Lytecel Recessed Fluorescent LCS8G12PR232 diagram (page 1)
図 1 · Lytecel Recessed Fluorescent LCS8G12PR232

G

exposed T-grid ceiling.

T

exposed slot T-grid ceiling.

Lightolier LCS8G12PR232 — T diagram (page 1)
図 2
Lightolier LCS8G12PR232 — T diagram (page 1)
図 3
Lightolier LCS8G12PR232 — T diagram (page 1)
図 4
Lightolier LCS8G12PR232 — T diagram (page 1)
図 5

2" max.

2" max.

End Plate for beginning and end of row

N

exposed T-grid ceiling.

Lightolier LCS8G12PR232 — N diagram (page 1)
図 6
Lightolier LCS8G12PR232 — N diagram (page 1)
図 7

2" max.

2" x 2-1/2" Access Plate with (2) 7/8" K.O.s 2-5/32" (55mm)

Lightolier LCS8G12PR232 — N diagram (page 1)
図 8

Job Information Type:

Job Name:

Cat. No.:

Hold-down Clip Side Rail continuous row coupler locks fixtures together for a continuous line of light

Lamp(s):

Volts/Ballast:

without cell configuration interruption

  • Lightolier a Genlyte Thomas Company <a href="http://www.lightolier.com" rel="nofollow noopener" target="_blank">www.lightolier.com</a> Technical Information: (978) 657-7600
  • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720
  • (508) 679-8131
  • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. Copyright 2004 Lightolier Section 2/Folio G07-21
Show 16 more labels / short text on this page
Hold-down Clip · Hold-down Clip · 6-1/8" (156mm) · 8-1/2" 15/16" · 8" · 9/16" · 6-1/2" (165mm) · T-Type 8" (203mm) · Hold-down Clip · 8" 9/16" · 5" (127mm) · Fixture Fixture · 48" (1219mm) · Continuous Row Coupler · Screw · 2/04
Page 2 of the Lightolier LCS8G12PR232 user manual — Job Information Type:
2ページ · クリックして拡大
2ページ

Lytecel Recessed Fluorescent LCS8G12PR232

Page 2 of 2 For Continuous Row Mounting – 6-1/2" wide, 12 Cell (1 Row) Parabolic Louver,

Static, 2 Lamp T8, IES RP1 For VDT

Photometry Model No. LCS8G12PR232120SO

LER = FP - 52.1 IW - 58.0 BF - 0.87 Comparative yearly lighting energy cost per 1000 lumens = $4.61

Lightolier LCS8G12PR232 — Static, 2 Lamp T8, IES RP1 For VDT diagram (page 2)
図 9 · Static, 2 Lamp T8, IES RP1 For VDT

coefficients of utilization — zonal cavity method

RF20 20 20 RC80 50 30 RW70 50 30 50 30 10 50 30 10 1 2 ratio 3 4 cavity 5 6 7 room 8 9 1069 67 65 63 62 60 61 60 59 65 61 58 58 56 54 56 54 53 60 56 52 53 50 48 52 49 47 57 51 47 49 46 43 48 45 43 53 47 43 45 42 39 44 41 39 50 43 39 42 38 35 41 37 35 46 40 35 38 35 32 38 34 32 44 37 32 36 32 29 35 32 29 41 34 30 33 29 27 32 29 27 39 32 28 31 27 25 30 27 25

G03007 LCS8G12PR232120SO

20 20 20 30 20 40 20 6093 95 93 83 95 95 93 84 96 95 93 84 95 96 93 8499 98 98 94 99 98 98 95 99 98 98 95 99 98 98 95 30 20 30 30 30 40 30 60 30 8093 95 94 86 95 95 94 86 95 95 94 86 95 96 94 87 97 97 94 87 ise99 98 98 94 99 98 98 95 99 98 98 95 99 98 98 95 99 98 98 95 ise iseise 40 20 40 30 40 40 40 60 40 80 40 100inaries lengthw93 95 94 87 95 95 94 88 95 95 94 88 95 96 94 88 97 97 94 88 97 97 94 88inaries crossw99 98 98 94 99 98 98 95 99 98 98 95 99 98 98 95 99 98 98 95 99 98 98 95 60 30 60 40 60 60 60 80 60 10095 95 94 88 lum 94 95 94 88 97 97 94 88 97 97 95 88 97 97 95 88lum99 98 98 95 lum 99 98 98 95 99 98 98 95 99 98 98 95 99 98 98 95lum 100 40 100 60 100 80 100 10094 95 94 88 97 97 95 88 97 97 95 88 97 97 95 8899 98 98 95 99 98 98 95 99 98 98 95 98 98 98 95

THIS REPORT IS BASED ON PUBLISHED INDUSTRY PROCEDURES • FIELD PERFORMANCE MAY VARY FROM LABORATORY PERFORMANCE.

Ordering Information Explanation of Catalog Number. Example: LCS8G12PR232120SOGLR

S

R

Body Style:

Ceiling TypeG = 15/16" Grid N = 9/16" Grid T = Slot Grid
Louver FinishP =Low
Voltage120 or 277
OptionsAdd appropriate suffix to catalog

N = NYC Code

Iridescence Specular L=Low

LCLytecel 8" Continuous
no, ie(GLR)
Cells1 row of 12 cells

Length:

32=T8 (Nominal 48")

Ballast Type:

ReflectorR = Semi-Specular

DA=DALI digital addressable dimming.

Options/Accessories Access Plate: Top Wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order Catalog Number: ACP5 CSP. Electrical/Wiring Options: Consult factory. Fusing: Internal fast-blow fusing. Suffix: GLR.

Specifications (continued) Finish: Louver–specular low iridescence pre-anodized reflector sheet. Reflector: Semi-Specular reflector sheet, 95% reflective. Chassis exterior– black baked polyester enamel. Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. Labels: I.B.E.W./UL and ULc Listed.

Internal slow-blow fusing. Suffix: GMF. Chicago Plenum: Suffix: CP.

Specifications Performance: In an installation of 2 lamp 32W luminaires in a room cavity ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .67 with a spacing to mounting ratio of 1.4 perpendicular to the lamps. To meet IES RP-1 for VDT areas the VCP (visual comfort probability) shall not be less than 97 either crosswise or lengthwise and the candela value between 55° and 90° in the 0° to 90° planes shall not exceed 839. Candelas at Nadir (0°) not to exceed 1870. Materials: Chassis parts are die-formed cold rolled steel. Housing is with all edges turned-in for safe handling. Louver: Pre-anodized aluminum (Coilzak® or equal).

Job Information Type:

  • Lightolier a Genlyte Thomas Company <a href="http://www.lightolier.com" rel="nofollow noopener" target="_blank">www.lightolier.com</a> Technical Information: (978) 657-7600
  • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720
  • (508) 679-8131
  • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. Copyright 2004 Lightolier Section2/Folio G07-21
Show 9 more labels / short text on this page
Blank = Standard · Lamp Quantity · S=Static · Fixture · Number of · Lamp/Fixture · Width · Iridescence Semi-specular · 95% Reflective
情報源

参考資料・リンク

この取扱説明書で参照されているリンク(メーカー、サポート、ダウンロード等)。

Lightolier LCS8G12PR232について質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Lightolier LCS8G12PR232に関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

Lightolier LCS8G12PR232 取扱説明書(PDF)

2 ページ·459 KB·インテリア家具・調度品·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…