Page 1 of 2
60' x 60' x 9' Office

3' 9' 15' 21' 27' 33' 39' 45' 51' 57'
Fixture: MBS2GPW154120PG (2'x4') Quantity: 8 Rows of 6 Fixtures Efficiency: 78% Room Size: 60'x60'x9' Reflectance: 80 Ceiling
44 46 43 44 46 46 44 43 46 44
43 44 43 43 45 45 43 43 44 42
50 Wall 20 Floor Light Loss Factor: 0.93* Lumens T5 Lamp: 4400** Ballast Factor: 1.02 Average Maint. fc: 47 Watts/Square Foot: .83
53 54 50 51 54 54 51 50 53 52
44 45 44 45 46 46 45 44 45 44
49 51 49 49 51 51 49 48 50 49
49 51 49 49 51 51 49 48 50 49
Average Maintained fc:
30" High Work Surface
44 45 45 45 46 46 45 44 45 44
*Light Loss Factor Ballast Maintenance Light Loss Typical T8 Fixture 0.89 x 0.92 = 0.82 1 Lite T5 Fixture 1.02 x 0.92 + 0.93
53 54 50 51 54 54 51 50 53 52
43 44 43 43 45 45 43 43 44 43
** Lumens At 25˚c
45 46 44 44 47 47 44 44 46 44
60' x 60' x 9' Office
3' 9' 15' 21' 27' 33' 39' 45' 51' 57'
Fixture: MBS2GPW154120PG (2'x4') Quantity: 8 Rows of 7 Fixtures Efficiency: 78% Room Size: 60'x60'x9' Reflectance: 80 Ceiling

42 43 42 42 44 44 42 42 43 41
54 55 53 54 56 56 54 53 55 54
50 Wall 20 Floor Light Loss Factor: 0.93* Lumens T5 Lamp: 4400** Ballast Factor: 1.02 Average Maint. fc: 55.1 Watts/Square Foot: .96
60 61 59 58 62 62 58 58 61 59
61 62 59 59 63 63 59 59 62 60
57 59 57 57 60 60 57 57 59 57
57 59 57 57 60 60 57 57 59 57
Average Maintained fc:
30" High Work Surface
61 62 59 59 63 63 59 59 62 60
*Light Loss Factor Ballast Maintenance Light Loss Typical T8 Fixture 0.89 x 0.92 = 0.82 1 Lite T5 Fixture 1.02 x 0.92 + 0.93
60 61 58 58 62 62 58 58 61 60
54 55 53 54 56 56 54 53 55 54
** Lumens At 25˚c
42 44 42 43 44 44 43 42 43 42

Page 2 of 2
15' x 15' x 9' Office
3' 6' 9' 12’

Fixture: MBS2GPW154120PG (2'x4') Quantity: 2 Rows of 2 Fixtures Efficiency: 78.9% Room Size: 15'x15'x9' Reflectance: 80 Ceiling
50 48 48 50
50 Wall 20 Floor Light Loss Factor: 0.93* Lumens T5 Lamp: 4400** Ballast Factor: 1.02 Average Maint. fc: 49 Watts/Square Foot: 1.1
49
Average Maintained fc:
30" High Work Surface
49
*Light Loss Factor Ballast Maintenance Light Loss Typical T8 Fixture 0.89 x 0.92 = 0.82 1 Lite T5 Fixture 1.02 x 0.92 + 0.93
50 48 48 50
** Lumens At 25˚c
30' x 30' x 9' Office
3' 9' 15' 20' 26'

Fixture: MBS2GPW154120PG (2'x4') Quantity: 4 Rows of 4 Fixtures Efficiency: 78% Room Size: 30'x30'x9' Reflectance: 80 Ceiling
56 56 54 57 56
50 Wall 20 Floor Light Loss Factor: 0.93* Lumens T5 Lamp: 4400** Ballast Factor: 1.02 Average Maint. fc: 56.3 Watts/Square Foot: 1.1
57 57 56 59 57
55 56 55 57 55
Average Maintained fc:
30" High Work Surface
57 57 56 59 57
*Light Loss Factor Ballast Maintenance Light Loss Typical T8 Fixture 0.89 x 0.92 = 0.82 1 Lite T5 Fixture 1.02 x 0.92 + 0.93
56 56 54 58 56
** Lumens At 25˚c