Page 1 of 2 1'x4' SURFACE BOX FLUORESCENT, PREMIUM SPECIFICATION GRADE LENSED 1, 2, OR 3 LAMP T8/T12

DIMENSIONS



12" (305mm)
9/32" mounting hole 3/16" x 5/8" K.O.
(FA) flat full-size aluminum frame.
(RA) regressed full-size aluminum frame.

1-3/16" (30mm)
20" (508mm)


12" (305mm) 7/8" dia. K.O. within 1-7/8" dia. K.O.
(FS) flat full-size steel frame. (RF) 1/2" regressed floating aluminum frame.

Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
Stem mounting (four per fixture is required)

Page 2 of 2 1'x4' SURFACE BOX FLUORESCENT, PREMIUM SPECIFICATION GRADE LENSED 1, 2, OR 3 LAMP T8/T12
coefficients of utilization — zonal cavity method

RF 20 20 20 RC 80 50 30 RW 70 50 30 50 30 10 50 30 10 1 65 63 61 59 57 56 57 55 54 2 60 56 53 53 51 49 51 49 48 3 56 51 47 48 45 43 47 44 42 4 52 46 42 44 40 38 43 40 37 5 48 41 37 40 36 33 39 35 33 6 45 38 33 36 32 29 35 32 29 7 41 34 30 33 29 26 32 28 26 8 38 31 26 30 26 23 29 25 23 9 35 28 23 27 23 20 26 23 20 10 33 25 21 25 21 18 24 20 18 visual comfort probability
F32/T8 2850
ALUMINUM FRM & VIRGIN ACRYLIC LENS
room size ceiling height ceiling height W L 8.5 10.0 13.0 16.0 8.5 10.0 13.0 16.0 20 20 68 71 77 80 68 72 77 81 20 30 61 64 68 72 62 65 69 73 20 40 58 60 64 66 58 61 64 67 20 60 55 57 60 62 55 58 60 62 30 20 69 73 77 80 69 73 77 80 30 30 62 65 69 72 62 65 69 72 30 40 58 60 63 65 58 61 63 66 30 60 54 57 58 61 54 57 59 61 30 80 53 55 55 58 53 55 56 58 40 20 71 74 78 81 71 74 79 81 40 30 63 66 70 73 63 66 70 73 40 40 58 61 64 66 59 61 64 66 40 60 54 57 58 60 55 57 59 61 40 80 53 55 55 57 53 55 56 58 40 100 52 53 54 55 52 54 54 56 60 30 64 67 70 73 64 67 71 73 60 40 59 62 64 67 59 62 64 67 60 60 55 57 58 61 55 57 58 61 60 80 52 54 55 57 52 54 55 57 60 100 51 53 53 55 51 53 53 55 100 40 62 64 66 69 62 64 66 69 100 60 57 59 60 62 57 59 60 63 100 80 54 55 56 58 54 56 56 58 100 100 52 53 53 55 53 54 54 55
PN
B
S
FIXTURE
VOLTAGE:
120 or 277 OPTIONS:
aluminum frame FS=Flush
suffix to catalog no.,
CEILING
LENS/ SHIELDING
1=1 Lamp 2=2 Lamp 3=3 Lamp LAMP/ FIXTURE LENGTH:
full-size steel frame RA=Regressed
32=T82 34=T12 (Nominal 48")
BALLAST TYPE: 1 & 2 Lamp Mag. T12 LE
acrylic (standard) See specifications and consult factory
full-size aluminum frame RF*=1/2"
regressed floating aluminum frame
*With 7/16" black reveal four sides.
OPTIONS & ACCESSORIES FUSING: Internal fast-blow fusing. SUFFIX: GLR. Internal slow-blow fusing. SUFFIX: GMF. RADIO INTERFERENCE FILTER 120 or 277 volt, 50 or 60 Hz. One per fixture is standard. SUFFIX: RF. ELECTRICAL/WIRING OPTIONS Consult factory. STEM AND CANOPY SETS: Suspends fixture 6", 12", 18" or 24" from surface. (Four per fixture is recommended.) Catalog Number: ASC6 CSP (6"), ASC12 CSP (12"), ASC18 CSP (18"), ASC24 CSP (24")
SPECIFICATIONS (continued) MATERIALS: Chassis parts are die-formed 20 gauge cold rolled steel, stud- welded for rigidity. Lens Frame—(FA) flush full-size aluminum frame, (FS) flush full-size steel frame, (RA) regressed full-size aluminum frame, (RF) 1/2" regressed floating aluminum frame with 7/16" black reveal, four sides. FINISH: Chassis exterior—white baked acrylic enamel. Cavity—white baked acrylic enamel minimum reflectance 86%. Phosphate undercoating. Lens—extruded virgin acrylic, 3/16" square based female cones, running 45° to the panel edge, .095" nominal thickness (similar to pattern 12). ELECTRICAL: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. LABELS: I.B.E.W./UL and C-UL.
SPECIFICATIONS PERFORMANCE: In an installation of 2 lamp 32W luminaires in a room cavity ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .63. To prevent glare the VCP shall not be less than 55 either length- wise or crosswise (at 100 fc level) and the average brightness at 65° shall not exceed 647 footlamberts. To control veiling reflections, luminaire output in the 30° - 90° zone shall be not less than 63.5%.