Page 1 of 2 2' x 4' Recessed Fluorescent, Tri-Lens Frame Static or Air Supply/Return, 2 or 3 Lamp T 8




2" max.
2" max.
5" (127mm)
G T
Exposed T-grid ceiling.
Exposed Slot T-grid ceiling



(SKA Only)
Drywall Kit (See Options)
2" X 2-1/2" Access Plate with (2) 7/8" (73mm) Dia. KO’s
Drywall Kit, Catalog Number: FK92X4.
earthquake clip installed (lay-in grid)
47-31/32" (1218mm)
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:

Page 2 of 2 2' x 4' Recessed Fluorescent, Tri-Lens Frame Static or Air Supply/Return, 2 or 3 Lamp T8
Model No. SKS2GPK232UNVC5 LER = FP - 69.3 IW - 51.9 BF - 0.77 Comparative yearly lighting energy cost per
Model No. SKS2GPK332UNVH3 LER = FP - 70.9 IW - 87.0 BF - 0.88 Comparative yearly lighting energy cost per
1000 lumens = $3.46
1000 lumens = $3.38


0 1990 1990 1990
0 3104 3104 3104
5 1972 1975 1978 188
5 3082 3082 3092 293
prismatic acrylic lens assembly. Ballast: INC-2P32-LW-SC Report is based on 3100 Lumens per lamp. Efficiency: 75.3% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.3 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 45.600 21.600
15 1875 1891 1913 535
prismatic acrylic lens assembly. Ballast: ICN-3P32-SC Report is based on 3100 Lumens per lamp. Efficiency: 75.4% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.3 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 45.600 21.600
15 2940 2945 2951 831
25 1702 1765 1831 815
25 2672 2662 2625 1222
35 1464 1589 1647 979
35 2284 2184 2158 1382
45 1156 114 1063 867
45 1710 1657 1665 1284
55 732 714 643 630
55 1052 1099 990 955
65 406 401 354 400
65 608 639 565 626
75 205 185 170 207
75 323 296 284 333
85 48 35 31 46
85 90 74 66 88
90
90 15 16 8
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
COEFFICIENTS OF UTILIZATION –
ZONAL LUMEN SUMMARY
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.200
ZONE LUMENS % LAMP % FIXT 00-030 1537 24.8 32.9 00-040 2516 40.6 53.9 00-060 4013 64.7 86.0 00-090 4666 75.3 100.0 90-180 0000 0.0 000.0 00-180 4666 75.3 100.0
ZONE LUMENS % LAMP % FIXT 00-030 2346 25.2 33.5 00-040 3728 40.1 53.2 00-060 5967 64.2 85.1 00-090 7014 75.4 100.0 90-180 0000 0.0 000.0 00-180 7014 75.4 100.0
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
01 83 80 77 75 73 71 72 70 69 02 76 70 66 66 63 60 64 61 58 03 70 63 57 59 55 51 57 54 50 04 64 56 50 53 48 44 52 47 44 05 60 51 44 48 43 39 47 42 39 06 55 46 39 44 38 34 43 38 34 07 51 42 35 40 35 31 39 34 31 08 48 38 32 37 31 28 36 31 28 09 45 35 29 34 29 25 33 28 25 10 42 33 27 31 26 23 31 26 23
01 83 80 77 75 73 71 72 70 68 02 76 70 66 66 63 60 64 61 58 03 70 63 57 59 55 51 57 53 50 04 64 56 50 53 48 44 51 47 44 05 60 50 44 48 43 39 47 42 38 06 55 46 39 44 38 34 42 38 34 07 51 42 35 40 35 31 39 34 30 08 48 38 32 37 31 28 36 31 28 09 45 35 29 34 29 25 33 28 25 10 42 33 27 31 26 23 31 26 23
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 2572. 2478. 2365. 55 2008. 1958. 1764. 65 1511. 1493. 1318. 75 1246. 1124. 1033. 85 866. 632. 560.
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 3804. 3686. 3704. 55 2885. 3014. 2715. 65 2263. 2379. 2103. 75 1963. 1895. 1726. 85 1624. 1336. 1191.
P
32 K
Body Style:
Ceiling Type:
Lamp Quantity 2=2 Lamp 3=3 Lamps
Grid T = Slot Grid
.156 Virgin Acyrlic Lens
Ballast Type:
Ballast
NK For NYC Code – Local 3 Manufactured
1 or 2 Lamp Elec. T8 – C5* 0.77 1 - 3 Lamp Elec. T8 – C6* 0.77 LOL Dimming T8 PS* – *Instant Start Standard Other dimming options. Consult factory. NOTE: For T8 UNV, you must use HI OR H3 Ballast Code.
Options/Accessories Fusing: Internal fast blow fusing: SUFFIX: A.
Internal slow blow fusing: SUFFIX: C. Drywall Kit: Order Catalog Number: FK92X4. Electrical Wiring Options: Consult factory. For motion or light sensor: See Folio OA20-10 and OA20-30. Specifications Performance: In an installation of 2 lamp 32W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .80. To reduce glare the average brightness at 65° shall not exceed 1511 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 67.1%. Air Handling: (SKA only) side air passages for air supply or air return. Supply air is discharged vertically. Optional side closure strips. Air return is also provid- ed through the lamp compartment through fixture body ends. Materials: Chassis parts are die-formed code gauge cold rolled steel. Housing has side rails hemmed over and housing ends turned-in for safe handling. Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked polyester enamel minimum 86% reflectance. Rust preventative undercoating. Reflectors- 95% reflective white powder coated.
Specifications (continuned) Lens: Proprietary high quailty frost white acrylic and clear conical prism lens assembly. Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed. This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org