Page 1 of 2 2'x4' RECESSED FLUORESCENT, LENS FRAME TROFFER, STATIC, 4 LAMP, T8 OR T12

G exposed T-grid ceiling. (with flat aluminum frame)
F plaster ceiling/flanged.



1/4" max.
24-1/8" 1-1/8" min. 3-3/4" max.
1-1/2" max.
2" x 2-1/2" access plate with two K.O.s (7/8" dia.)

15/16" or 1" 24"
drywall kit (see options) exposed T-grid ceiling (with flat steel frame)


Drywall Kit (See Options)
1/4" max.
1-1/2" max.
24" Ceiling Opening 24-5/16" x 48-5/16"
15/16" 15/16" or 1"


Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:

Page 2 of 2 2'x4' RECESSED FLUORESCENT, LENS FRAME TROFFER, STATIC, 4 LAMP, T8 OR T12
Luminaire Efficacy Rating LER-73.2 Watts-108.7 BF-0.86
coefficients of utilization — zonal cavity method (effective floor cavity reflectance 0.20)

RF 20 20 20 RC 80 50 30 RW 70 50 30 50 30 10 50 30 10 1 89 85 82 80 78 76 77 75 73 2 82 75 70 71 67 64 68 65 62 3 75 67 61 63 58 54 61 57 53 4 69 60 53 57 51 47 55 50 46 5 64 54 47 51 45 41 50 44 41 6 59 49 42 46 41 36 45 40 36 7 55 44 37 42 36 32 41 36 32 8 51 40 34 39 33 29 38 33 29 9 48 37 31 36 30 26 35 30 26 10 45 34 28 33 28 24 32 27 24 visual comfort probability (rated lumens per lamp 3150.)
room size ceiling height ceiling height W L 8.5 10.0 13.0 16.0 8.5 10.0 13.0 16.0 20 20 57 62 69 77 57 60 67 75 20 30 49 54 59 66 52 54 58 64 20 40 45 49 54 59 49 51 54 57 20 60 41 45 49 54 46 49 51 54 30 20 59 63 68 75 59 62 66 73 30 30 50 54 58 64 53 55 57 62 30 40 45 49 52 56 49 51 53 55 30 60 41 44 47 51 46 48 49 52 30 60 39 42 43 47 44 46 47 50 40 20 61 65 69 74 61 64 68 73 40 30 52 56 59 64 54 57 59 62 40 40 47 50 53 56 50 52 54 56 40 60 42 45 47 50 46 49 49 51 40 80 39 42 43 46 44 47 47 49 40 100 38 40 41 44 43 45 46 47 60 30 54 58 60 64 55 58 59 63 60 40 48 51 53 57 51 53 54 56 60 60 43 45 47 50 47 49 49 51 60 80 40 42 43 46 44 46 47 49 60 100 38 40 40 43 43 45 45 47 100 40 51 54 56 59 53 55 56 59 100 60 46 48 49 53 49 51 51 53 100 80 42 44 44 48 46 48 48 50 100 100 40 42 42 44 44 46 46 47
SP
S
VA
FIXTURE
aluminum frame FA=Flat aluminum
BALLAST TYPE: 2-2 Lamp Mag. T12 LE
LAMP/ FIXTURE LENGTH:
VA (virgin acrylic) standard (see options and
32=T8 34=T12 (Nominal 48")
Other dimming options. Consult factory.
OPTIONS & ACCESSORIES SPECIAL LENSES: Substitute VB for VA (standard) = .125" nominal pattern 12 with 7.8 oz. average weight per square foot. Substitute VI for VA (standard) = .125" nominal pattern 12 with 6.8 oz. average weight per square foot. PLASTER FRAME: Catalog Number PF24. CONTINUOUS ROW INSTALLATION: For F type fixtures, half width flanges are required between fixtures. Order Catalog Number: S2FCTRIM (each joint). RADIO INTERFERENCE FILTER: 120 or 277 volt, 50 or 60 Hz. One per fixture is standard. SUFFIX: RF. FUSING: Internal fast-blow fusing. SUFFIX: GLR. Internal slow-blow fusing. SUFFIX: GMF. ELECTRICAL/WIRING OPTIONS: Consult factory. DRYWALL KIT: Order Catalog Number: FK92X4.
SPECIFICATIONS (continued) MATERIALS: Chassis parts are die-formed code gauge cold rolled steel. Housing with side rails hemmed over and housing ends turned-in for safe handling. FINISH: Chassis exterior—black baked polyester enamel. Cavity—white baked polyester enamel minimum 86% reflectance. Phosphate undercoating. LENSES: VA (standard) extruded virgin acrylic, 3/16" square based female cones, running 45° to the panel edge, .095" nominal thickness (similar to pattern 12). VB (optional) .125" nominal pattern 12 with 7.8 oz. average weight per square foot. VI (optional) .125" nominal pattern 12 with 6.8 oz. average weight per square foot. ELECTRICAL: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. LABELS: I.B.E.W./UL and ULc Listed.
Request Folio OA30-10. CHICAGO PLENUM: SUFFIX: CP.
SPECIFICATIONS PERFORMANCE: In an installation of 4 lamp 32W luminaires in a room cavity ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .85. To prevent glare the VCP shall be not less than 43 either lengthwise or crosswise (at 100fc level) and the average brightness at 65° shall not exceed 3108 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 68.6%.