Page 1 of 2 1'x4' SURFACE BOX FLUORESCENT, 3" DEEP PARABOLIC LOUVER IES RP1 FOR NORMAL VDT USE, 1 OR 2 LAMP T8, T12



5-1/2" (140mm)
12" (305mm)
12" (305mm)
9/32" mounting hole
3/16" x 5/8" K.O.

20" (508mm)
8 Cell 12 Cell
2" (51mm)
7/8" K.O. (4)
12" (305mm) 7/8" dia. K.O. within 1-7/8" dia. K.O.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
• · 5-7/8" (149mm)

Page 2 of 2 1'x4' SURFACE BOX FLUORESCENT, 3" DEEP PARABOLIC LOUVER IES RP1 FOR NORMAL VDT USE, 1 OR 2 LAMP T8, T12
LER = FP - 25.9 IW - 63.8 BF - 0.88 Comparative yearly lighting energy cost per 1000 lumens = $9.26

coefficients of utilization — zonal cavity method
RF 20 20 20 RC 80 50 30 RW 70 50 30 50 30 10 50 30 10 1 73 71 69 67 65 64 64 63 62 2 68 64 60 60 57 55 58 56 54 3 63 57 52 54 50 47 52 49 47 4 58 51 46 48 44 41 47 43 41 5 53 46 40 44 39 36 42 39 36 6 49 41 36 40 35 32 38 34 31 7 46 37 32 36 31 28 35 31 28 8 42 34 29 33 28 25 32 28 25 9 40 31 26 30 26 22 29 25 22 10 37 29 24 28 23 20 27 23 20 visual comfort probability
room size ceiling height ceiling height W L 8.5 10.0 13.0 16.0 8.5 10.0 13.0 16.0 20 20 90 87 82 86 88 85 80 78 20 30 91 89 86 84 90 87 82 78 20 40 92 90 88 86 90 88 85 80 20 60 93 91 89 88 90 88 86 83 30 20 91 89 84 84 88 88 82 79 30 30 92 91 87 82 90 90 84 78 30 40 93 92 89 84 90 90 86 80 30 60 94 93 90 86 90 90 87 83 30 80 94 93 90 86 90 90 87 83 40 20 91 89 85 85 88 88 84 80 40 30 93 91 88 83 90 90 86 80 40 40 94 92 80 85 90 90 88 82 40 60 94 93 91 87 90 90 88 84 40 80 94 92 91 87 90 90 88 84 40 100 94 92 91 87 90 90 88 84 60 30 93 91 88 85 90 90 86 81 60 40 93 92 90 87 90 90 88 83 60 60 94 93 91 88 90 90 88 85 60 80 94 93 91 88 91 90 88 85 60 100 94 93 91 88 91 90 88 85 100 40 93 92 90 87 90 90 88 83 100 60 94 93 91 88 91 90 88 85 100 80 94 93 91 89 91 90 88 85 100 100 94 93 91 89 91 90 88 86
VR
B
S
S
VR 3" Deep Pre- anodized Aluminum
NUMBER OF
WHITE REFLECTOR
LAMP/ FIXTURE LENGTH:
WIDTH:
CELLS: 8= 1 row of 8 cells 12= 1 row of 12 cells 16= 2 rows of 8 cells 24= 2 rows of 12 cells
32=T8 34=T12 (Nominal 48")
BALLAST TYPE: 1 or 2 Lamp Mag. T12 LE
CEILING
Semi-specular P= Low-iridescence
1 lamp 2 lamp
OPTIONS & ACCESSORIES FUSING: Internal fast-blow fusing.
SPECIFICATIONS (continued) MATERIALS: Chassis parts are die-formed 20 gauge cold rolled steel with 45° mitered corners welded and turned in edges for safe handling. LOUVER: Pre-anodized aluminum (Coilzak® or equal). FINISH: Louver—semi-specular low iridescence, pre-anodized reflector sheet. Cavity—white baked acrylic minimum reflectance 86%, Phosphate undercoat- ing. Chassis exterior—white baked acrylic enamel. ELECTRICAL: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. LABELS: I.B.E.W./UL and C-UL listed.
SUFFIX: GLR. Internal slow-blow fusing. SUFFIX: GMF. RADIO INTERFERENCE FILTER: 120 or 277 volt, 50 or 60 Hz. One per fixture. SUFFIX: RF. ELECTRICAL/WIRING OPTIONS: Consult factory. STEM AND CANOPY SETS: Suspends fixture 6", 12", 18" or 24" from surface. (Four per fixture is required). Catalog Number: ASC6 CSP (6"), ASC18 CSP (12"), ASC18 CSP (18"), ASC24 CSP (24").
SPECIFICATIONS PERFORMANCE: In an installation of 1 lamp 32W luminaires in a room cavity ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .71 with a spacing to mounting ratio of 1.9 perpendicular to the lamp. To meet IES RP-1 recommended (basic) requirements for VDT areas the VCP (visual comfort probability) shall not be less than 90 either crosswise or length- wise and the maximum average brightness at 65°, 75° and 85° shall not exceed 592, 109 and 81 candelas per square meter respectively in the 0°, 45° and 90° horizontal planes. Candelas at Nadir (0°) not to exceed 671.