FPI FIREPLACE PRODUCTS INTERNA TIONAL L TD. 6988 V enture St., Delta, BC Canada, V4G 1H4 918-524a MODELS: P48-NG2 Natural Gas P48-LP2 Propane P48-2 Gas Fireplace W ARNING: If the information in these instructions are not followed exactly , a fi re or explosion may result causing property damage, personal injury or loss of life.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 2 T o the New Owner: Congratulations! Y ou are the owner of a state-of-the-art Gas Fireplace by REGENCY ® . The P48-2 has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 3 T ABLE OF CONTENTS Optional Bay Door ....................................................... 35 Optional Bay T rim ........................................................ 35 Bay Louvers ...
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 4 This is a copy of the label that accompanies each P48-NG2 and P48-LP2 Zero Clearance Direct V ent Gas Fireplace. We have printed a copy of the contents here for your review . The safety label is located on the front inside base of the unit, visible when the bottom louver is open.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 5 REQUIREMENTS 5.08: Modifica tions to NFPA-54, Chap ter 10 (2) Revise 10.8. 3 by adding the following a dditional requi rements: (a) For all.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 6 12) Installation and any repairs to this appliance should be done by an authorized service person. A professional service person should be called to inspect this appliance annually . Make it a practice to have all of your gas appliances checked annually .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 7 INST ALLA TION UNIT SPECIFICA TIONS This includes: 1) Clocking the appliance to ensure the correct fi ring rate (rate noted on label 51,000 (NG) Btu/h, 48,000 (LP) Btu/h) after burning appliance for 15 minutes.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 8 CLEARANCES The clearances listed below are Minimum distances unless otherwise stated: A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 9 MANTELS Because of the extreme heat this fi replace emits, the mantel clearances are critical.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 10 INST ALLA TION Note: 43" (1092mm) is the minimum height for fl ex termination and Simpson Dura-V ent terminations.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 11 VENTING INTRODUCTION The P48-2 uses the "balanced fl ue" technology Co Axial system.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 12 INST ALLA TION EXTERIOR VENT TERMINA TION REQUIREMENTS A= Clearance above grade, veranda, porch, deck, or balcony *(min. 12"/30cm) B= Clearance to window or door that may be opened *(12"/30cm) C= Clearance to permanently closed window *(min.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 13 VENTING ARRANGEMENTS HORIZONT AL TERMINA TION Regency ® Direct V ent System (Flex) These venting systems, in combination with the P48-2 Direct V ent Gas Fireplace, have been tested and listed as a direct vent he ater system by W arnock Hersey .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 14 SIMPSON DURA-VENT VENTING Horizontal or V ertical T erminations The Simpson Dura-V ent Direct V ent System offers a complete line of component parts for installation of both horizontal and vertical installations.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 15 Description Simpson Direct V ent Pro ® Simpson Direct V ent GS ® Discontinued Selkirk Direct-T emp™ Metal-Fab ® Sure Seal 6” Pipe L.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 16 L676 & L900 Direct V ent Fireplace IMPORT ANT NOTE • A V ent Guard is required when the AstroCap is installed above grade at 7 feet or lower . • The Simpson Dura-V ent and Selkirk Direct T emp horizontal termination caps cannot be used in any applications.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 17 SIMPSON DURA-VENT DIRECT VENT GS SYSTEM and Regency ® DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas) The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 45 o and one 90 o elbow (two 45 o elbows equal one 90 o elbow).
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 18 INST ALLA TION Horizontal V enting with T wo (2) 90 o Elbows Horizontal V enting with T wo (2) 90 o Elbows Horizontal V enting with Three (3) 90 o Elbows One 90 o elbow = T wo 45 o elbows. One 90 o elbow = T wo 45 o elbows.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 19 INST ALLA TION Horizontal V enting with Three (3) 90 o Elbows V ertical V enting with T wo (2) 90 o Elbows V ertical V enting with T wo (2) 90 o Elbows One 90 o elbow = T wo 45 o elbows. One 90 o elbow = T wo 45 o elbows.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 20 INST ALLA TION V ertical V enting with Three (3) 90 o Elbows V ertical V enting with Three (3) 90 o Elbows One 90 o elbow = T wo 45 o elbows. Option H V H + H 1 V + V 1 With these options, max.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 21 INST ALLA TION • V ent must be supported at offsets. • Firestops are required at each fl oor level and whenever passing through a wall. • Maintain clearances to combustibles. Note: Must use optional rigid pipe adapter when using Simpson Dura-V ent pipe (Part # 510-994).
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 22 INST ALLA TION The P48-2 is approved for a maximum 40 ft. straight vertical, with Simpson Dura-V ent Direct V ent GS vent systems for Propane and Natural Gas, as per diagram.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 23 Diagram 7 Diagram 6 9) Install wall thimble in the center of the 1 1" (279mm) square and attach with wood screws (Diagram 7). Diagram 5 6) The arrow on the vent cap should be pointing up.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 24 INST ALLA TION 6) Continue to assemble pipe lengths. Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet (0.9 meter), to avoid excessive stress on the elbows, and possible separation.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 25 INST ALLA TION 4) Separate the 2 halves of the wall thimble and securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 26 INST ALLA TION GAS PIPE PRESSURE TESTING The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve dur ing any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 27 INST ALLA TION 5) Pull off the pilot cap to expose the pilot orifi ce. 6) Unscrew the pilot orifi ce with the allen key and replace with the LP pilot orifi ce in the kit and replace pilot cap.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 28 INST ALLA TION 17) Reverse steps 4) to 1). 18) Attach the label "This unit has been converted to LPG" near or on top of the serial # decal. 19) Replace yellow "Natural Gas" label with red "Propane" label 20) Check for gas leaks.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 29 INST ALLA TION 28) Locate the ground lug at the receptical box, left of the unit. 29) Connect one end of the supplied green ground wire to the lug with the nut and washer from the kit. 30) Install the 1/2" bushing to the heat shield.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 30 BRICK P ANELS INST ALLA TION 1) Unhook the 2 spring loaded hooks from the bottom of the fl ush door and lift the Flush Front off the unit. 2) Unwrap the brick pattern panels from the protective wrapping.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 31 INST ALLA TION LOG SET INST ALLA TION Read the instructions below carefully and refer to the dia- grams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot opera- tion.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 32 INST ALLA TION 7) Place Log 02-83 onto the pin in Log 02-88 and position the notch on the bottom of the log into the 4th grate post. 6) Embers should be placed in front of Log 02-85 and Log 02-86.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 33 INST ALLA TION 10) Place Log 02-90 onto the right side of the grate. Posi- tion the cut-out on the underside of the log onto the grate bar . Cut-out on the underside of the log. Position the cut-out onto the grate bar .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 34 Diagram 1 Diagram 3 ST ANDARD FLUSH DOOR The standard fl ush door comes with a black frame. T o install the frame, simply hook the top door fl ange onto the top of the unit and swing the door towards the unit, diagram 1.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 35 INST ALLA TION BA Y LOUVERS 1) Install top louver by sliding the two bracket clips into the brackets located on top of the bay door . See below . The fi tted louver leaves a small gap between faceplate bottom and louver top.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 36 OPTIONAL FINISHING TRIM NOTE: Remove both the Flush Louvers or Bay Louvers and the Flush Front or Bay Front prior to installing the Finishing T rim. 1) Install the Finishing T rim sides as shown in the diagram, line up the holes in the side trim with the holes in the fi rebox side.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 37 INST ALLA TION Can be used with Option 1 o r 3 but not both. 1) Run the supplied 15' of wire through the back gas inlet opening. Be careful not to damage wire. Note: We recommend a maximum of 15' of wire but if you wish to go with a longer run, use the Thermostat Wire T able.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 38 WIRING DIAGRAMS CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. No electrical power supply is required for the gas control to operate.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 39 INST ALLA TION For PROP ANE Units and Units Equipped with DC Spark Boxes* *For installation of the DC Spark Box refer to the LP Conversion instructions in this manual.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 40 INST ALLA TION INST ALLING THE OPTIONAL F AN 120 V olt AC power is needed for the fan switch and blower . The fan can be hard wired if desired. The receptacle box should be installed on the left hand side of the unit by a qualifi ed electrician.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 41 OPERA TING INSTRUCTIONS OPERA TING INSTRUCTIONS 1) Read and understand these instructions before operating this appliance. 2) Check to see that all wiring is correct and enclosed to prevent possible shock.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 42 Copy of the Lighting Plate Instructions NORMAL OPERA TING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 43 MAINTENANCE INSTRUCTIONS 1) Always turn off the gas valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 44 CAUTION: Wear gloves when removing damaged or broken glass. BA Y GLASS REPLACEMENT 1) Remove the door from the unit and place on a soft surface to prevent scratching. 2) Remove the nuts holding the glass clips in place and remove.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 45 MAINTENANCE 6) Remove the burner by removing the screw on the left side and then slide the burner to the left and lift out. 7) Remove the right and left side defl ectors by removing the 2 screws on each defl ector .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 46 P ARTS LIST MAIN ASSEMBL Y Part # Description Part # Description 1) 948-259 Door Handle 3) 948-046 Chain 4) 948-1 15 Spring 6) 430-129 Rec.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 47 P ARTS LIST HEA T RELEASE DUCT KIT 42 48 49 46 24 105 106 101 20 21 21 24 27 30 28 30 29 5 0 50 23 23 22 97 98 100 99 95 96 93 89 92 90 10.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 48 P ARTS LIST BURNER & LOG ASSEMBL Y Part # Description 370-574/P V alve Assembly - Natural Gas 370-576/P V alve Assembly - Propane 52) * Gasket - V alve Access Plate 56) 910-190 Piezo Ignitor & Nut 57) 910-478 V alve S.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 49 P ARTS LIST FLUSH DOOR & LOUVERS Part # Description Part # Description 370-925 Flush Louvers (Set) - Steel/Black 370-924 Flush Louvers.
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 50 P ARTS LIST BA Y FRONT & LOUVERS 106) 940-337/P Side Glass 107) 936-243 Glass Gasket 108) 940-336/P Center Glass 1 1 1) * Brick Panel .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 51 W ARRANTY Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance T eam carefully inspects each unit thoroughly before it leaves our facility .
Regency ® P48-2 Zero Clearance Direct V ent Gas Fireplace 52 Installer: Please complete the following information Dealer Name & Address: ______________________________________________ ___________.
デバイスRegency P48-2の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Regency P48-2をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRegency P48-2の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Regency P48-2の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Regency P48-2で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Regency P48-2を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRegency P48-2の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Regency P48-2に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRegency P48-2デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。