List of Pagesp.5Summary of Changesp.6Contentsp.7Figuresp.10Tablesp.11Prefacep.13How to Use This Guidep.13How This Guide is Organizedp.13Trademarksp.14Conventionsp.14Related Publicationsp.15Obtaining Informationp.15Customer Resource Centerp.15Documents on CDp.16Electronic Document Centerp.16KnowledgeMapp.16Partners Pagep.16StorageTek Storefrontp.16Comments and Suggestionsp.17Educationp.171: The System Assurance Processp.19System Assurance Team Responsibilitiesp.20The System Assurance Flowchartp.22Proposal Acceptancep.23System Assurance Planning Meetingsp.23Order Placementp.23Sales Entry Form or Order Worksheet Checkp.23System Assurance Review Meetingsp.23Preinstallation Checklist Error Checkp.24Installationp.24Post-installation Follow-upp.24Schedule Planningp.242: Key Personnelp.25Customer Teamp.25CPU Hardware Contactp.25Operating Systems Software Contactp.25Communication Hardware Contactp.25Operations Contactp.25Delivery Contactp.25StorageTek Teamp.26Marketing Representativep.26Solutions Delivery Systems Specialistp.26Solutions Delivery Engineerp.26Solutions Delivery Installation Consultantp.26StorageTek Hardware and Software Supportp.27Client Processor(s) Teamsp.27Hardware Contactsp.27Software Contactsp.27Channel Partner Teamp.28Marketing Representativep.28Solutions Delivery Systems Specialistp.28Solutions Delivery Engineerp.28Solutions Delivery Installation Consultantp.283: Product Overviewp.29Drive Configurationsp.30Power Distribution Unit (PDU)p.30Host Interfacesp.31Data Interfacesp.374890 Data Busesp.37DLT Data Busesp.37I/O Cabling Limitsp.37RS423p.38SCSI Library Robotic Interfacep.384: Ordering the Equipmentp.41The Ordering Processp.41Fax Numbers and Addressesp.41Hardware Order Worksheetsp.42DLT Drivesp.444890 Drivesp.48PDU Power Cablesp.49Serial Cables, 9710 to Hostp.49SCSI Cablingp.51Cable Restrictionp.51Cable Length Subtractionp.539710 to Hostp.55Daisy Chainp.56Daisy Chain Terminatorsp.56PRS Cardp.57Robotics Control, Internalp.58AS/400 Data Pathp.59Sun Sparc Workstationp.60RS/6000, Bull DPX/20p.61SCSI Adaptersp.62Single-Ended Narrow or Fast/Narrow to Widep.62High Density 68-68 Pin Standard Jackscrewp.62AS/400 Serial Cablesp.63Sequent Cablesp.63FIPS Cablingp.64FIPS Cablesp.64FIPS Terminatorsp.66FIPS Drive to I/Op.66Modem Cablesp.67Cartridge Tapes and Labelsp.685: Pre-installation Checklistp.71Fire Suppression Systemp.72Hardware Support Servicesp.72A: Site Planning Informationp.75Indexp.81Reader’s Comment Formp.83
Page 1 of the StorageTek Tape Library (9710) user manual — System Assurance Guide
1ページ · クリックして拡大
1ページ

9710 Library Storage Module

System Assurance Guide

StorageTek Tape Library (9710) — System Assurance Guide diagram (page 1)
図 1 · System Assurance Guide

Document MR0012

Page 2 of the StorageTek Tape Library (9710) user manual
2ページ · クリックして拡大
2ページ
Page 2 of the StorageTek Tape Library (9710) user manual
Page 3 of the StorageTek Tape Library (9710) user manual — System Assurance Guide
3ページ · クリックして拡大
3ページ

9710 Library Storage Module

System Assurance Guide

Page 4 of the StorageTek Tape Library (9710) user manual
4ページ · クリックして拡大
4ページ

Information contained in this publication is subject to change. In the event of changes, the publication will be revised. Comments concerning its contents should be directed to:

Nearline Information Development Storage Technology Corporation One StorageTek Drive Louisville, CO 80028-2201 USA

© 1995 through 1999, Storage Technology Corporation, Louisville, CO, USA. All rights reserved.

ii 9710 System Assurance Guide MR0012J

Page 5 of the StorageTek Tape Library (9710) user manual — List of Pages
5ページ · クリックして拡大
5ページ

List of Pages

Document Title9710 Library Storage Module System Assurance Guide
Guide Part NumberMR0012J
Initial Release DateJuly 1996
Reissue J DateDecember 1999

Total number of pages in this document is 86, consisting of the following:

Pages Disposition Cover Replace entire manual Blank page Title page Copyright page (ii) iii through xiv 1-1 through 1-6 2-1 through 2-4 3-1 through 3-12 4-1 through 4-30 5-1 through 5-4 A-1 through A-6 Index-1 through Index-2 Reader’s Comment Form Business Reply Mailer Blank Page Back Cover

MR0012J 9710 System Assurance Guide iii

Page 6 of the StorageTek Tape Library (9710) user manual — Summary of Changes
6ページ · クリックして拡大
6ページ

Summary of Changes

Date Reissue Level Change

Dec. 1999 J throughout: Incorporated template 103199 and updated boilerplate. Changed personnel references to reflect new Customer Service organization. Indicated support of 9840 Fibre Channel drives. Chapter 3: Removed note about AS/400 not supporting 9840 or DLT drives. Added host interface graphics (Figure 3- 2 through 3-6). Added illustration of I/O panel that shows Fibre Channel plate in lower left corner. Chapter 4: Expanded power cable table with new power cable part numbers. Corrected drawing of Centronics 50-pin connector. Added new in-country media services telephone numbers. Added note clarifying feature codes 1603 and 2016. Appendix A: Updated weight specifications.

iv 9710 System Assurance Guide MR0012J

Page 7 of the StorageTek Tape Library (9710) user manual — 目次
7ページ · 目次
目次

目次

List of Pagesp.5Summary of Changesp.6Contentsp.7Figuresp.10Tablesp.11Prefacep.13How to Use This Guidep.13How This Guide is Organizedp.13Trademarksp.14Conventionsp.14Related Publicationsp.15Obtaining Informationp.15Customer Resource Centerp.15Documents on CDp.16Electronic Document Centerp.16KnowledgeMapp.16Partners Pagep.16StorageTek Storefrontp.16Comments and Suggestionsp.17Educationp.171: The System Assurance Processp.19System Assurance Team Responsibilitiesp.20The System Assurance Flowchartp.22Proposal Acceptancep.23System Assurance Planning Meetingsp.23Order Placementp.23Sales Entry Form or Order Worksheet Checkp.23System Assurance Review Meetingsp.23Preinstallation Checklist Error Checkp.24Installationp.24Post-installation Follow-upp.24Schedule Planningp.242: Key Personnelp.25Customer Teamp.25CPU Hardware Contactp.25Operating Systems Software Contactp.25Communication Hardware Contactp.25Operations Contactp.25Delivery Contactp.25StorageTek Teamp.26Marketing Representativep.26Solutions Delivery Systems Specialistp.26Solutions Delivery Engineerp.26Solutions Delivery Installation Consultantp.26StorageTek Hardware and Software Supportp.27Client Processor(s) Teamsp.27Hardware Contactsp.27Software Contactsp.27Channel Partner Teamp.28Marketing Representativep.28Solutions Delivery Systems Specialistp.28Solutions Delivery Engineerp.28Solutions Delivery Installation Consultantp.283: Product Overviewp.29Drive Configurationsp.30Power Distribution Unit (PDU)p.30Host Interfacesp.31Data Interfacesp.374890 Data Busesp.37DLT Data Busesp.37I/O Cabling Limitsp.37RS423p.38SCSI Library Robotic Interfacep.384: Ordering the Equipmentp.41The Ordering Processp.41Fax Numbers and Addressesp.41Hardware Order Worksheetsp.42DLT Drivesp.444890 Drivesp.48PDU Power Cablesp.49Serial Cables, 9710 to Hostp.49SCSI Cablingp.51Cable Restrictionp.51Cable Length Subtractionp.539710 to Hostp.55Daisy Chainp.56Daisy Chain Terminatorsp.56PRS Cardp.57Robotics Control, Internalp.58AS/400 Data Pathp.59Sun Sparc Workstationp.60RS/6000, Bull DPX/20p.61SCSI Adaptersp.62Single-Ended Narrow or Fast/Narrow to Widep.62High Density 68-68 Pin Standard Jackscrewp.62AS/400 Serial Cablesp.63Sequent Cablesp.63FIPS Cablingp.64FIPS Cablesp.64FIPS Terminatorsp.66FIPS Drive to I/Op.66Modem Cablesp.67Cartridge Tapes and Labelsp.685: Pre-installation Checklistp.71Fire Suppression Systemp.72Hardware Support Servicesp.72A: Site Planning Informationp.75Indexp.81Reader’s Comment Formp.83
Page 10 of the StorageTek Tape Library (9710) user manual — Figures
10ページ · クリックして拡大
10ページ

Figures

Figure 1-1. The System Assurance Overview 1-1 Figure 1-2. The System Assurance Process Flow 1-4 Figure 3-1. 9710 LSM with Expansion Door 3-1 Figure 3-2. Direct Connection for AS/400 Control 3-4 Figure 3-3. Client Configuration (Indirect Connection) with AS/400 3-5 Figure 3-4. SCSI Direct Connection (Open Systems) with Common Bus 3-6 Figure 3-5. Host-Indirect Connection 3-7 Figure 3-6. Subsystem Generic Software Types 3-8 Figure 3-7. 9710 I/O Panel (Showing FIPS) 3-11 Figure 3-8. 9710 I/O Panel (Showing Fibre Channel) 3-12 Figure 4-1. 9710 Model/Feature Selections 4-3 Figure 4-2. DLT8000 Model and Feature Selections 4-5 Figure 4-3. DLT7000 Feature Selections 4-6 Figure 4-4. DLT4000 Feature Selections 4-7 Figure 4-5. 4890 Drive Feature Selections 4-8 Figure 4-6. SCSI Connector Types 4-12 Figure 4-7. FIPS AS/400 Cabling Configurations 4-24 Figure A-1. 9710 Layout and Floor Space Requirements A-3

viii 9710 System Assurance Guide MR0012J

Page 11 of the StorageTek Tape Library (9710) user manual — Tables
11ページ · クリックして拡大
11ページ

Tables

Table 1-1. Team Member Responsibilities 1-2 Table 4-1. PDU Cables 4-9 Table 4-2. Serial Cables, 9710 to Host 4-10 Table 4-3. SCSI Cable Restriction 4-11 Table 4-4. SCSI Cable Length Subtraction 4-13 Table 4-5. SCSI Cables 9710 to Host 4-15 Table 4-6. Specialized Daisy Chain Cables 4-16 Table 4-7. Daisy Chain Terminators 4-16 Table 4-8. PRS Card Cables 4-17 Table 4-9. Robotics Control Cables, Internal 4-18 Table 4-10. SCSI Cables and Adapters for AS/400 Path 4-19 Table 4-11. SCSI Cables and Adapters for Sun Sparc Workstation 4-20 Table 4-12. SCSI Cables and Adapters for RS/6000 and Bull DPX/20 4-21 Table 4-13. Adapters, SCSI 4-22 Table 4-14. Single-Ended Narrow or Fast/Narrow to Wide SCSI 4-22 Table 4-15. High Density 68-68 Pin Jackscrew SCSI 4-22 Table 4-16. AS/400 Serial Cables 4-23 Table 4-17. Sequent Cables 4-23 Table 4-18. FIPS Cables 4-25 Table 4-19. FIPS Terminators 4-26 Table 4-20. FIPS Cables 4-26 Table 4-21. Modem Cables 4-27 Table 4-22. Remote Diagnostic Support for PC Use 4-27 Table 4-23. In-Country Media Supply Services 4-28 Table 5-1. Pre-installation Checklist 5-1 Table 5-2. Remote Support Hardware and Cables 5-2 Table A-1. 9710 Dimensions and Weights A-1 Table A-2. LSM Power Specifications A-1 Table A-3. Optional Power Distribution Unit (PDU) Specifications A-2 Table A-4. LSM Environmental Specifications A-2 Table A-5. Power Characteristics A-4

MR0012J 9710 System Assurance Guide ix

Page 12 of the StorageTek Tape Library (9710) user manual — Tables
12ページ · クリックして拡大
12ページ

This page intentionally left blank.

x 9710 System Assurance Guide MR0012J

Tables

Page 13 of the StorageTek Tape Library (9710) user manual — I How This Guide is Organized
13ページ · クリックして拡大
13ページ

Preface

This guide contains information about planning, ordering, installing, and follow-up activities required during StorageTek TimberWolf 9710 Library Storage Module sales, delivery, and installation.

The audience for this guide includes StorageTek marketing representatives, solutions delivery systems specialists (SDSSs), ssolutions delivery installation consultants (SDICs), solutions delivery engineers (SDEs), independent consultants, service representatives, and customers involved with installation planning.

I How to Use This Guide

This guide provides a series of worksheets and checklists that, when completed properly, ensure that no aspect of the installation process has been overlooked. This promotes error-free installation and customer satisfaction. Use only those checklists that are applicable to your system. However, certain worksheets (noted below) must be completed for the product to be shipped. Refer to Chapter 4 for more information.

Administration, the product will not be shipped.

  • Library Configuration Worksheet
  • Site Survey
  • Product Checklist

I How This Guide is Organized

This guide contains the following information:

Chapter 1 “The System Assurance Process” provides detailed information useful for understanding the System Assurance process.

Chapter 2 “Key Personnel” provides a worksheet for recording names and phone numbers of the key personnel on the system assurance teams.

Chapter 3 “Product Overview” provides an overview of the LSM, drive configurations, and interfaces

Chapter 4 “Ordering the Equipment” contains worksheets to complete when ordering the 9710 Library

MR0012J 9710 System Assurance Guide xi

Page 14 of the StorageTek Tape Library (9710) user manual — I Conventions
14ページ · クリックして拡大
14ページ

Chapter 5 “Pre-installation Checklist” provides checklists to ensure no unresolved issues exist at installation.

Appendix A “Site Planning Information” provides LSM specifications and floor space layout.

Index The Index assists in locating information in this publication.

I Trademarks

StorageTek is a trademark of Storage Technology Corporation. Other features and terms used in this publication are for informational purposes only and might be trademarks of Storage Technology Corporation or other companies.

I Conventions

Typographical conventions highlight special words, phrases, and actions used in this publication.

Button MENU Physical buttons or switches, onscreen buttons, and softkeys appear in Helvetica font and in all capital letters.

not or must Important or emphasized words and phrases appear in italics.

Filenames dictionary.txt Filenames appear in Courier font.

Open Indicators and LEDs appear with initial capital letters and in italics.

Keyboard keys [Y], [Enter] or [Ctrl+Alt+Delete]

Keyboard keys appear within brackets, in Helvetica font, with initial capital letters or as the key appears on the keyboard.

downloading Screen captures or messages appear in Courier font.

Screen captures or messages

Device = xx Names of variables that require values assigned appear in italics.

Pathnames P:\Printshp\Pubs or home/gandalf/litdist

Pathnames appear in Courier font.

Positions for switches, jumpers, and circuit breakers

ON Switch, jumper, and circuit breaker positions appear in default font and all capital letters.

xii 9710 System Assurance Guide MR0012J

Show 5 more labels / short text on this page
Preface · Item Example Description · Emphasized text · Indicators/ LEDs · Parameters or input
Page 15 of the StorageTek Tape Library (9710) user manual — Customer Resource Center
15ページ · クリックして拡大
15ページ

URLs and hypertext links

www.stortek.com/techpubs Universal Resource Locator (URL) and hypertext links appear in blue text and underlined.

I Related Publications

Additional information is contained in the following publications:

9710 Publication Part Number

9710 Library Storage Module Installation Manual 9640

Quantum™ DLT Publications Part Number DLT4000 Cartridge Subsystem Product Manual 313127601 (StorageTek) 81-60043-0x (Quantum)

DLT7000 Tape Drive Product Manual 313134501 (StorageTek) 81-60000-0x

DLT8000 Tape Drive Product Manual 81-60118-0x (Quantum)

9840 Publications Part Number 9840 Tape Drive System Assurance Guide MT 5003 9840 Tape Drive Installation Manual 95879

4890 Publications Part Number 4890 Maintenance Manual 9512952900 4890 Product Manual 9512941000

I Obtaining Information

You may have access to the following additional sources of information.

Customer Resource Center

StorageTek’s Customer Resource Center (CRC) is an online service that provides technical information such as software publications, user documentation, maintenance fixes, and answers to frequently asked questions. The CRC is for

MR0012J 9710 System Assurance Guide xiii

Preface · Item Example Description

Page 16 of the StorageTek Tape Library (9710) user manual — StorageTek Storefront
16ページ · クリックして拡大
16ページ

StorageTek employees and for contract customers and partners with a login and password.

The location of the CRC is http://www.support.storagetek.com

Documents on CD

Documents on CD is a compact disc that contains portable document format (PDF) files of StorageTek’s tape, library, and OPENstorage disk publications. This CD is for StorageTek employees only. Contact the Logistics Depot to order the CD or get onto the distribution list.

Electronic Document Center

StorageTek’s Electronic Document Center (EDC) is an online service that provides links to technical publications about StorageTek products, pre-sales planning, and strategic tools. The EDC is for StorageTek employees only.

The location of the EDC is http://gandalf.stortek.com/dynaweb/prod

KnowledgeMap

StorageTek’s KnowledgeMap is an online service that provides product information, general resources, white papers, and answers to frequently asked questions. It also contains information about networks, platforms, and sales support. The KnowledgeMap is for StorageTek employees and distributors.

The location of the KnowledgeMap is http://wwfokm.stortek.com/

Partners Page

StorageTek’s Partners Page is an online service that provides information about events, education, products, and connectivity. The Partners Page is for StorageTek employees and partners with a login and password.

The location of the Partners Page is http://www.storagetek.com/Partners/

StorageTek Storefront

The Storefront is StorageTek’s external web site. The Storefront provides information about topics such as news bulletins, products, services, integrated solutions, customer support, and upcoming events. The storefront is accessible to all persons with a web browser.

The location of the Storefront is http://www.storagetek.com

xiv 9710 System Assurance Guide MR0012J

Preface

Page 17 of the StorageTek Tape Library (9710) user manual — I Education
17ページ · クリックして拡大
17ページ

I Comments and Suggestions

A Reader’s Comment Form at the back of this publication is for communicating suggestions or requests for change. We encourage and appreciate reader feedback.

I Education

The following paragraphs describe how to locate the training available for the 9710 Library.

If you have questions about registering for courses (including tuition and schedules), call the registrar at 303-673-6262.

Consult the current Corporate Education Course Catalog or view EDUCATION announcements on the intranet using Netscape for the latest offerings and schedules.

StorageTek employees should follow these steps to register:

1. Start Netscape.
2. Type the following URL: http://intwww.stortek.com
3. At the right side of the screen click on alphabetical .
4. Click on W for Workforce Development.
5. Scroll down and click on Workforce Development Home Page .

This takes you to the StorageTek Workforce Development web page. Make your selections from here.

MR0012J 9710 System Assurance Guide xv

Preface

Page 18 of the StorageTek Tape Library (9710) user manual — Comments and Suggestions
18ページ · クリックして拡大
18ページ

This page intentionally left blank.

xvi 9710 System Assurance Guide MR0012J

Preface

Page 19 of the StorageTek Tape Library (9710) user manual — 1: The System Assurance Process
19ページ · クリックして拡大
19ページ
StorageTek Tape Library (9710) — 1: The System Assurance Process diagram (page 19)
図 2 · 1: The System Assurance Process

Figure 1-1 shows the system assurance overview. The system assurance team members appear across the top of the figure. The process is the exchange of information among the team members to ensure that no aspects of the sale, ordering, and installation are overlooked. This promotes an error-free installation and contributes to customer satisfaction.

Figure 1-1. The System Assurance Overview

StorageTek Tape Library (9710) — 1: The System Assurance Process diagram (page 19)
図 3 · 1: The System Assurance Process
Page 20 of the StorageTek Tape Library (9710) user manual — I System Assurance Team Responsibilities
20ページ · クリックして拡大
20ページ

I System Assurance Team Responsibilities

Table 1-1 lists the responsibilities of the system assurance team members. The team ensures that all aspects of the process are planned carefully and carried out efficiently. Customer and StorageTek team members jointly own and control the process.

Table 1-1. Team Member Responsibilities

Solutions Delivery Installation Consultant (SDIC) (United States)

  • Leads the system assurance team in most cases.
  • Coordinates the system assurance process and oversees the use and implementation of this guide.

Solutions Delivery Manager (SDM) (international)

  • Schedules meetings between team members.
  • Supplies or obtains all necessary support documentation.
  • Works with the customer to complete the following worksheets:
  • Key personnel ( Chapter 2 )
  • Hardware configuration ( Chapter 4 )
  • Site survey ( Chapter 4 )
  • Receiving dock information ( Chapter 5 )
  • Inside delivery information ( Chapter 5 )
  • Access and administrative issues ( Chapter 5 )
  • Faxes all of the required and completed work sheets (except the sales entry form) to the appropriate orders offices. See Chapter 4 .
  • Works with the solutions delivery engineer (SDE) and the customer to provide delivery information as listed in “Solutions delivery engineer” responsibilities in this table.

Marketing representative (United States)

  • Leads the system assurance team in some cases.
  • Is responsible for the customer account.
  • Faxes the sales entry form to the Shared Services Center.
  • Follows up with the customer to ensure customer satisfaction.

System Assurance Team · Team Member Responsibilities

Page 21 of the StorageTek Tape Library (9710) user manual — System Assurance Team Responsibilities
21ページ · クリックして拡大
21ページ

Table 1-1. Team Member Responsibilities (Continued)

Solutions Delivery Engineer (SDE) • Prepares customer service support procedures.

  • Explains available levels of hardware support and criteria for problem escalation.
  • Installs the product at the customer site.

Customer • Works with the solutions delivery installation consultant (SDIC) at the system assurance planning meetings to provide the data for the worksheets listed for the SDIC.

  • Works with the solutions delivery systems specialist (SDSS) at the system assurance planning meetings to provide the data for the worksheet listed for the SE.
  • Names a contact person for any unresolved issues in the above worksheets.
  • Discusses the schedule and names a contact per son for all scheduling matters.

Solutions Delivery Systems Specialist (SDSS)

  • Explains available levels of software support and criteria for problem escalation.
  • Works with the customer to complete the work sheet.
  • Provides data migration information.

System Assurance Team · Team Member Responsibilities

Page 22 of the StorageTek Tape Library (9710) user manual — I The System Assurance Flowchart
22ページ · クリックして拡大
22ページ

The System Assurance Flowchart

I The System Assurance Flowchart

Figure 1-2 shows the system assurance process flow. The following pages describe the steps in more detail.

No two installations are the same; however, following this flowchart promotes a smooth system assurance process and an error-free installation.

Figure 1-2. The System Assurance Process Flow

StorageTek Tape Library (9710) — I The System Assurance Flowchart diagram (page 22)
図 4 · I The System Assurance Flowchart
Page 23 of the StorageTek Tape Library (9710) user manual — System Assurance Review Meetings
23ページ · クリックして拡大
23ページ

The System Assurance Flowchart

Proposal Acceptance

The system assurance process begins when the customer accepts the proposal. At this time, the solutions delivery installation consultant (in the United States) or the solutions delivery manager (internationally) schedules one or more system assurance planning meetings.

System Assurance Planning Meetings

The purpose of the system assurance planning meetings is to:

  • Explain system assurance as it applies to the 9710 Library
  • Establish the system assurance team
  • Establish the responsibilities of the team members
  • Establish the schedule for the system assurance process
  • Define hardware and software requirements
  • Complete the configuration worksheets, order worksheets, and other required worksheets ( Chapter 4 )
  • Set the dates and times for one or more system assurance review meetings

Order Placement

Depending on the customer, the appointed team member must now either:

  • Fax the completed worksheets to Orders Management (OM), or
  • Transfer information from the completed worksheets to the sales entry form and fax the sales entry form to the Shared Services Center (SSC)

See Chapter 4 for which of the above options and fax numbers to use.

Sales Entry Form or Order Worksheet Check

If the sales entry form or order worksheets are complete and correct, OM or SSC approves the order and assigns a ship date. If they are not correct, OM or SSC contacts the system assurance team for more information.

System Assurance Review Meetings

The purpose of the system assurance review meetings is to:

  • Complete the pre-installation checklists ( Chapter 5 )
  • Identify additional requirements
Page 24 of the StorageTek Tape Library (9710) user manual — I Schedule Planning
24ページ · クリックして拡大
24ページ

Preinstallation Checklist Error Check

If the preinstallation checklists are complete and correct, the sale is approved and the product is shipped. If they are not correct, the system assurance team completes or corrects them.

Installation

The SDE installs the 9710 Library at the customer’s site.

Post-installation Follow-up

The following actions follow up the installation:

  • The Error-Free Delivery Team tracks any exceptions to the original shipment.
  • The system assurance team leader completes the reader's comment form at the back of this guide or online to submit any comments on this guide. Refer to the end of the “How This Guide is Organized” on page xi for the fax number, address, and URL.
  • The SDE logs installation data into the Customer Services Data Collection (CSDC) system.
  • The SDE attends a follow-up meeting with the customer to review the completed project.

I Schedule Planning

When schedule planning is completed, attach a copy of the proposed schedule to this guide, and have the system assurance team members sign below.

Schedule Planning · StorageTek Representative (date) · Customer Representative (date)

Page 25 of the StorageTek Tape Library (9710) user manual — Delivery Contact
25ページ · クリックして拡大
25ページ

2 Key Personnel

This chapter enables you to record the names and phone numbers of the key personnel on the teams. The home phone number is optional.

I Customer Team

List names and telephone numbers of the following people:

CPU Hardware Contact

Phone office: home:

Operating Systems Software Contact

Phone office: home:

Communication Hardware Contact

Phone office: home:

Operations Contact

Phone office: home:

Delivery Contact

Phone office: home:

Show 5 more labels / short text on this page
___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________
Page 26 of the StorageTek Tape Library (9710) user manual — Solutions Delivery Installation Consultant
26ページ · クリックして拡大
26ページ

I StorageTek Team

List names and telephone numbers of the following people:

Marketing Representative

Phone office: home:

Solutions Delivery Systems Specialist

Phone office: home:

Solutions Delivery Engineer

Phone office: home:

SDE room on site:

Solutions Delivery Installation Consultant

Phone office: home:

Show 5 more labels / short text on this page
StorageTek Team · ___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________
Page 27 of the StorageTek Tape Library (9710) user manual — Software Contacts
27ページ · クリックして拡大
27ページ

StorageTek Hardware and Software

I StorageTek Hardware and Software Support

StorageTek provides the following phone numbers for hardware and software support:

Call Center (Hardware) U.S.-Colorado 1.303.673.4056 U.S.-Outside Colorado (Customers) 1.800.525.0369 U.S.-Outside Colorado (SDEs) 1.800.735.2778 Software Support U.S.-Outside Colorado 1.800.678.4430 U.S.-Colorado 1.303.673.4430

I Client Processor(s) Teams

List names and telephone numbers of the following CPU vendor people:

Hardware Contacts

Phone office: home:

Phone office: home:

Phone office: home:

Software Contacts

Phone office: home:

Phone office: home:

Phone office: home:

Show 6 more labels / short text on this page
_____________________________________________________________ · _____________________________________________________________ · _____________________________________________________________ · _____________________________________________________________ · _____________________________________________________________ · _____________________________________________________________
Page 28 of the StorageTek Tape Library (9710) user manual — Solutions Delivery Installation Consultant
28ページ · クリックして拡大
28ページ

I Channel Partner Team

List names and telephone numbers of the following people:

Marketing Representative

Phone office: home:

Solutions Delivery Systems Specialist

Phone office: home:

Solutions Delivery Engineer

Phone office: home:

SDE room on site:

Solutions Delivery Installation Consultant

Phone office: home:

Show 5 more labels / short text on this page
Channel Partner Team · ___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________ · ___________________________________________________________
Page 29 of the StorageTek Tape Library (9710) user manual — 3 Product Overview
29ページ · クリックして拡大
29ページ

3 Product Overview

This chapter provides an overview of the LSM, drive configurations, and interfaces.

The 9710 library consists of:

  • An LSM that stores 224 to 588 tape cartridges
  • A cartridge access port (CAP) that stores up to 14 cartridges
  • 9840, Digital Linear Tape (DLT), or 4890 drives installed behind the LSM right, front door.

Figure 3-1. 9710 LSM with Expansion Door

Page 30 of the StorageTek Tape Library (9710) user manual — I Power Distribution Unit (PDU)
30ページ · クリックして拡大
30ページ

I Drive Configurations

The LSM is shipped standard with no drive plates and with two 14-pack arrays above the drive wall (Panel 2). If fewer than four drives are ordered, two 14- pack arrays are installed above the three drives. If fewer than seven drives are ordered, one 14-pack array is installed above the six drives.

If the LSM is to contain more than six drives, you must also install the optional power distribution unit (PDU) and the PRM logic card.

Follow these rules for the cartridge drives, their associated arrays, and the cartridges used in the drives:

  • Install drives from bottom to top.
  • Allow no empty drive slots between installed drives.
  • If fewer than six drives are installed, install the optional arrays on Panel 2.
  • Do not use DATA D3 (helical recording) cartridges.

When mixing 4890 and DLT drives within the same LSM:

  • No more than six 4890 drives may be installed
  • The DLT drives must be installed above the 4890 drives.

When installing only DLT drives:

  • A maximum of 10 drives may be installed per LSM.

When mixing 9840 and DLT drives within the same LSM:

  • No more than six DLT drives may be installed
  • The DLT drives must be installed above the 9840 drives.
  • You may mix SCSI and Fibre Channel drives.

When installing only 9840 drives:

  • A maximum of 10 drives may be installed per LSM.
  • You may mix SCSI and Fibre Channel drives.

I Power Distribution Unit (PDU)

The standard 9710 can support up to 10 drives, but has power connections for only six drives. When you order the 9710 mounting hardware kits for more than six drives, you must also order the PDU. The PDU gives you power connections for four additional drives.

The PDU is a pass-through AC connector box with a power drop cable at one end and receptacles for four drives at the other end. The box is mounted in the 9710, but must be connected to a separate customer power drop. The international version comes without a cable plug, and cable leads are stripped.

Drive Configurations

Page 31 of the StorageTek Tape Library (9710) user manual — I Host Interfaces
31ページ · クリックして拡大
31ページ

The PRM card is shipped with the PDU, even though it is not part of the PDU. The card is mounted in the 9710 to provide data communication paths for the additional drives.

I Host Interfaces

The LSM provides two host ports for AS/400 direct connections. Two internal LSM cables are supplied for this configuration (see Figure 3-2 on page 3-4). Other configurations with the AS/400 might include a RISC/6000 server (see Figure 3-3 on page 3-5). Direct connections in non-AS/400 (open systems) configurations are also supported (see Figure 3-4 on page 3-6).

For host indirect connections to the LSM, a server [Unix-based, using Automated Cartridge Server Library (ACSLS) software or a RISC System/6000, using the Advanced Interactive Executive (AIX) operating system] is connected between the host and the LSM. An example of an indirect connection is an LSM hooked to a Unix server, with the server connected to an Ethernet LAN network. A cable is run from the Ethernet LAN to the host (see Figure 3-5 on page 3-7).

The connection from the server to the LSM is a SCSI Type-3 68-pin cable. The server may have its own control-side path (through a connection on the optional PRS circuit card), or may be daisy-chained to a shared data bus with one or more drives.

Figure 3-6 on page 3-8 shows the generic software requirements for the subsystems in either a direct connection or an indirect connection to the LSM.

Host Interfaces

Page 32 of the StorageTek Tape Library (9710) user manual — Host Interfaces
32ページ · クリックして拡大
32ページ

Figure 3-2. Direct Connection for AS/400 Control

StorageTek Tape Library (9710) — Host Interfaces diagram (page 32)
図 5 · Host Interfaces

Host Interfaces

Page 33 of the StorageTek Tape Library (9710) user manual — Host Interfaces
33ページ · クリックして拡大
33ページ

Figure 3-3. Client Configuration (Indirect Connection) with AS/400

StorageTek Tape Library (9710) — Host Interfaces diagram (page 33)
図 6 · Host Interfaces

Host Interfaces

Page 34 of the StorageTek Tape Library (9710) user manual — Host Interfaces
34ページ · クリックして拡大
34ページ

Figure 3-4. SCSI Direct Connection (Open Systems) with Common Bus

StorageTek Tape Library (9710) — Host Interfaces diagram (page 34)
図 7 · Host Interfaces

Host Interfaces

Page 35 of the StorageTek Tape Library (9710) user manual — Host Interfaces
35ページ · クリックして拡大
35ページ

Figure 3-5. Host-Indirect Connection

StorageTek Tape Library (9710) — Host Interfaces diagram (page 35)
図 8 · Host Interfaces

Host Interfaces

Page 36 of the StorageTek Tape Library (9710) user manual — Host Interfaces
36ページ · クリックして拡大
36ページ

Figure 3-6. Subsystem Generic Software Types

StorageTek Tape Library (9710) — Host Interfaces diagram (page 36)
図 9 · Host Interfaces

Host Interfaces

Page 37 of the StorageTek Tape Library (9710) user manual — I I/O Cabling Limits
37ページ · クリックして拡大
37ページ

I Data Interfaces

Refer to the 9840 Tape Drive System Assurance Guide, MT 5003, for 9840 data interface information.

The LSM has three data interfaces available:

  • Small Computer System Interface (SCSI) for all drives
  • Federal Information Processing Standard (FIPS) interface for 4890s
  • Fibre Channel for 9840s

4890 Data Buses

You may order FIPS bus drives, SCSI bus drives, or both. FIPS and SCSI are not available on the same drive.

Two FIPS data bus terminal blocks are present on a drive. Each bus in this definition includes the Data In, Data Out, Tag In, and Tag Out lines. You can use the two terminals for two data buses, use only one terminal block and terminate the other, or use the second terminal block for daisy chaining.

Each SCSI drive has two SCSI data bus connectors. You may use only one SCSI data bus input per drive. The other connector must be terminated, or it can be used for daisy chaining in a non-AS/400 environment, but it cannot be used for a second data bus.

DLT Data Buses

Each DLT has two SCSI data bus connectors. You can use only one SCSI data bus input per drive. The other connector must be terminated, or it can be used for daisy chaining, but it cannot be used for a second data bus.

I I/O Cabling Limits

Examine Figure 3-7 on page 3-11 and Figure 3-8 on page 3-12 while you read the following discussion.

Only one SCSI control line can exist. The other SCSI port, on both the SCSI card and the I/O tower, is reserved for daisy chaining; it should be terminated on the SCSI control interface card.

Two RS423/RS232 control lines can exist on the I/O tower. Each control may be connected to a separate AS/400.

Six FIPS data buses can exist on the I/O tower. Each bus in this definition includes the Data In, Data Out, Tag In, and Tag Out lines. If you are using two- bus FIPS drives, each connected at the I/O tower to two FIPS buses, then no

Data Interfaces

Page 38 of the StorageTek Tape Library (9710) user manual — I SCSI Library Robotic Interface
38ページ · クリックして拡大
38ページ

RS423

more than three FIPS drives can exist in the 9710. The remaining available drive slots can be used by SCSI drives.

Twenty SCSI data buses can exist on the I/O tower: 10 in and 10 out.

Twenty Fibre Channel data buses can exist on the I/O tower (with 9840 drives only): 10 in and 10 out.

The 3270 ports on the I/O tower currently are not used.

I RS423

The 9710 uses RS423 electronics in its control interface, rather than RS232. The RS423 and RS232 protocols are the same, but the RS423 electronics can drive a signal to greater distances.

The maximum RS423 cable length is 60 m (200 ft).

I SCSI Library Robotic Interface

The fast/narrow interface is single-ended or differential, and supports up to eight devices including the host.

The fast/wide interface is differential only, and supports up to 16 devices including the host.

Both interfaces are provided with the fast/wide 68-pin connector.

Page 39 of the StorageTek Tape Library (9710) user manual — RS423
39ページ · クリックして拡大
39ページ

SCSI Library Robotic Interface

Figure 3-7. 9710 I/O Panel (Showing FIPS)

StorageTek Tape Library (9710) — RS423 diagram (page 39)
図 10

not presently used. One of the two SCSI control interface ports is used for the control line; the other is reserved for daisy chaining.

Page 40 of the StorageTek Tape Library (9710) user manual — RS423
40ページ · クリックして拡大
40ページ

SCSI Library Robotic Interface

Figure 3-8. 9710 I/O Panel (Showing Fibre Channel)

StorageTek Tape Library (9710) — RS423 diagram (page 40)
図 11

not presently used. One of the two SCSI control interface ports is used for the control line; the other is reserved for daisy chaining.

Page 41 of the StorageTek Tape Library (9710) user manual — I Fax Numbers and Addresses
41ページ · クリックして拡大
41ページ

4 Ordering the Equipment

This chapter provides the worksheets to use when ordering the 9710 LSM.

I The Ordering Process

To order a 9710 LSM:

1. Make photocopies of the blank worksheets provided in this guide.
2. Obtain other required worksheets not provided in this guide.
3. Review the customer’s existing hardware and software.
4. Select the correct equipment and configuration for the customer’s needs.
5. Enter the information on the worksheets.
6. Review the items with the customer.
7. If necessary, transfer the appropriate information from the order worksheets to a sales entry form.
8. Fax the order worksheets or sales entry form to the appropriate orders department.

I Fax Numbers and Addresses

The orders department, the fax number, and the documents to fax depend on the customer. The department addresses and voice phone numbers are for your information.

Domestic customers, value-added distributors (VADs), and value-added resellers (VARs) must:

1. Transfer the information from the hardware order worksheet and the cables order worksheet to a sales entry form.

You are encouraged to use the software tool Galileo to identify a valid configuration, generate an accurate quote, and produce an error-free sales entry form.

2. Fax the following forms to Atlanta Shared Services Center:
  • Sales entry form
Page 42 of the StorageTek Tape Library (9710) user manual — I Hardware Order Worksheets
42ページ · クリックして拡大
42ページ
  • Library configuration worksheet
  • Site survey
  • Product checklist
Atlanta Shared Services Center Fax1-678-969-4015 , 4016 , or 4017

5390 Triangle Parkway, Suite 300 Norcross, GA 30092 Voice: 1-678-969-4000 or 1-800-903-7278 (toll-free in the U.S. only)

Original equipment manufacturers (OEMs), distributors, and subsidiaries in Canada, Japan, Australia, South Asia, and Mexico must fax the following forms to Orders Management:

  • Hardware order worksheet
  • Cables order worksheet
  • Site survey
Orders Management Fax1-303-673-2640 for distributors or subsidiaries Fax: 1-303-673-7654 for OEM

One StorageTek Drive Louisville, CO 80028-4350 Voice: 1-303-673-5513

I Hardware Order Worksheets

Use the following paragraphs and worksheets to plan your order.

For 9840 Drive information, refer to 9840 Tape Drive System Assurance Guide, MT 5003.

Hardware Order Worksheets

Page 43 of the StorageTek Tape Library (9710) user manual — Hardware Order Worksheets
43ページ · クリックして拡大
43ページ

Figure 4-1. 9710 Model/Feature Selections

StorageTek Tape Library (9710) — Hardware Order Worksheets diagram (page 43)
図 12 · Hardware Order Worksheets

include a SCSI card.

Hardware Order Worksheets

Page 44 of the StorageTek Tape Library (9710) user manual — DLT Drives
44ページ · クリックして拡大
44ページ

DLT Drives

Figure 4-2 on page 4-5 lists the DLT8000 model and feature number. Figure 4-3 on page 4-6 and Figure 4-4 on page 4-7 list the DLT7000 and DLT4000 feature numbers. The drives will ship with either a SCSI Fast/Narrow Differential interface or a SCSI Fast/Narrow Single-Ended interface. You will need SCSI Fast/ Wide 68-pin connectors to connect to the differential drives.

Each kit contains one DLT drive, differential terminator, slides, drive mounting tray, drive actuator mechanism, drive chassis, DLT power supply, cooling, hardware to mount the drive to the tray, and the drive power cord.

The PDU feature code includes the PDU, the appropriate power cord, the PRM card, and an additional drive-to-LSM interface cable.

Hardware Order Worksheets

Page 45 of the StorageTek Tape Library (9710) user manual — DLT Drives
45ページ · クリックして拡大
45ページ

Figure 4-2. DLT8000 Model and Feature Selections

Hardware Order Worksheets

Page 46 of the StorageTek Tape Library (9710) user manual — DLT Drives
46ページ · クリックして拡大
46ページ

Figure 4-3. DLT7000 Feature Selections

StorageTek Tape Library (9710) — DLT Drives diagram (page 46)
図 13 · DLT Drives

Hardware Order Worksheets

Page 47 of the StorageTek Tape Library (9710) user manual — DLT Drives
47ページ · クリックして拡大
47ページ

Figure 4-4. DLT4000 Feature Selections

StorageTek Tape Library (9710) — DLT Drives diagram (page 47)
図 14 · DLT Drives

Hardware Order Worksheets

Page 48 of the StorageTek Tape Library (9710) user manual — 4890 Drives
48ページ · クリックして拡大
48ページ

4890 Drives

Figure 4-5 lists the 4890 drive feature numbers.

Figure 4-5. 4890 Drive Feature Selections

StorageTek Tape Library (9710) — 4890 Drives diagram (page 48)
図 15 · 4890 Drives

Hardware Order Worksheets

Page 49 of the StorageTek Tape Library (9710) user manual — I Serial Cables, 9710 to Host
49ページ · クリックして拡大
49ページ

I PDU Power Cables

The PDU power cables are included when you order the PDU feature code. They are listed below in case you still want to order them separately.

Table 4-1. PDU Cables

Description Part Number Quantity K Cable assembly, international, 200–240 V, 10 A, 3 m (10 ft), 2-wire and ground. For main PDU

K Cable assembly, international, 200–240 V, 10 A, 2.4 m (8 ft), harmonized cord 1.5 mm2, EuroPlug. For optional PDU

K Cable assembly, South Korea, 100–127 V, VCTF cord 3 x 1.25 mm2, KSC 8305 plug. For optional PDU

K Cable assembly, domestic, twisted lock, 200–240 V, 20 A, 2.5 m (8.2 ft), 14 AWG SJT cord. For main PDU

K Cable assembly, domestic, twisted lock 200–240 V, 15 A, 2.5 m (8.2 ft), 16 AWG SJT cord. For optional PDU

K Cable assembly, domestic, 100–127 V, 20 A, 3 m (10 ft), 14 AWG SJT cord, NEMA 5-20P (IEC 320 plug). For main PDU

K Cable assembly, domestic, 100–127 V, 15 A, 2 m (7 ft), 16 AWG SJT cord, NEMA 5-15P (IEC 320 plug). For optional PDU

K Cable assembly, domestic, twisted lock, 100–127 V, 20 A, 2.5 m (8.2 ft), 14 AWG SJT cord. For main PDU

K Cable assembly, domestic, twisted lock, 100–127 V, 15 A, 2.5 m (8.2 ft), 16 AWG SJT cord. For optional PDU

I Serial Cables, 9710 to Host

If the robot is controlled by a serial RS423 connection, the 9710-end of the cables requires a female DB9 connector.

Show 10 more labels / short text on this page
PDU Power Cables · 411063801 ________ · 10083241 ________ · 10083657 ________ · 10083638 ________ · 10083639 ________ · 310287201 ________ · 10083242 ________ · 10083641 ________ · 10083642 ________
Page 50 of the StorageTek Tape Library (9710) user manual — K Cable assembly, DB9 (F)-DB24 (F), 6 m (20 ft) 310227201 ________
50ページ · クリックして拡大
50ページ

Serial Cables, 9710 to Host

Table 4-2. Serial Cables, 9710 to Host

Description Part Number Quantity K Cable assembly, DB9 (F)-DB24 (F), 4 m (13 ft) 310227101

K Cable assembly, DB9 (F)-DB24 (F), 6 m (20 ft) 310227201

K Cable assembly, DB9 (F)-DB24 (F), 12 m (39.4 ft) 310227301 ________

K Cable assembly, DB9 (F)-DB24 (F), 24 m (79 ft) 310227401 ________

Page 51 of the StorageTek Tape Library (9710) user manual — Cable Restriction
51ページ · クリックして拡大
51ページ

I SCSI Cabling

The following pages contain SCSI cable and adapter information.

Cable Restriction

Maximum allowed cable lengths (including the lengths already inside the 9710) are:

  • Single-ended: up to 6 m (20 ft) for up to 5 mega transfers per second
  • Single-ended: up to 3 m (9.5 ft) above 5 mega transfers per second
  • Differential: up to 25 m (82 ft)

(tailgate). Customers using SCSI Type 1 or 2 cable connectors must order a SCSI-1- or 2-to-SCSI 3 adapter for the LSM-end of their cables to correctly mate with the LSM.

Table 4-3 lists additional restrictions for SCSI connections.

Table 4-3. SCSI Cable Restriction

Single-Ended Stub length0.1 m (4 in.)
5–10 MHz data transfer rate3 m (10 ft)
1–5 MHz data transfer rate6 m (20 ft)
Differential Stub length0.2 m (10 in.)
1–10 MHz data transfer rate25 m (82 ft)

SCSI Cabling · Application Length Restriction

Page 52 of the StorageTek Tape Library (9710) user manual — SCSI Cabling
52ページ · クリックして拡大
52ページ

Figure 4-6. SCSI Connector Types

StorageTek Tape Library (9710) — SCSI Cabling diagram (page 52)
図 16 · SCSI Cabling

SCSI Cabling

Page 53 of the StorageTek Tape Library (9710) user manual — Cable Length Subtraction
53ページ · クリックして拡大
53ページ

Cable Length Subtraction

When considering the length of an external SCSI interface bus, you must subtract the length of bus already inside the 9710 from the maximum allowed cable length. The individual cable measurements inside the 9710 are:

  • From I/O tower to drive: 1.2 m (4 ft)
  • Daisy chains between drives: 0.5 m (18 in.) each
  • From I/O tower to library control: 2.4 m (8 ft)
  • From drive to library control (library control can be daisy chained from the drive data bus):

- 0.5 m (18 in.), or - 1.2 m (4 ft), or - 1.8 m (6 ft)

The total length of cable that must be subtracted from each bus is shown in Table 4-4. For the IBM AS/400 system, always subtract 1.2 m (4 ft) from the control or data bus. The AS/400 does not allow daisy chains.

Table 4-4. SCSI Cable Length Subtraction

Number of drives on the same data bus

Are data and control on the same bus? (Yes/No)

Subtract this value from maximum allowed cable length

1 (always 1 for AS/400) no (always no for AS/400) 1.2 m (4.0 ft) from drive bus 2.4 m (8.0 ft) from control bus

2 no 1.7 m (5.5 ft) from drive bus 2.4 m (8.0 ft) from control bus

3 no 2.1 m (7.0 ft) from drive bus 2.4 m (8.0 ft) from control bus

4 no 2.6 m (8.5 ft) from drive bus 2.4 m (8.0 ft) from control bus

5 no 3 m (10.0 ft) from drive bus 2.4 m (8.0 ft) from control bus

6 no 3.5 m (11.5 ft) from drive bus 2.4 m (8.0 ft) from control bus

7 no 4 m (13.0 ft) from drive bus 2.4 m (8.0 ft) from control bus

8 no 4.4 m (14.5 ft) from drive bus 2.4 m (8.0 ft) from control bus

9 no 5 m (16.0 ft) from drive bus 2.4 m (8.0 ft) from control bus

SCSI Cabling

Page 54 of the StorageTek Tape Library (9710) user manual — Cable Length Subtraction
54ページ · クリックして拡大
54ページ

Table 4-4. SCSI Cable Length Subtraction (Continued)

Number of drives on the same data bus

Are data and control on the same bus? (Yes/No)

Subtract this value from maximum allowed cable length

10 no 5.3 m (17.5 ft) from drive bus 2.4 m (8.0 ft) from control bus

1 yes 2.4 m (8.0 ft) from bus 1

2 yes 3 m (9.5 ft) from bus 1

3 yes 3.4 m (11.0 ft) from bus 1

4 yes 3.8 m (12.5 ft) from bus 1

5 yes 4.3 m (14.0 ft) from bus 1

6 yes 4.7 m (15.5 ft) from bus 1

7 yes 5.2 m (17.0 ft) from bus 1

8 yes 5.6 m (18.5 ft) from bus 1

9 yes 6 m (20.0 ft) from bus 1

10 yes 6.6 m (21.5 ft) from bus 1

SCSI Cabling

Page 55 of the StorageTek Tape Library (9710) user manual — K SCSI Daisy Chain Cable 250 mm (10 in.) 313109302 _____
55ページ · クリックして拡大
55ページ

9710 to Host

There are many external SCSI cables, depending on the platform. These cables are available through StorageTek. These are “standard” and will fit most applications for data and the control path.

Table 4-5. SCSI Cables 9710 to Host

x Description Part Number Quantity K Type CL21 SCSI External Interface Cable 3 m (10 ft) 10083309

K Type CL2P2 SCSI External Interface Cable 3 m (10 ft) 10083313

K Type CL2 SCSI External Interface Cable 6 m (20 ft) 10083310

K Type CL2P SCSI External Interface Cable 6 m (20 ft) 10083314

K Type CL2 SCSI External Interface Cable 15 m (49 ft) 10083311

K Type CL2P SCSI External Interface Cable 15 m (49 ft) 10083315

K Type CL2 SCSI External Interface Cable 20 m (65 ft) 10083312

K Type CL2P SCSI External Interface Cable 20 m (65 ft) 10083316

K SCSI Daisy Chain Cable 250 mm (10 in.) 313109302

K SCSI Daisy Chain Cable 460 mm (18 in.) 310292001 _____

2. Plenum-rated cable materials

SCSI Cabling

Page 56 of the StorageTek Tape Library (9710) user manual — K Terminator, fast/wide SCSI, 68-pin, differential 10148003 ________
56ページ · クリックして拡大
56ページ

Daisy Chain

Table 4-6. Specialized Daisy Chain Cables

x Description Part Number Quantity

K SCSI cable assembly, 1,830 mm (72 in.) 1–6 control 310254001

K SCSI cable assembly, 2,130 mm (84 in.) 1–6 control 313115701 ________

K SCSI cable assembly, 460 mm (18 in.) 310292001 ________

K SCSI cable assembly, 1,220 mm (48 in.) 7–10 control

K SCSI cable assembly, 250 mm (10 in.) 9840 313109302 ________

K SCSI cable assembly, 460 mm (18 in.) 9840 310292001 ________

Daisy Chain Terminators

Table 4-7 lists available terminators if your configuration requires additional terminators.

Table 4-7. Daisy Chain Terminators

x Description Part Number Quantity K Terminator, fast/wide SCSI, 68-pin, single ended 10148002

K Terminator, fast/wide SCSI, 68-pin, differential 10148003

SCSI Cabling · 310292101

Page 57 of the StorageTek Tape Library (9710) user manual — PRS Card
57ページ · クリックして拡大
57ページ

PRS Card

When installing a PRS in the 9710, the cables listed below are required from the PRC to the drives.

Table 4-8. PRS Card Cables

Drive Location Cable Length Part Number Quantity

9 1220 mm (48 in.) 310292101

8 1220 mm (48 in.) 310292101

7 1220 mm (48 in.) 310292101

6 1830 mm (72 in.) 310254001

5 1830 mm (72 in.) 310254001

4 1830 mm (72 in.) 310254001

3 1830 mm (72 in.) 310254001

2 1830 mm (72 in.) 310254001

1 2130 mm (84 in.) 313115701

0 2130 mm (84 in.) 313115701

SCSI Cabling

Page 58 of the StorageTek Tape Library (9710) user manual — Robotics Control, Internal
58ページ · クリックして拡大
58ページ

Robotics Control, Internal

The SCSI control card can be connected directly to the I/O panel or can be daisy chained to a tape drive.

Table 4-9. Robotics Control Cables, Internal

x Description Part Number Quantity K SCSI cable assembly, 68 (M) pin to 68 pin (F), 2,440 mm (96 in.) PRS to I/O panel 310294201

K SCSI cable assembly, 68 (M) pin to 68 pin (M), 40 mm (18 in.) PRS to drive (daisy chain) 310292001

K SCSI cable assembly, 68 (M) pin to 68 pin (M), 1,220 mm (48 in.) PRS to drive (daisy chain) 310292101

K SCSI cable assembly, 68 (M) pin to 68 pin (M), 1,820 mm (72 in.) PRS to drive (daisy chain) 310254001

SCSI Cabling

Page 59 of the StorageTek Tape Library (9710) user manual — AS/400 Data Path
59ページ · クリックして拡大
59ページ

AS/400 Data Path

The AS/400 special SCSI cables come in two models: above floor, and under floor (plenum). They must be used with the AS/400, and any other system which has similarly designed SCSI connectors.

only the IBM AS/400 Interposer connector, Part Number 05H3834. This IBM adapter connects standard 68–68 pin SCSI cables to the AS/400. In that case, do not order any additional cables.

Table 4-10. SCSI Cables and Adapters for AS/400 Path

x Description Part Number Quantity K IBM 68–68-pin AS/400 interposer connector is an adapter connector to attach standard 68–68-pin SCSI cables to the AS/400. Order this connector if you already have standard SCSI cables on site. If you do not, order only the cables below.

05H3834 (order from IBM)

K AS/400 special 68–68-pin SCSI cable, 3 m (10 ft) goes above floor

K AS/400 special 68–68-pin SCSI cable, 3m (10 ft) goes under floor (plenum)

K AS/400 special 68–68-pin SCSI cable, 6 m (20 ft) goes above floor

K AS/400 special 68–68-pin SCSI cable, 6 m (20 ft) goes under floor (plenum)

K AS/400 special 68–68-pin SCSI cable, 24 m (78.7 ft) goes above floor

K AS/400 special 68–68-pin SCSI cable, 24 m (78 ft) goes under floor (plenum)

Show 8 more labels / short text on this page
SCSI Cabling · ________ · 100821102 ________ · 100821111 ________ · 100821103 ________ · 100821112 ________ · 100821109 ________ · 100821118 ________
Page 60 of the StorageTek Tape Library (9710) user manual — Sun Sparc Workstation
60ページ · クリックして拡大
60ページ

Sun Sparc Workstation

Table 4-11. SCSI Cables and Adapters for Sun Sparc Workstation

x Description Part Number Quantity K StorageTek 3 m (10 ft) cable to attach the 9710 directly to the Sun/Sparc workstation motherboard, or to a station with SBE/S (fast/narrow, differential) or RSBE/S (fast/narrow, single-ended)

K Standard 68–68-pin SCSI cable. With this workstation interface feature, standard SCSI cables can be used without adapters: DWIS/S (fast/wide, differential)

SCSI Cabling · 10083522

Page 61 of the StorageTek Tape Library (9710) user manual — RS/6000, Bull DPX/20
61ページ · クリックして拡大
61ページ

RS/6000, Bull DPX/20

Table 4-12. SCSI Cables and Adapters for RS/6000 and Bull DPX/20

x Description Part Number Quantity K StorageTek 3 m (10 ft) cable to attach the 9710 directly to the Sun/Sparc workstation motherboard, or to a station with IBM RISC System/6000 with interface feature code 2420 (fast/narrow, single- ended)

K StorageTek 3 m (10 ft) cable to attach the 9710 directly to the Sun/Sparc workstation motherboard, or to a station with BULL DPX/20 with fast/narrow, single-ended feature

K IBM 68–68-pin (RISC System/6000) Interposer connector. This is an IBM adapter connector to attach standard 68–68-pin SCSI cables to RISC System/6000 with interface feature code 2416 (fast/ wide, differential). Use with one of the standard 68–68-pin cables.

50G0460 (order from IBM)

K IBM 68–68-pin (RISC System/6000) Interposer connector. This is an IBM adapter connector to attach standard 68–68 pin SCSI cables to BULL DPX/20 with fast/wide differential feature. Use with one of the standard 68–68-pin cables.

50G0460 (order from IBM)

K 68–68-pin special SCSI cable RISC System/6000 with IBM245 differential fast/wide adapter 12 m (40 ft). Use this cable in place of the IBM (50G0460) interposer and standard cables above, if a 12 m (40 ft) cable length is satisfactory.

Show 6 more labels / short text on this page
SCSI Cabling · 10083522 ________ · 10083522 ________ · ________ · ________ · 100821105 ________
Page 62 of the StorageTek Tape Library (9710) user manual — K 3 m (10 ft) 10083309 10083313 ______
62ページ · クリックして拡大
62ページ

SCSI Adapters

Table 4-13. Adapters, SCSI

x Description Part Number Quantity K SCSI adapter, narrow to wide bus (50-to-68 pin) 10148010

Single-Ended Narrow or Fast/Narrow to Wide

Table 4-14. Single-Ended Narrow or Fast/Narrow to Wide SCSI

x Description Part Number Quantity K Cable assembly, 50 (M) D Squeeze Lock, 68 (M) D Screw Lock, 3 m

High Density 68-68 Pin Standard Jackscrew

Table 4-15. High Density 68-68 Pin Jackscrew SCSI

x Cable Length Metric (English)

Above Floor Cable P/ N

Plenum (under floor Cable P/N) Quantity

K 3 m (10 ft) 10083309 10083313

K 6 m (20 ft) 10083310 10083314 ______

K 15 m (49 ft) 10083311 10083315 ______

K 20 m (66 ft) 10083312 10083316 ______

SCSI Cabling · 10083522

Page 63 of the StorageTek Tape Library (9710) user manual — K SCSI DIFF, TM 68-pin, 10 m (33 ft) 308398801 ________
63ページ · クリックして拡大
63ページ

AS/400 Serial Cables

Table 4-16. AS/400 Serial Cables

x Description Part Number Quantity K Cable assembly, serial AS/400, 4 m (13 ft) 310227101

K Cable assembly, serial AS/400, 6 m (20 ft) 310227201

K Cable assembly, serial AS/400, 12 m (39 ft) 310227301 ________

K Cable assembly, serial AS/400, 24 m (79 ft) 310227401 ________

Sequent Cables

Cables specific to Sequent are listed below.

Table 4-17. Sequent Cables

x Description Part Number Quantity K SCSI DIFF, TM 68-pin, 5 m (16.4 ft) 308398701

K SCSI DIFF, TM 68-pin, 10 m (33 ft) 308398801

K SCSI DIFF, TM 68-pin, 0.3 m (1 ft) 308398901 ________

K SCSI DIFF, TM 68-pin, 1.2 m (4 ft) 308399001 ________

K SCSI DIFF, TM 68-pin, 7.5 m (25 ft) 308399101 ________

K SCSI DIFF, TM 68-pin, 15 m (49 ft) 308399201 ________

K SCSI, DIFF, Terminator, 68-pin, 308399301 ________

SCSI Cabling

Page 64 of the StorageTek Tape Library (9710) user manual — FIPS Cables
64ページ · クリックして拡大
64ページ

I FIPS Cabling

The following pages contain FIPS cable and adapter information.

FIPS Cables

The two types of FIPS cables are Bus and Tag, and Internal Style. The Bus and Tag cables come in pairs. The Internal Style cable is a single cable with a shorter length limit.

A Y (serpentine) adapter cable may have to be used, depending on the AS/400 IOP and FIPS cable types. Cabling configurations are shown in Figure 4-7. Part numbers are listed below. The flagged 4-digit IBM part numbers must be ordered from IBM.

Figure 4-7. FIPS AS/400 Cabling Configurations

StorageTek Tape Library (9710) — FIPS Cables diagram (page 64)
図 17 · FIPS Cables

FIPS Cabling

Page 65 of the StorageTek Tape Library (9710) user manual — K Bus and tag cable pair 3 m (10 ft) 305436010 ________
65ページ · クリックして拡大
65ページ

Table 4-18. FIPS Cables

Description Part Number Quantity K Serpentine cable adapter, AS/400 IOP side (see usage in Figure 4-7 on page 4-24).

9980 (order from IBM)

K Y cable adapter, tape side (see usage in Figure 4-7 on page 4-24)

9927 (order from IBM)

K Internal Style cable 1.7 m (5.6 ft) 9928 (order from IBM)

K Internal Style cable 6.6 m (22 ft) 9929 (order from IBM)

K Internal Style cable 24 m (79 ft) 9930 (order from IBM)

K Bus and tag cable pair 3 m (10 ft) 305436010

K Bus and tag cable pair 15.24 m (50 ft) 305436050 ________

K Bus and tag cable pair 23 m (75 ft) 305436075 ________

K Bus and tag cable pair 31 m (100 ft) 305436100 ________

K Bus and tag cable pair 61 m (20 ft) 305436200 ________

K Bus and tag cable pair 91.44 m (300 ft) 305436300 ________

K Bus and tag cable pair 122 m (400 ft) 305436400 ________

FIPS Cabling

Page 66 of the StorageTek Tape Library (9710) user manual — FIPS Drive to I/O
66ページ · クリックして拡大
66ページ

FIPS Terminators

The following table lists available terminators if your configuration requires additional terminators.

Table 4-19. FIPS Terminators

x Description Part Number Quantity K Terminator, FIPS, Bus 10041793

K Terminator, FIPS, Tag 10041794 ________

FIPS Drive to I/O

The FIPS cable is listed below.

Table 4-20. FIPS Cables

x Description Part Number Quantity K FIPS cable assembly from drive to I/O panel 310259302

FIPS Cabling

Page 67 of the StorageTek Tape Library (9710) user manual — K Adapter, RJ45 9 pin (F) - DB9 (F) 10410823 ________
67ページ · クリックして拡大
67ページ

I Modem Cables

If the client plans on using a modem for remote support, make sure that one of the following modem cables is ordered.

Table 4-21. Modem Cables

x Description Part Number Quantity K 6 m (20 ft) 4108289-02

K 15 m (50 ft) 4108289-05 ________

K 31 m (100 ft) 4108289-10 ________

K 46 m (150 ft) 4108289-15 ________

K 61 m (200 ft) 4108289-20 ________

K 76 m (250 ft) 4108289-25 ________

Table 4-22. Remote Diagnostic Support for PC Use

x Description Part Number Quantity K Cable assembly, RJ45 8 pin (M) - RJ45 8 pin (M), 6 m (20 ft) 410828902

K Cable assembly, RJ45 8 pin (M) - RJ45 8 pin (M), 15 m (50 ft) 410828905

K Cable assembly, RJ45 8 pin (M) - RJ45 8 pin (M), 76 m (250 ft) 410828925

K Adapter, RJ45 9 pin (F) - DB9 (F) 10410823

Modem Cables

Page 68 of the StorageTek Tape Library (9710) user manual — I Cartridge Tapes and Labels
68ページ · クリックして拡大
68ページ

Cartridge Tapes and Labels

I Cartridge Tapes and Labels

The Media Service Center in Atlanta handles orders for cartridge tapes and labels. To obtain additional information about cartridge tapes and labels call the Media Service Center at 1-800-905-8502, or fax 1-877-888-0609; from 8:00 a.m. to 8:00 p.m. United States Eastern Standard Time Monday through Friday.

must be in place. We recommend that you order the necessary cartridges ahead of time.

For 9840 drives, order PN 310319401 (data cartridges used for diagnostics) and PN 310324601 (cleaning cartridges).

Order cartridge tapes and labels by including the order on the sales entry form, if used; the media portion of the order will be routed to the appropriate department.

Orders for domestic customers, valued-added distributors (VADs), and value-added resellers VARs):

5390 Triangle Parkway, Suite 300 Norcross, GA 30092 Voice: 1-800-905-8502 Media Service Center Fax: 1-877-888-0609

Orders from distributors, original equipment manufacturers (OEMs), and Canada, Japan, Australia, South Asia, or Mexico subsidiaries:

Orders Management Fax: 1-303-673-2640 for distributors or subsidiaries Fax: 1-303-673-7654 for OEM One StorageTek Drive Louisville, CO 80028-4350 Voice: 1-303-673-5513

Table 4-23. In-Country Media Supply Services (Sheet 1 of 2)

Region Country Telephone Number

Canada 1-800-668-1843 extension 605

Mexico 525 258 8000

United States 1-800-905-8502 · North America

Page 69 of the StorageTek Tape Library (9710) user manual — EAME
69ページ · クリックして拡大
69ページ

Cartridge Tapes and Labels

Table 4-23. In-Country Media Supply Services (Sheet 2 of 2)

Region Country Telephone Number

Austria 0800 20 16 31

Belgium 0800 75 327

France 0800 82 83 57

Germany 0800 181 6238

Holland 0800 022 8496

EAME

Ireland 1800 55 33 54

Italy 167 790 852

Norway 800 11 220

South Africa 0800 99 5820

Spain 900 99 33 66

Switzerland 0800 83 87 65

United Kingdom 0800 731 8852

Brazil 55 11 5185 2850

Japan 3 3746 9824

Singapore 65 774 9248

Kuala Lumpur 60 3 233 6102

China 86 10 6841 2211

Thailand 662 656 8873

Hong Kong 852 8200 0791

Show 4 more labels / short text on this page
Denmark 8088 0744 · Finland 08001 13361 · Sweden 020 798711 · World
Page 70 of the StorageTek Tape Library (9710) user manual — Cartridge Tapes and Labels
70ページ · クリックして拡大
70ページ

Cartridge Tapes and Labels

This page intentionally left blank.

Page 71 of the StorageTek Tape Library (9710) user manual — 5 Pre-installation Checklist
71ページ · クリックして拡大
71ページ

5 Pre-installation Checklist

On the following pages, verify that all issues have been addressed and resolved. Circle either “Yes” or “No” for each item. For unresolved issues, assign a required action with a due date to the appropriate person.

Table 5-1. Pre-installation Checklist

Item Description Yes/No Action Required/Due Date/Person Responsible

Options or features ordered

Tapes and labels ordered

Software prerequisites met Yes/No

Show 29 more labels / short text on this page
Site Preparation · Floor plans completed · Yes/No · Clearance adequate · Yes/No · Cooling adequate · Yes/No · Power requirements met · Yes/No · Cable lengths determined · Yes/No · Cable routing established · Yes/No · Future expansion considered · Yes/No · Dock facilities scheduled · Yes/No · Hardware Procurement · Subsystems ordered · Yes/No · Power cables ordered · Yes/No · Yes/No · Interface cables ordered · Yes/No · Interface adapters ordered · Yes/No · Yes/No · Software Procurement
Page 72 of the StorageTek Tape Library (9710) user manual — I Hardware Support Services
72ページ · クリックして拡大
72ページ

Table 5-1. Pre-installation Checklist (Continued)

Item Description Yes/No Action Required/Due Date/Person Responsible

I Fire Suppression System

K Yes K No

Ensure customer is aware that StorageTek does not supply fire suppression systems. Any fire suppression system for the 9710 is the customers’ responsibility.

I Hardware Support Services

K Yes K No

StorageTek offers an exclusive remote service to customers which is available 24 hours a day 7 days a week if a problem with the equipment occurs.

Table 5-2 lists the remote support hardware and cables to provide remote support for the customer.

Table 5-2. Remote Support Hardware and Cables

Equipment Description Part Number Ref Number

Modem 9600 Baud 4953 1

16 Port MARS+ 32 Port MARS+ 4954 4955 5 5

Show 20 more labels / short text on this page
Fire Suppression System · Software Installation · Scheduled · Yes/No · Completed · Yes/No · Hardware Installation · Delivery schedule completed · Yes/No · Dock hours scheduled · Yes/No · Pre-staging area set · Yes/No · Installation team identified · Yes/No · Site access arranged · Yes/No · Installation hours defined · Yes/No · Modem Switches
Page 73 of the StorageTek Tape Library (9710) user manual — Fire Suppression System
73ページ · クリックして拡大
73ページ

Table 5-2. Remote Support Hardware and Cables (Continued)

Equipment Description Part Number Ref Number

Cable RJ-45 to RJ-45

20 ft MARS/UUT interconnect 50 ft MARS/UUT interconnect 100 ft MARS/UUT interconnect 150 ft MARS/UUT interconnect 200 ft MARS/UUT interconnect 250 ft MARS/UUT interconnect

410828902 410828905 410828910 410828915 410828920 410828925

7

Modem/ MARS Interconnect Cable

4 ft modem to MARS interconnect (DB-25 to DB-9)

Hardware Support Services

Page 74 of the StorageTek Tape Library (9710) user manual — Fire Suppression System
74ページ · クリックして拡大
74ページ

This page intentionally left blank.

Hardware Support Services

Page 75 of the StorageTek Tape Library (9710) user manual — 100–254 VAC
75ページ · クリックして拡大
75ページ

A Site Planning Information

This appendix provides specifications and floor space requirements.

The following table lists the dimensions and weight of the LSM. Refer to your drive publications for the weight of the drives and cartridges and add the weights to the weights in the table.

Table A-1. 9710 Dimensions and Weights

Height 1830 mm (72 in.)

Width with covers 1490 mm (59 in.)

Depth 790 mm (32 in.)

Depth with expansion door 1020 mm (40 in.)

Weight of base unit with arrays 339 kg (747 lbs)

Weight of base unit with expansion door and arrays

375 kg (826 lbs)

Table A-2. LSM Power Specifications

Power cable U.S./Canada100 VAC UL/CSA power cable
International200–240 VAC HAR power cable

100–254 VAC

120 or 240 VAC

Power configuration U.S./CanadaSingle phase 100 VAC, 47–63 Hz, 20 A Service, 3-wire
InternationalSingle phase 200–240 VAC, 47–63 Hz, 10 A Service, 3wire

Power consumption 200 W

MR0012J 9710 System Assurance Guide A-1

Show 4 more labels / short text on this page
Input voltage range · Nominal voltage · Maximum heat output · 683 Btu/hr
Page 76 of the StorageTek Tape Library (9710) user manual — 29.2°C (84.5°F) 35°C (95°F) 35°C (95°F)
76ページ · クリックして拡大
76ページ

Table A-3. Optional Power Distribution Unit (PDU) Specifications

Power cable U.S./Canada120 VAC UL/CSA power cable
International200–240 VAC HAR power cable

100–254 VAC

120 or 240 VAC

Power configuration U.S./CanadaSingle phase 120 VAC, 47–63 Hz, 6 A Service, 3-wire
I nternationalSingle phase 200–240 VAC, 47–63 Hz, 3 A Service, 3wire

Power consumption 38 W

Table A-4. LSM Environmental Specifications

Temperature Operating Storage Shipping

15° to 32°C (59° to 90°F) 10° to 40°C (50° to 104°F) 10° to 40°C (50° to 104°F)

Relative Humidity Operating Storage Shipping

20% to 80% (noncondensing) 10% to 95% (noncondensing) 10% to 95% (noncondensing)

Wet Bulb Maximum Operating Storage Shipping

29.2°C (84.5°F) 35°C (95°F) 35°C (95°F)

Altitude Operating Storage Shipping

0 to 3.05 km (0 to 10,000 ft) 0 to 3.05 km (0 to 10,000 ft) 0 to 15.24 km (0 to 50,000 ft)

A-2 9710 System Assurance Guide MR0012J

Show 4 more labels / short text on this page
Input voltage range · Nominal voltage · Maximum heat output · 128 Btu/hr
Page 77 of the StorageTek Tape Library (9710) user manual — LSM EXPANDED UNIT SERVICE AREA REQUIREMENTS
77ページ · クリックして拡大
77ページ

Figure A-1. 9710 Layout and Floor Space Requirements

SEE NOTE 1

POWER CABLE CUTOUT

148.82 (58.59) 153.26 (60.34)

218.92 (86.19)

LSM BASIC UNIT SERVICE AREA REQUIREMENTS

218.92 (86.19)

SEE NOTE 1

15.24 (6)

60.96 (24)

FIPS CABLES CUTOUT

(SEE NOTE 2)

149.12 (58.71) 153.57 (60.46)

240.23 (94.58)

LSM EXPANDED UNIT SERVICE AREA REQUIREMENTS

NOTES:

91.44 cm (3.0 ft) access required during installation. Library may then be pushed back against a wall and stablilized.

Cable cutout is optional as cables may be routed above the floor. For raised floor installation, a 15.24 x 61cm (6 X 24 in.) cutout is recommended if FIPS cables are used.

The dimensions in parentheses are in inches.

MR0012J 9710 System Assurance Guide A-3

Page 78 of the StorageTek Tape Library (9710) user manual — A: Site Planning Information
78ページ · クリックして拡大
78ページ

Table A-5. Power Characteristics

Description Value / Part Identification Picture

Power drops for 9710 and PDU 1, each: (47-63 Hz AC range. 3-wire cables supplied. International cables are supplied without cable connectors)

U.S./Canada120 VAC, single phase
International200-240 VAC, single phase

9710 120 VAC domestic plug feature code 70DD

NEMA 5-20P, supplied with 9710

PDU 120 VAC domestic plug NEMA 5-15P, supplied by client

9710 120 VAC domestic wall receptacle

NEMA 5-20R, supplied by client

PDU 120 VAC domestic wall receptacle

NEMA 5-15R, supplied by client

International plugs and receptacles for 9710 and, if applicable, for PDU

May be supplied by client according to local electrical codes. See power specifications below. See Table 4-1 on page 4-9.

Current input for library without drives 1

1.250 A at 120 VAC 0.625 A at 240 VAC 2.000 A at 120 VAC

Current input for each 4890 drive 1 1.000 A at 240 VAC 0.60 A at 120 VAC 0.30 A at 240 VAC

Power usage for library without drives 1

Watts 150 peak / 100 Continuous KVA 0.15 Peak / 0.10 Continuous

A-4 9710 System Assurance Guide MR0012J

Page 79 of the StorageTek Tape Library (9710) user manual — A: Site Planning Information
79ページ · クリックして拡大
79ページ

Table A-5. Power Characteristics (Continued)

Description Value / Part Identification Picture

Power usage for library without drives 1

Watts 150 peak / 100 Continuous KVA 0.15 Peak / 0.10 Continuous

Power usage for each 4890 drive 1 Watts 270 Peak / 230 Continuous KVA 0.27 Peak / 0.23 Continuous

Power usage for each DLT drive 1 Watts 70 Peak / 60 Continuous KVA .070 Peak / .060 Continuous

Heat output for library without drives

Heat output for each 4890 drive 880 BTU/hr

Heat output for each DLT drive 257 BTU/hr

MR0012J 9710 System Assurance Guide A-5

680 BTU/hr

Page 80 of the StorageTek Tape Library (9710) user manual — A: Site Planning Information
80ページ · クリックして拡大
80ページ

This page intentionally left blank.

A-6 9710 System Assurance Guide MR0012J

Page 83 of the StorageTek Tape Library (9710) user manual — R EADER ’ S C OMMENT F ORM
83ページ · クリックして拡大
83ページ

R EADER ’ S C OMMENT F ORM

Manual Name___________________________________________ Manual PN: _______________

Please check or fill in the items; adding explanations/comments in the space provided.

Which of the following terms best describes your job?

K Field Engineer K Manager K Programmer K Systems Analyst K Engineer K Mathematician K Sales Representative K Systems Engineer K Instructor K Operator K Student/Trainee K Other (explain below)

How did you use this publication?

K Introductory text K Reference Manual K Student/Trainee K Instructor text K Other (explain)

Did you find the material easy to read and understand? K Yes K No (explain below)

Did you find the material organized for convenient use? K Yes K No (explain below)

Specific criticisms (explain below):

Clarification on pages Additions on pages Deletions on pages Errors on pages

Explanations and other comments:

Thank you for your cooperation. No postage stamp is required if mailed in the U.S.A.

Page 84 of the StorageTek Tape Library (9710) user manual — Reader’s Comment Form
84ページ · クリックして拡大
84ページ
StorageTek Tape Library (9710) — Reader’s Comment Form diagram (page 84)
図 18 · Reader’s Comment Form

TO COMPLY WITH POSTAL REGULATIONS, FOLD EXACTLY ON DOTTED LINES AND TAPE (DO NOT STAPLE)

NEARLINE INFORMATION DEVELOPMENT MS 2201 STORAGE TECHNOLOGY CORPORATION ONE STORAGETEK DRIVE LOUISVILLE CO 80027-9984

FOLD HERE AND TAPE DO NOT STAPLE FOLD HERE AND TAPE

STORAGE TECHNOLOGY CORPORATION ONE STORAGETEK DRIVE Louisville, CO 80028-2201

CSE World Wide Tech Support303-673-4056 OEM Tech Support 303-673-3126
Page 85 of the StorageTek Tape Library (9710) user manual — Reader’s Comment Form
85ページ · クリックして拡大
85ページ
Page 85 of the StorageTek Tape Library (9710) user manual — Reader’s Comment Form
Page 86 of the StorageTek Tape Library (9710) user manual — Reader’s Comment Form
86ページ · クリックして拡大
86ページ

World Headquarters Storage Technology Corporation One StorageTek Drive Louisville, Colorado 80028 USA Phone: 1.800.786.7835 Fax: 719.536.4053

© 1999 Storage Technology Corporation, Louisville, CO. All rights reserved. Printed in USA. StorageTek, the signature, and Information Made Powerful are trademarks of Storage Technology Corporation. Other product names mentioned may be trademarks of Storage Technology Corporation or other vendors/manufacturers.

情報源

参考資料・リンク

この取扱説明書で参照されているリンク(メーカー、サポート、ダウンロード等)。

StorageTek Tape Library (9710)について質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
StorageTek Tape Library (9710)に関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

StorageTek Tape Library (9710) 取扱説明書(PDF)

86 ページ·1.4 MB·PC用ドライブ·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…