NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,.
can be no deviation. Consult the Application Guideline and Service Manual—Air Conditioners and Heat Pumps Using Pu- ron® Refrigerant to obtain required unit changes for specific applications and for R-22 retrofit. I. CHECK EQUIPMENT AND JOB SITE A.
INSTALLING TXV IN PLACE OF PISTON 1. Pump system down to 2 psig and recover refrigerant. 2. Remove hex nut from piston body. Use backup wrench on fan coils. 3. Remove and discard factory-installed piston. Be sure teflon seal is in place. 4. Reinstall hex nut.
CAUTION: To prevent improper performance and/or unit component failures, do not leave system open to atmosphere any longer than minimum required for instal- lation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
C. REFRIGERANT TUBING Connect vapor tube to fitting on outdoor unit vapor service valves. Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Use refrigerant grade tubing. D. SWEAT CONNECTION CAUTION: To avoid valve damage while brazing, ser- vice valves must be wrapped in a heat-sinking material such as a wet cloth.
A. ROUTE GROUND AND POWER WIRES Remove access panel to gain access to unit wiring. Extend wires from disconnect through power wiring hole provided and into unit control box. WARNING: The unit cabinet must have an uninter- rupted or unbroken ground to minimize personal injury if an electrical fault should occur.
EXAMPLE: To calculate additional charge requried for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/f t=6o zo f additional charge. B. COOLING ONLY PROCEDURE UNITS WITH COOLING MODE PURON® TXV Units installed with cooling mode TXV require charging by the subcooling method.
6. Refer to Table 4. Find outdoor temperature and evaporator entering air wet-bulb temperature. At this intersection, note superheat. 7. Refer to Table 5. Find superheat temperature located in item 6 and suction pressure. At this intersection, note suction line temperature.
24 VAC HOT 24 VAC COM R C G W/W1 Y/Y2 R C C BRYANT NON-PROGRAMMABLE THERMOSTAT MODEL AC SINGLE-STAGE FURNACE AIR CONDITIONER SEE NOTE 2 Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97359 24 VAC HOT R G.
24 VAC HOT R C W/W1 Y/Y2 G R DH W2 W1 Y/Y2 BRYANT NON-PROGRAMMABLE THERMOSTAT MODEL AC FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 24 VAC COM Y1 C SEE NOTE 2 G O J2 JUMPER J1 .
PURON® (R–410A) QUICK REFERENCE GUIDE • Puron® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron® • Puron® refrigerant cylinders are rose colored.
© 2003 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —12— Printed in U.S.A. 550a184 Catalog No. 5355-020.
デバイスBryant 591Bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 591Bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 591Bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 591Bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 591Bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 591Bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 591Bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 591Bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 591Bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。