Compact Make-up Air Unit

Modbus Communication Module User Guide

neptronic Compact Make-up Air Unit (CMU-Modbus) — Compact Make-up Air Unit diagram (page 1)
図 2 · Compact Make-up Air Unit
neptronic Compact Make-up Air Unit (CMU-Modbus) — Compact Make-up Air Unit diagram (page 1)
図 3 · Compact Make-up Air Unit

CMU-Modbus Guide-211125

Page 2 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Introduction
2ページ · クリックして拡大
2ページ
neptronic Compact Make-up Air Unit (CMU-Modbus) — Introduction diagram (page 2)
図 4 · Introduction

Introduction

The Compact Make-up Air Unit Modbus Communication Module User Guide provides information for using Neptronic communication feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic Compact Make-up Air Unit devices. The Compact Make-up Air Unit Modbus Guide assumes that you are familiar with Modbus terminology. The following are the requirements for Modbus:

  • Data Model . The Compact Make-up Air Unit Modbus server data model uses only the Holding Registers table.
  • Register Address :

o As per protocol base (base 0); for PLC add 1 to protocol base.

o As per holding register (base 40001).

  • Function Codes . The Compact Make-up Air Unit Modbus server supports a limited function codes subset comprising:

o Read Holding Registers (0x03)

o Write Single Register (0x06)

o Write Multiple Registers (0x10)

  • Exception Responses . The Compact Make-up Air Unit Modbus server supports the following exception codes:

o Illegal data address

o Illegal data value

o Slave device busy

  • Serial Line . The Compact Make-up Air Unit Modbus over serial line uses RTU transmission mode over a twowire configuration RS485 (EIA/TIA-485 standard) physical layer.

o The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.

o The supported baud rates are 9600, 19200, 38400, 57600 and 76800 bps.

o The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.

o In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.

o If the device does not detect any activity for one second or more, it will find a silent line to prevent a possible baud rate scan on the next frame it detects.

  • Addressing . The Compact Make-up Air Unit device only answers at the following address:

o The device's unique address (1 to 247) that can be set through the device menu or through holding register index 0.

Page 3 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Holding Register Table
3ページ · クリックして拡大
3ページ

Holding Registers Table

Glossary

NameDescriptionNameDescription WWritable RegisterASCIIFor registers containing ASCII (8-bit) characters RORead Only RegisterMSBMost Significant Byte UnsignedFor range of values from 0 to 65,535, unless otherwise specifiedLSBLeast Significant Byte SignedFor range of values from -32,768 to 32,767, unless otherwise specifiedMSWMost Significant Word Bit StringFor registers with multiple values using bit mask (example, flags)LSWLeast Significant Word
neptronic Compact Make-up Air Unit (CMU-Modbus) — Holding Registers Table diagram (page 3)
図 5 · Holding Registers Table

Holding Register Table

ProtocolHoldingDescriptionData TypeRangeWritable BaseRegister 040001Modbus product type and address.UnsignedMB = Modbus Address (e.g. 110), LB = 1-247W 140002Analog input 1 voltage.Unsigned Scale 1000Unit: Volts (V), Range: 0V to 10V Value x 1000 (e.g. 2V = 2000)RO 240003Analog input 2 voltage.Unsigned Scale 1000Unit: Volts (V), Range: 0V to 10V Value x 1000 (e.g. 2V = 2000)RO 340004Analog input 3 temperature.Signed Scale 100Units: °C/°F, Range: -40°C to 85°C or -40°F to 185°F Value x 100 (e.g. 25°C = 2500 or 25°F = 2500)RO 440005Analog input 4 temperature.Signed Scale 100Units: °C/°F, Range: -40°C to 85°C or -40°F to 185°F Value x 100 (e.g. 25°C = 2500 or 25°F = 2500)RO 540006Room air temperature value measured by TDF.Unsigned Scale 100Units: °C/°F, Range : 0°C to 50°C or 32°F to 122°F Value x 100 (e.g. 5°C = 500 or 50°F = 5000)RO 640007Room air relative humidity value measured by TDF.Unsigned Scale 10Unit: %RH, Range: 0 to 100%RH Value x 10 (e.g. 10%RH = 100)RO 740008Room CO2 concentration value measured by TDF.Unsigned Scale 1Unit: PPM, Range: 0 to 2000 PPM Value x 1 (e.g. 2 PPM = 2)RO 840009Volatile organic compound index measured by TDF.Unsigned Scale 1Unit: No Unit, Range: 0 to 65535, Value x 1 (e.g. 100 = 100)RO
Page 4 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Holding Registers Table
4ページ · クリックして拡大
4ページ
ProtocolHoldingDescriptionData TypeRangeWritable BaseRegister 940010Luminous flux measured by TDF.Unsigned Scale 1Unit: Lux, Range: 0 to 16000 Lux Value x 1 (e.g. 2 Lux = 2)RO 1040011CMU on-board potentiometer temperature setpoint.Unsigned Scale 100Units: °C/°F, Range: 0°C to 35°C or 32°F to 95°F Value x 100 (e.g. 2°C = 200 or 50°F = 5000)RO 1140012CMU intake temperature.Signed Scale 100Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)RO 1240013CMU outtake temperature.Signed Scale 100Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)RO 1340014CMU board temperature.Signed Scale 100Units: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°F Value x 100 (e.g. 23°C = 2300 or 23°F = 2300)RO 1440015CMU SSR temperature.SignedUnits: °C/°F, Range: -40ºC to 85ºC or -40°F to 185°FRO Scale 100Value x 100 (e.g. 23°C = 2300 or 23°F = 2300) 1540016AI3/BI3 multi-mode input state.Unsigned0 = Open, 1 = ClosedRO 1640017AI4/BI4 multi-mode input state.Unsigned0 = Open, 1 = ClosedRO 1740018Room movement detection occupancy sensor.Unsigned0 = No, 1 = YesRO 1840019CMU On/Off contact input state.Unsigned0 = Off, 1 = OnRO 1940020Analog output 1 voltage.Unsigned Scale 100Unit: Volts, Range: 0V to 10V Value x 100 (e.g. 3V = 300)RO 2040021Analog output 2 voltage.Unsigned Scale 100Unit: Volts, Range: 0V to 10V Value x 100 (e.g. 3V = 300)RO 2140022Binary output 1 state.Unsigned0 = Open, 1 = ClosedRO 2240023Binary output 1 state.Unsigned0 = Open, 1 = ClosedRO 2340024Supply air temperature.Unsigned Scale 100Units: °C/°F, Range: 0°C to 100°C or 32°F to 212°F Value x 100 (e.g. 2°C = 200 or 50°F = 5000)RO 2440025Supply air relative humidity.Unsigned Scale 100Units: %RH, Range: 0 to 100%RH Value x 100 (e.g. 23%RH = 2300)RO 2540026Outside air temperature.SignedUnits: °C/°F, Range: -40ºC to 50ºC or -40°F to 122°FRO Value x 100 (e.g. 23°C = 2300 or 23°F = 2300) Scale 100 2640027Outside air relative humidity.Unsigned Scale 100Units: %RH, Range: 0 to 100%RH Value x 100 (e.g. 23%RH = 2300)RO 2740028Duct static pressure.Unsigned Scale 10Units: Pascal (Pa), Range: 0 to 1250 Pa Value x 10 (e.g. 50 Pa = 500)RO
Page 5 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Holding Registers Table
5ページ · クリックして拡大
5ページ
ProtocolHoldingDescriptionData TypeRangeWritable BaseRegister 2840029Damper position feedback.Unsigned Scale 1Unit: %, Range: 0% to 100%, Value x 1 (e.g. 100% = 100)RO 2940030Current airflow setpoint in percent of maximum capacity.Unsigned Scale 1Unit: %, Range: 0% to 100%, Value x 1 (e.g. 100% = 100)RO 3040031CMU ECM fan speed feedback value.Unsigned Scale 1Unit: RPM, Range: 0 to 10000 RPM, Value x 1 (e.g. 100 RPM = 100)RO 3140032Heater vernier stage duty cycle.Unsigned Scale 10Unit: %, Range: 0 to 100%, Value x 10 (e.g. 100% = 1000)RO 3240033Network temperature setpoint.Unsigned Scale 100Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F, Value x 1 (e.g. 5°C = 500 or 50°F = 5000)W 3340034TDF temperature setpoint.Unsigned Scale 100Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F, Value x 1 (e.g. 5°C = 500 or 50°F = 5000)W 3440035CMU anti-freeze setpoint.Unsigned Scale 100Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F, Value x 1 (e.g. 5°C = 500 or 50°F = 5000)W 3540036Occupied airflow setpoint in percent of maximum capacity.Unsigned Scale 1Unit: %, Range: 0 to 100%, Value x 1 (e.g. 100% = 100)W 3640037Unoccupied airflow setpoint in percent of maximum capacity.Unsigned Scale 1Unit: %, Range: 0 to 100%, Value x 1 (e.g. 100% = 100)W 3740038Binary input 3 stage weight.Unsigned Scale 1Unit: %, Range: 0 to 100%, Value x 1 (e.g. 100% = 100)W 3840039Binary input 4 stage weight.Unsigned Scale 1Unit: %, Range: 0 to 100%, Value x 1 (e.g. 100% = 100)W 3940040Exhaust fan start delay.Unsigned Scale 1Unit: Seconds, Range: 1 to 255 seconds Value x 1 (e.g. 10 secs = 10)W 4040041Exhaust fan control signal minimum value.Unsigned Scale 100Unit: Volts (V), Range: 0 to 10V, Value x 100 (e.g. 3V = 300)W 4140042Exhaust fan control signal maximum value.Unsigned Scale 100Unit: Volts (V), Range: 0 to 10V, Value x 100 (e.g. 3V = 300)W 4240043Damper stroke time.Unsigned Scale 1Unit: Seconds, Range: 1 to 255 seconds, Value x 1 (e.g. 100 secs = 100)W 4340044Occupancy inputs minimum time.Unsigned Scale 1Unit: Minutes, Range: 0 to 240 minutes, Value x 1 (e.g. 10 mins = 10)W
Page 6 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Holding Registers Table
6ページ · クリックして拡大
6ページ
ProtocolHoldingDescriptionData TypeRangeWritable BaseRegister 4440045Temperature setpoint minimum value.Unsigned Scale 100Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F, Value x 1 (e.g. 5°C = 500 or 50°F = 5000)W 4540046Temperature setpoint maximum value.Unsigned Scale 100Unit: °C/°F, Range: 0°C to 35°C or 32°F to 95°F, Value x 1 (e.g. 5°C = 500 or 50°F = 5000)W 4640047Dry mode relative humidity setpoint.Unsigned Scale 1Unit: %RH, Range: 10 to 90%RH Value x 1 (e.g. 10%RH = 10)W 4740048Dry mode relative humidity setpoint dead band.Unsigned Scale 1Unit: %RH, Range: 1 to 10%RH Value x 1 (e.g. 10%RH = 10)W 4840049Occupied static pressure control loop setpoint.Unsigned Scale 10Unit: Pascal (Pa), Range: 0 to 1250 Pa Value x 10 (e.g. 3 Pa = 30)W 4940050Unoccupied static pressure control loop setpoint.Unsigned Scale 10Unit: Pascal (Pa), Range: 0 to 1250 Pa Value x 10 (e.g. 3 Pa = 30)W 5040051CO2 concentration setpoint.Unsigned Scale 1Unit : PPM, Range : 0 to 1000 PPM Value x 1 (e.g. 3 PPM = 3)W 5140052CO2 concentration setpoint dead band.UnsignedUnit : PPM, Range : 0 to 200 PPMW Value x 1 (e.g. 3 PPM = 3) Scale 1 5240053Supply air temperature offset.Signed Scale 100Unit: °C/°F, Range: ± 5ºC or +/-9ºF Value x 100 (e.g. 2ºC = 200 or 3ºF = 300)W 5340054Supply air temperature humidity offset.Signed Scale 100Unit: %RH, Range: ± 5%RH Value x 100 (e.g. 2%RH = 200)W 5440055Outside air temperature offset.Signed Scale 100Unit: °C/°F, Range: ± 5ºC or +/-9ºF Value x 100 (e.g. 2ºC = 200 or 3ºF = 300)W 5540056Outside air temperature humidity offset.Signed Scale 100Unit: %RH, Range: ± 5%RH Value x 100 (e.g. 2%RH = 200)W 5640057Room air temperature offset.Signed Scale 100Unit: °C/°F, Range: ± 10ºC or ± 18ºF Value x 100 (e.g. 2ºC = 200 or 3ºF = 300)W 5740058Room air relative humidity offset.Signed Scale 100Unit: %RH, Range: ± 5%RH Value x 100 (e.g. 2%RH = 200)W 5840059Static pressure offset.Signed Scale 10Unit: Pascal (Pa), Range: ± 125 Pa Value x 10 (e.g. 2 Pa = 200)W 5940060Minimum fan speed.Unsigned Scale 1Unit: %, Range: 0 to 100% Value x 1 (e.g. 3% = 3)W
Page 7 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Holding Registers Table
7ページ · クリックして拡大
7ページ

60 40061 Temperature control proportional band. Unsigned

Unit: °C/°F, Range: 0.5°C to 20°C or 33°F to 68°F, Value x 100 (e.g. 5°C = 500 or 50°F = 5000) W

Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W

61 40062 Temperature control integral time. Unsigned

62 40063 Temperature control derivate time. Unsigned

Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W

63 40064 Static pressure control proportional band. Unsigned

Unit: Pascal (Pa), Range: 0 to 250 Pa Value x 1 (e.g. 3 Pa = 3) W

64 40065 Static pressure control integral time. Unsigned

Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W

65 40066 Static pressure control derivate time. Unsigned

Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W

66 40067 Control band. Unsigned

Unit: °C/°F, Range: 2°C to 10°C or 36°F to 50°F, Value x 100 (e.g. 5°C = 500 or 50°F = 5000) W

Unit: Seconds, Range: 15 to 1800 seconds, Value x 1 (e.g. 100 secs = 100) W

67 40068 Modbus timeout. Unsigned

68 40069 Number of synchronization timeouts. Unsigned

UnitNo Unit, Range: 0 to 65535, Value x 1 (e.g. 100 = 100) W

69 40070 No heat detection deadband. Unsigned

Unit: °C/°F, Range: 2°C to 8°C or 36°F to 46°F, Value x 100 (e.g. 5°C = 500 or 5°F = 500) W

70 40071 No heat detection delay. Unsigned

Unit: Seconds, Range: 30 to 240 seconds, Value x 1 (e.g. 100 secs = 100) W

71 40072 Exhaust fan state. Unsigned 0 = Off, 1 = On RO

72 40073 On/Off damper state. Unsigned 0 = Closed, 1 = Open RO

73 40074 On/Off damper feedback. Unsigned 0 = Closed, 1 = Open RO

74 40075 CMU fan enable. Unsigned 0 = No, 1 = Yes RO

75 40076 CMU heater stage 2 state. Unsigned 0 = Off, 1 = On RO

76 40077 Binary input 3 contact type. Unsigned 0 = NO, 1 = NC W

77 40078 Binary input 4 contact type. Unsigned 0 = NO, 1 = NC W

78 40079 Binary output 1 contact type. Unsigned 0 = NO, 1 = NC W

79 40080 Binary output 2 contact type. Unsigned 0 = NO, 1 = NC W

Page 8 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Holding Registers Table
8ページ · クリックして拡大
8ページ

80 40081 Enable occupancy inputs. Unsigned 0 = No, 1 = Yes W

81 40082 Dry mode. Unsigned 0 = Disable, 1 = Enable W

82 40083 CO2 extract. Unsigned 0 = Disable, 1 = Enable W

83 40084 Static pressure loop. Unsigned 0 = Disable, 1 = Enable W

84 40085 Occupancy inactive mode. Unsigned 0 = Unoccupied, 1 = Off W

85 40086 CMU occupancy state. Unsigned 1 = Occupied | 2 = Unoccupied | 3 = Off W

86 40087 Temperature setpoint source. Unsigned 1 = On Board | 2 = TSTAT | 3 = Network W

87 40088 AI1 input mode. Unsigned 1 = Off | 2 = SAT | 3 = SARH | 4 = OAT | 5 = OARH | 6 = Static Pressure | 7 = Fan Setpoint | 8 = Damper Feedback W

88 40089 AI2 input mode. Unsigned 1 = Off | 2 = SAT | 3 = SARH | 4 = OAT | 5 = OARH | 6 = Static Pressure | 7 = Fan Setpoint | 8 = Damper Feedback W

89 40090 AI3/BI3 input mode. Unsigned 1 = Off | 2 = SAT | 3 = OAT | 4 = Damper Feedback | 5 = Occupancy | 6 = Fan Speed Stage W

90 40091 AI4/BI4 input mode. Unsigned 1 = Off | 2 = SAT | 3 = OAT | 4 = Damper Feedback | 5 = Occupancy | 6 = Fan Speed Stage W

91 40092 AO1 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W

92 40093 AO2 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W

93 40094 BO1 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W

94 40095 BO2 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W

95 40096 Static pressure sensor range. Unsigned 1 = 250 Pa | 2 = 500 Pa | 3 = 1250 Pa W

96 40097 Analog input 1 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W

97 40098 Analog input 2 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W

98 40099 Analog output 1 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W

99 40100 Analog output 2 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W

100 40101 Control temperature source. Unsigned 1 = SAT | 2 = RAT W

101 40102 LCD screen top line value. Unsigned 1 = None | 2 = Time | 3 = CO2 | 4 = SARH | 5 = RARH W

102 40103 LCD screen displayed temperature. Unsigned 1 = Default | 2 = Alternate | 3 = SAT | 4 = TSTAT W

103 40104 LCD screen last reset reason. Unsigned 1 = No reason | 2 = Independent Watchdog | 3 = Window Watchdog | 4 = Software Reset | 5 = Power Down RO

Page 9 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — RO
9ページ · クリックして拡大
9ページ

B0 = Unblocking Damper Required B1 = SSOR1 Sens Not Detected B2 = SSOR2 Sens Not Required B3 = SAT Not Detected B4 = RAT Not Detected

B5 = Timeout Comm B6 = AI1 Reading Error B7 = AI2 Reading Error B8 to B31 = Reserved

104 40105 Alarm status. Bit String

RO

B0 = Thermal Cutout B1 = Comm Timeout B3 = Heater Temp Cutout B4 = SSR Temp Cutout B5 = Board Temp Cutout B6 = Duct Temp Cutout B7 = Heater Temp 1 Failure B8 = Heater Temp 2 Failure B9 = Board Temp Failure B10 = SSR Temp Failure

B11 = TRL Failure B13 = Invalid Config B14 = Fan Temp Failure B16 = External Temp Failure B17 = Supply Temp Failure B22 = Fan Feedback Error B30 = Air Flow Not Detected B31 = Heat Not Detected B2, B12, B15, B18 to B21, B23 to B29 = Reserved

105 40106 System alarm host. Bit String

RO

Page 10 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Notes
10ページ · クリックして拡大
10ページ

Notes

Page 11 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Notes
11ページ · クリックして拡大
11ページ
Page 11 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Notes
Page 12 of the neptronic Compact Make-up Air Unit (CMU-Modbus) user manual — Notes
12ページ · クリックして拡大
12ページ
neptronic Compact Make-up Air Unit (CMU-Modbus) — Notes diagram (page 12)
図 6 · Notes

400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll free in North America: 1-800-361-2308

Tel.: (514) 333-1433 Fax: (514) 333-3163 Customer service fax: (514) 333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)

情報源

参考資料・リンク

この取扱説明書で参照されているリンク(メーカー、サポート、ダウンロード等)。

neptronic Compact Make-up Air Unit (CMU-Modbus)について質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
neptronic Compact Make-up Air Unit (CMU-Modbus)に関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

neptronic Compact Make-up Air Unit (CMU-Modbus) 取扱説明書(PDF)

12 ページ·186 KB·生活家電·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…