Modbus Communication Module User Guide


CMU-Modbus Guide-211125


The Compact Make-up Air Unit Modbus Communication Module User Guide provides information for using Neptronic communication feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic Compact Make-up Air Unit devices. The Compact Make-up Air Unit Modbus Guide assumes that you are familiar with Modbus terminology. The following are the requirements for Modbus:
o As per protocol base (base 0); for PLC add 1 to protocol base.
o As per holding register (base 40001).
o Read Holding Registers (0x03)
o Write Single Register (0x06)
o Write Multiple Registers (0x10)
o Illegal data address
o Illegal data value
o Slave device busy
o The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
o The supported baud rates are 9600, 19200, 38400, 57600 and 76800 bps.
o The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
o In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
o If the device does not detect any activity for one second or more, it will find a silent line to prevent a possible baud rate scan on the next frame it detects.
o The device's unique address (1 to 247) that can be set through the device menu or through holding register index 0.

Glossary





60 40061 Temperature control proportional band. Unsigned
Unit: °C/°F, Range: 0.5°C to 20°C or 33°F to 68°F, Value x 100 (e.g. 5°C = 500 or 50°F = 5000) W
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W
61 40062 Temperature control integral time. Unsigned
62 40063 Temperature control derivate time. Unsigned
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W
63 40064 Static pressure control proportional band. Unsigned
Unit: Pascal (Pa), Range: 0 to 250 Pa Value x 1 (e.g. 3 Pa = 3) W
64 40065 Static pressure control integral time. Unsigned
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W
65 40066 Static pressure control derivate time. Unsigned
Unit: Seconds, Range: 0 to 255 seconds, Value x 1 (e.g. 100 secs = 100) W
66 40067 Control band. Unsigned
Unit: °C/°F, Range: 2°C to 10°C or 36°F to 50°F, Value x 100 (e.g. 5°C = 500 or 50°F = 5000) W
Unit: Seconds, Range: 15 to 1800 seconds, Value x 1 (e.g. 100 secs = 100) W
67 40068 Modbus timeout. Unsigned
68 40069 Number of synchronization timeouts. Unsigned
69 40070 No heat detection deadband. Unsigned
Unit: °C/°F, Range: 2°C to 8°C or 36°F to 46°F, Value x 100 (e.g. 5°C = 500 or 5°F = 500) W
70 40071 No heat detection delay. Unsigned
Unit: Seconds, Range: 30 to 240 seconds, Value x 1 (e.g. 100 secs = 100) W
71 40072 Exhaust fan state. Unsigned 0 = Off, 1 = On RO
72 40073 On/Off damper state. Unsigned 0 = Closed, 1 = Open RO
73 40074 On/Off damper feedback. Unsigned 0 = Closed, 1 = Open RO
74 40075 CMU fan enable. Unsigned 0 = No, 1 = Yes RO
75 40076 CMU heater stage 2 state. Unsigned 0 = Off, 1 = On RO
76 40077 Binary input 3 contact type. Unsigned 0 = NO, 1 = NC W
77 40078 Binary input 4 contact type. Unsigned 0 = NO, 1 = NC W
78 40079 Binary output 1 contact type. Unsigned 0 = NO, 1 = NC W
79 40080 Binary output 2 contact type. Unsigned 0 = NO, 1 = NC W

80 40081 Enable occupancy inputs. Unsigned 0 = No, 1 = Yes W
81 40082 Dry mode. Unsigned 0 = Disable, 1 = Enable W
82 40083 CO2 extract. Unsigned 0 = Disable, 1 = Enable W
83 40084 Static pressure loop. Unsigned 0 = Disable, 1 = Enable W
84 40085 Occupancy inactive mode. Unsigned 0 = Unoccupied, 1 = Off W
85 40086 CMU occupancy state. Unsigned 1 = Occupied | 2 = Unoccupied | 3 = Off W
86 40087 Temperature setpoint source. Unsigned 1 = On Board | 2 = TSTAT | 3 = Network W
87 40088 AI1 input mode. Unsigned 1 = Off | 2 = SAT | 3 = SARH | 4 = OAT | 5 = OARH | 6 = Static Pressure | 7 = Fan Setpoint | 8 = Damper Feedback W
88 40089 AI2 input mode. Unsigned 1 = Off | 2 = SAT | 3 = SARH | 4 = OAT | 5 = OARH | 6 = Static Pressure | 7 = Fan Setpoint | 8 = Damper Feedback W
89 40090 AI3/BI3 input mode. Unsigned 1 = Off | 2 = SAT | 3 = OAT | 4 = Damper Feedback | 5 = Occupancy | 6 = Fan Speed Stage W
90 40091 AI4/BI4 input mode. Unsigned 1 = Off | 2 = SAT | 3 = OAT | 4 = Damper Feedback | 5 = Occupancy | 6 = Fan Speed Stage W
91 40092 AO1 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
92 40093 AO2 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
93 40094 BO1 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
94 40095 BO2 output mode. Unsigned 1 = Off | 2 = Exhaust Fan | 3 = Damper W
95 40096 Static pressure sensor range. Unsigned 1 = 250 Pa | 2 = 500 Pa | 3 = 1250 Pa W
96 40097 Analog input 1 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
97 40098 Analog input 2 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
98 40099 Analog output 1 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
99 40100 Analog output 2 signal range. Unsigned 1 = 2-10Vdc | 2 = 0-10Vdc W
100 40101 Control temperature source. Unsigned 1 = SAT | 2 = RAT W
101 40102 LCD screen top line value. Unsigned 1 = None | 2 = Time | 3 = CO2 | 4 = SARH | 5 = RARH W
102 40103 LCD screen displayed temperature. Unsigned 1 = Default | 2 = Alternate | 3 = SAT | 4 = TSTAT W
103 40104 LCD screen last reset reason. Unsigned 1 = No reason | 2 = Independent Watchdog | 3 = Window Watchdog | 4 = Software Reset | 5 = Power Down RO

B0 = Unblocking Damper Required B1 = SSOR1 Sens Not Detected B2 = SSOR2 Sens Not Required B3 = SAT Not Detected B4 = RAT Not Detected
B5 = Timeout Comm B6 = AI1 Reading Error B7 = AI2 Reading Error B8 to B31 = Reserved
104 40105 Alarm status. Bit String
B0 = Thermal Cutout B1 = Comm Timeout B3 = Heater Temp Cutout B4 = SSR Temp Cutout B5 = Board Temp Cutout B6 = Duct Temp Cutout B7 = Heater Temp 1 Failure B8 = Heater Temp 2 Failure B9 = Board Temp Failure B10 = SSR Temp Failure
B11 = TRL Failure B13 = Invalid Config B14 = Fan Temp Failure B16 = External Temp Failure B17 = Supply Temp Failure B22 = Fan Feedback Error B30 = Air Flow Not Detected B31 = Heat Not Detected B2, B12, B15, B18 to B21, B23 to B29 = Reserved
105 40106 System alarm host. Bit String





400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll free in North America: 1-800-361-2308
Tel.: (514) 333-1433 Fax: (514) 333-3163 Customer service fax: (514) 333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)