FriedrichメーカーSH20L30-Aの使用説明書/サービス説明書
ページ先へ移動 of 20
SH15L30-A SH20L30-A SH20L50-A HG-SVC-PRTS-05 (4-05) Ser vic e & P ar ts Manual R oom Air Conditioners 50 & 60 Hz M ode ls 20 05.
2 TA B L E O F C O N T E N T S Specifi cations ............................................................................................................... .................... 3 Performance Data ...................................................
3 EV APORA TOR AIR TEMP . DEG. F EV APORA TOR TEMP . DEG. F CONDENSER TEMP . DEG. F Discharge Te m p Suction Te m p Liquid Te m p Super Heat Sub- Cooling OPERA TING PRESSURES ELECTRICAL RA TINGS R-22 REF . Evap CFM Motor RPM BREAKER FUSE Discharge Air Te m p .
4 COMPRESSOR WINDING TEST (Figure 2.) Remov e the co mpressor ter minal box cover and disconnect the wires from the ter minals. Using an ohmmet er , check c ontinuity across the following: COMPONENT OPERA TION AND TESTING COMPRESSORS Com pr ess ors ar e s ing le p has e , 2 08 /230 v ol t.
5 F AN MOTOR (Figure 4) A 230 volt single phase permanent spl it capacitor motor is used to dr ive the evaporator blower and c ondens er fan. A running capacitor is wired a cross the star t and run terminals of the motor . The motor is t otally enclosed and is prot ected with a line voltage ov erload loc ated int ernally of the motor .
6 RED DOT RUN CAP ACITOR FA N MOTOR COMPRESSOR FIGURE 7 RUN CAP ACITOR HOOK–UP CAP ACITOR, RUN A run capacitor is wired across the auxiliar y and main winding of a single ph ase permanent split capacitor motor s uch as the compressor and fan motors.
7 Note: The t emperature mu st be within the range li sted to check the th ermostat. Ref er to the trou bleshooti ng section in this manual for additional in formation on ther most at te sting. TEST Remo ve the wires from the th ermostat. T urn the thermostat to its coldest position.
8 LOW AMBIENT BYP ASS V AL VE (Figure 9) T h e H a z a r d G a r d u n i t i s d e s i g n e d t o o p e r a t e a t l o w outside ambient temperatures.
9 NOTE: This procedur e can be sped up by the use of heat lam ps, or by brea king the vacuum with refrigerant or dr y nitrogen at 5,00 0 microns. Pressure s ystem to 5 PSIG an d leav e in the sys- tem a minimum o f 1 0 minutes. R ecover refriger - ant, an d proceed with evacu ation to a pressu re of 200 mic rons or a minimum of 1 0 % .
10 NOTE: All inoperative compressors returned to Friedrich must have all lines properly plugged with the plugs from the replacement compressor . REFRIGERANT CHARGE 1 . The refrigerant charge is e xtremely c ritic al. Measure the charge carefully an d as e xactly as possible t o the namepl ate ch arge.
11 TROUBLESHOOTING PROBLEM POSSIBLE CAUSE TO CORRECT UNI T DOES N OT RUN. Power disconnected. Check power sourc e. System switch in “O f f ” position. Se t switch co rrec tly . Branch c ircuit fuse blown or circuit breaker tripped. Replace fuse, reset break er .
12 TROUBLESHOOTING (Co ntinu ed ) PROBLEM POSSIBLE CAUSE T O CORRECT COM PRESSO R AT T E M P T S T O ST ART , O R RUNS FO R S H O R T PERIOD S ONL Y . C Y CLES ON OV ER LOA D. Compress or attempts to st ar t before system pressures are equal ized . Allow a minimum of t wo ( 2) minutes to allow pressures to equalize before attempting to st ar t.
13 TROUBLESHOOTING (Co ntinu ed ) PROBLEM POSSIBLE CAUSE T O CORRECT FA N M O T O R D O E S NOT R UN. Defective switch (O n- Of f ) . Check c ontinuit y across ter minals 2 and 3. Fan c a p a c i t o r o p e n . Check by substituting a known good c apac itor of the same rating .
14 WIRING D IA GR AM MODELS SH 1 5L3 0 - A , SH20 L30 - A , SH20L5 0 - A.
15 HAZARDGARD CABINET P ARTS.
16 HAZARDGARD CHASSIS P ARTS.
17 HAZARDGARD P ARTS LIST REF DESCRIPTION P ART NO# MODELS CODE ELECTRICAL P ARTS SH15L30-A SH20L30-A SH20L50-A 1 COMPRESSOR 61 193549 1 600 1 COMPRESSOR 61 193550 1 600 1 COMPRESSOR 61 193565 1 600 2.
18 REF DESCRIPTION P ART NO# MODELS CODE CHASSIS P ARTS SH15L30-A SH20L30-A SH20L50-A 26 SHROUD, CONDENSER 61803601 17 2 0 26 SHROUD, CONDENSER 61804901 11 7 2 0 27 BRACE, COND.SHROUD 61802600 33 3 7 2 2 22 F AN BLADE, COND. 60542003 17 1 0 22 F AN BLADE, COND.
19.
HG-SVC-PRTS-05 (4-05) Use Factory Certifi ed Parts. FRIEDRICH AIR CONDITIONING CO. P ost Office Box 1540 · San Antonio, T exas 78295-1540 4200 N. P an Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4480 www .friedrich.
デバイスFriedrich SH20L30-Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Friedrich SH20L30-Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFriedrich SH20L30-Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Friedrich SH20L30-Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Friedrich SH20L30-Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Friedrich SH20L30-Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFriedrich SH20L30-Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Friedrich SH20L30-Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFriedrich SH20L30-Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。