Room Air Conditioner Ser vice and P ar ts Man ual Slider Casement SV08 / SV10 / SV12 (01/05) 115V olts • SV08A10A • SV10A10A • SV12A10A High Cool Med Fan Off Mode Temperature Med Cool Low Cool L.
—2— 1. PREF A CE 1.1 SAFETY PRECAUTIONS ................................2 1.2 INSULATION RESISTANCE TEST .................2 1.3 SPECIFICATIONS ...........................................3 1.4 FEATURES...............................................
—3— POWER SUPPLY COOLING CAPACITY (Btu/h) INPUT (W) RUNNING CURRENT (A) E.E.R (BTU/W . h) INDOOR (°C) OUTDOOR (°C) REFRIGERANT (R-22) CHARGE EVAPORATOR CONDENSER FAN, INDOOR FAN, OUTDOOR FAN SPEEDS, FAN/COOLING FAN MOTOR OPERATION CONTROL ROOM TEMP.
—4— 1.4 FEA TURES • Designed for COOLING ONLY. • Powerful and whispering cooling. • Simple installation and service. • Low air-intake, top cooled-air discharge. 1.5 CONTR OL LOCA TIONS 1.5.1 COOLING ONL Y MODEL • VENTILATION The ventilation lever must be in the CLOSE position in order to maintain the best cooling conditions.
— 5 — 2.1 MECHANICAL P AR TS 2.1.1 FRONT GRILLE 1. Open the inlet grille downward and remove the air filter. 2. Remove the screws which fasten the front grille.(See Figure 1) 3. Pull the front grille from the right side. 4. Remove the front grille.
— 6 — 2.2 AIR HANDLING P AR TS 2.2.1 AIR GUIDE AND TURBO F AN 1. Remove the front grille. (Refer to section 2.1.1) 2. Remove the cabinet. (Refer to section 2.1.2) 3. Remove the control box. (Refer to section 2.1.3) 4. Remove the 4 screws which fasten the brace.
— 7 — 2.2.3 SHROUD 1. Remove the fan. (Refer to section 2.2.2) 2. Remove the shroud. (See Figure 8) 3. Re-install the components by referring to the removal procedure, above. 2.3 ELECTRICAL P AR TS 2.3.1 O VERLO AD PRO TECT OR 1. Remove the cabinet.
— 8 — 2.3.3 CAP A CIT OR 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the screw and the clamp which fasten the capacitor. 3. Disconnect all the leads of capacitor terminals. 4. Re-install the components by referring to the removal procedure, above.
— 9 — 2.3.7 MO T OR 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the turbo fan. (Refer to section 2.2.1) 3. Remove the fan. (Refer to section 2.2.2) 4. Remove the 4 screws which fasten the motor from the Motor Mount. (See Figure 15) 5.
— 10 — — Replacement of the refrigerant. 1. When replacing the refrigerant, be sure to Discharge the refrigerant system using a Freon TM recovery System. If there is no valve to attach the recovery system to, install one (such as a WATCO A-1) before venting the Freon TM .
— 11 — Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pinch-off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
— 12 — 3. INST ALLA TION 3.1 HO W T O INST ALL THE UNIT 1. To avoid vibration and noise, make sure the unit is installed securely and firmly. 2. Install the unit where the sunlight does not shine directly on the unit. If the unit receives direct sunlight, build an awning to shade the cabinet.
— 13 — 3.4 WINDO W REQUIREMENTS 1. These instructions are for a horizontal sliding or a casement window. 2. The electrical outlet must be within reach of the power cord. For installation in a casement window, the window frame assembly and the side of the building must be adequate to support the weight of the air conditioner.
— 14 — 1. Loosely attach the support bracket to the bottom of bracket using bolts, washers, and nuts. Attach the leveling bolt and nut. (See Figure 22) 2. Remove protective backing from window track seal and apply seal to window track. (See Figure 23) 3.
— 15 — 8. Slide curtain into curtain frame. Slide curtain frame assembly into side guides of the air conditioner cabinet. Make sure curtain is firmly enclosed on all sides by the frame.
— 16 — 4. TR OUBLESHOO TING GUIDE 4.1 OUTSIDE DIMENSIONS 368(14 1 / 2 ) 521(20 1 / 2 ) 607(23 3 / 5 ) CAPILLARY TUBE COMPRESSOR TURBO F AN EV APORA TOR COIL CONDENSER COIL FA N MOTOR 4.2 PIPING SYSTEM Following is a brief description of the important components and their functions in the refrigeration system.
— 17 — 4.3 TR OUBLESHOO TING GUIDE In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and/or improper application.
— 18 — Fails to Start Check circuit break er and fuse. Gas leakage of f eeler bulb of ther mostat Check control s witch. F an only fails to start. Improper wiring. Def ectiv e of f an motor capacitor . Irregular motor resistance ( ). Irregular motor insulation ( ).
— 19 — COMPLAINT CAUSE REMEDY Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram for terminal identification.
— 20 — COMPLAINT CAUSE REMEDY Check the position of knob If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open. Check the capacitor. Replace if not within ±10% of manufacturers rating.
5. SCHEMA TIC DIA GRAM 5.1 CIRCUIT DIA GRAM ■ MODEL : SV10A10A / SV1210A — 21 — SV10A10A SV12A10A PART NO. 1 POWER CORD - - 1 S 2 ROTARY SWITCH 67300501 1 S 3 FAN MOTOR 67303015 1 S 4 CAPACITOR 67300709 - 1 S 5 THERMOSTAT 67300403 1 S 6 COMPRESSOR 67301614 67301615 1 S LOCATION NO.
— 22 — 5.2 CIRCUIT DIA GRAM ■ MODEL : SV08A10A SV08A10A PART NO. 1 POWER CORD 67300005 1 S 2 ROTARY SWITCH 67300501 1 S 3 FAN MOTOR 67303014 1 S 4 CAPACITOR 67300712 1 S 5 THERMOSTAT 67300403 1 S 6 COMPRESSOR 67301612 1 S LOCATION NO.
6. EXPLODED VIEW — 23 — 554030 148000 352390-2 349001 349600 346811 354210 152312 147581 145200 147582-2 135312 147582-1 135301 264110 269310 266003 249950 130910 359011 130410 552111 352113 35239.
— 24 — 7. REPLA CEMENT P AR TS LIST ■ MODEL : SV08A10A, SV10A10A, SV12A10A P/No SV08A10A SV10A10A SV12A10A 130410 BASE ASSEMBLY, SINGLE 67302911 67302910 R 130910 CABINET ASSEMBLY, SINGLE 673037.
— 25 — MEMO.
— 26 — MEMO.
Printed in the U.S.A Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4480 FRIEDRICH AIR CONDITIONING CO. Visit our web site at www.friedrich.com P/NO.: 3828A20190X SV08 / SV10 / SV12 (01/05) Use F actor y Cer tified P ar ts.
デバイスFriedrich SV12の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Friedrich SV12をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはFriedrich SV12の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Friedrich SV12の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Friedrich SV12で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Friedrich SV12を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はFriedrich SV12の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Friedrich SV12に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちFriedrich SV12デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。