Page 1 of 2 Direct/Indirect – 1' x 4' with Acrylic Linear Prismatic Lens




Exposed T-bar by o hers
Exposed T-bar by others
1-1/2" max.
Acoustical material by o hers
1-7/8" max.
Acoustical material by others
* For flush mounting when using 9/16" Exposed T-Grid ceiling system consult factory
exposed slot t-grid ceiling
1-9/16" x 2-13/16" Access Plate Wi h 2-7/8" dia. K O.



fully enclosed lamp compartment
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:

Page 2 of 2 Direct/Indirect – 1' x 4' with Acrylic Linear Prismatic Lens
Model No. H9S1GLR132UNVHI LER = FP - 86.4 IW - 21.3 BF - 0.88 Comparative yearly lighting ene gy cost per
Model No. H9S1GLR232UNVHI LER = FP - 75.1 IW - 50.3 BF - 0.88 Comparative yearly lighting ene gy cost per
1000 lumens = $2.78
1000 lumens = $3.19


Report Number: G2007129 Catalog Number: H9S1GLR132UNVHI Lamps: (1) F28 T8 Luminaire: HP90 1' x 4' with linear
0 693 693 693
0 1506 1506 1506
5 685 690 696 66
5 1488 1498 1509 143
prismatic lens. Ballast: QTP1X32T8-UNV-PSX-TC Report is based on 2725 Lumens per lamp. Efficiency: 76.7% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.4 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 47.040 11.040
15 657 674 689 191
prismatic lens. Ballast: QTP2X32T8/UNV-ISN-SC Report is based on 2725 Lumens per lamp. Efficiency: 78.8% CIE Type-Direct-Indirect Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.3 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 47.040 11.040
15 1427 1450 1474 410
25 603 639 673 295
25 1308 1355 1399 625
35 525 587 644 367
35 1135 1216 1294 762
45 425 520 591 396
45 918 1044 1139 800
55 310 430 468 365
55 672 834 885 720
65 192 289 271 260
65 421 558 557 523
75 88 130 105 124
75 197 266 229 259
85 18 24 22 27
85 41 45 43 52
90 3 3 3
90 7 4 4
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
ZONAL LUMEN SUMMARY
ZONAL LUMEN SUMMARY
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
ZONE LUMENS % LAMP % FIXT 0- 30 551 20 2 26.4 0- 40 919 33 7 44.0 0- 60 1679 61 6 80.4 0- 90 2090 76 7 100.0 90-180.0 0-180 2090 76 7 100.0
RC 80 50 30 RW 70 50 30 50 30 10 50 30 10
ZONE LUMENS % LAMP % FIXT 0- 30 1178 21 6 27.4 0- 40 1940 35 6 45 2 0- 60 3461 63 5 80 6 0- 90 4295 78 8 100 0 90-180-180 4295 78 8 100 0
1 84 80 77 75 73 70 72 70 68 2 76 70 65 66 62 58 63 60 57 3 69 61 55 58 53 49 56 51 48 4 63 54 47 51 46 41 49 45 41 5 58 48 41 46 40 36 44 39 35 6 54 43 36 41 35 31 40 35 31 7 50 39 32 37 32 27 36 31 27 8 46 36 29 34 28 24 33 28 24 9 43 33 26 31 26 22 30 25 22 10 40 30 24 29 24 20 28 23 20
1 86 82 79 77 75 72 74 72 70 2 78 72 67 68 63 60 65 62 59 3 71 63 57 59 54 50 57 53 49 4 65 56 49 53 47 43 51 46 42 5 60 50 43 47 41 37 46 41 37 6 55 45 38 43 37 32 41 36 32 7 51 41 34 39 33 29 38 32 28 8 48 37 30 35 30 25 34 29 25 9 45 34 28 33 27 23 32 27 23 10 42 31 25 30 25 21 29 24 21
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 1793. 2194. 2494. 55 1613. 2237. 2434. 65 1355. 2040. 1913. 75 1014. 1499. 1210. 85 616. 822. 753.
IN DEG. 0-DEG. 45-DEG. 90-DEG. 45 3873. 4405. 4806. 55 3496. 4338. 4604. 65 2972. 3939. 3932. 75 2271. 3066. 2640. 85 1404. 1540. 1472.
S
G
R
Body Style:
Ceiling Type:
Reflector:
Lamp Quantity 1=1 Lamp 2=2 Lamp
Fits both Standard Grid
Ballast Type:
HY For NYC Code – I B.E.W. Manufactured
HN For NYC Code – Local 3 Manufactu ed
Options/Accessories Fusing: Internal fast blow fusing: SUFFIX: GLR.
Specifications (continued) Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed. This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org
Internal slow blow fusing: SUFFIX: GMF. Drywall Kit: Order Catalog Number: FK91X4. Electrical Wiring Options: Consult factory. For motion or light sensor: See Folio OA20-10.
Specifications Performance: In an installation of 2 lamp 28W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .80. To reduce glare the average brightness at 65° shall not exceed 1913 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 73.6%. Materials: Chassis parts are die-formed code gauge steel. Lamp Shield: Linear prismatic translucent DR acrylic lens. Finish: Chassis exterior – baked white polyester enamel. Cavity – baked white polyester enamel. Rust preventative undercoating. Reflector – low irides- cence specular aluminum 95% reflectance.