INST ALLA TION INSTRUCTIONS ECONOMIZERS WITH EXHAUST MODELS EIFM-2B EIFM-3B For Use with Bard 1-1/2 thru 3 T on W all Mount Air Conditioners and Heat Pump s Manual : 2100-390 Supersedes: File: V olume III T ab 19 Date: 04-26-01 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914.
CONTENTS GENERAL General Information ................................................. 1 Unp acking ................................................................ 1 Description ............................................................... 1 INST ALLA TION Basic Installation .
Manual 2100-390 Page 1 GENERAL GENERAL INFORMATION The economizer should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the economizer package.
Manual 2100-390 Page 2 2. Remove and save the existing exterior blower access and service access panels on the Bard wall mount unit. (See Figure 1.) INST ALLA TION BASIC INSTALLATION 1.
Manual 2100-390 Page 3 4. Remove and discard the condenser partition blank off plate. (See Figure 2.) 3. RIGHT HAND UNITS Remove and save existing unit return air filter and left side filter support bracket. Remove and save top four (4) screws from grille.
Manual 2100-390 Page 4 5. FOR RIGHT HAND UNITS Install economizer by inserting the economizer into the unit to the far left side clearing the right filter bracket. Once the economizer is fully inserted, slide the economizer to the right until it is tight against the back of the control panel.
Manual 2100-390 Page 5 6. Mount mixed air thermistor to blower partition as shown with screws provided. Bracket with sensor installs on top of blower partition. Screws are inserted from the underside. Route wires as shown and secure with wire tie. Connect wires to thermistor.
Manual 2100-390 Page 6 FIGURE 5 TOP VIEW OF CONTROL PANEL MIS-350.
Manual 2100-390 Page 7 9. Connect lead with fork terminal to corresponding points on terminal strip. Re.: C.Y.G. (See wiring diagram.) 10. Wire nut leads with 5/8” stripped ends to Y1 and Y2 leads from thermostat. See wiring diagram in this manual or on economizer.
Manual 2100-390 Page 8 ECONOMIZER – WA, WL & WH SERIES FEATURES • One piece construction – easy to install with no mechanical linkage adjustment required. • Exhaust air damper – built in with positive closed position. Provides exhaust air capability to prevent pressurization of tight buildings.
Manual 2100-390 Page 9 CONDITION B – WARM OUTDOORS First stage cooling cycles and compressor and dampers remain in mechanical cooling mode. FIGURE 7 MECHANICAL COOLING OPERATION MIS-348.
Manual 2100-390 Page 10 FIGURE 8 ECONOMIZER OPERATION FOR SINGLE COMPRESSOR UNIT MIS-1351 WALL THERMOSTATS FOR HEAT PUMPS WITH ECONOMIZER Thermostat Part 8403-027 (White Rodgers IF92-71) Electronic Heat Pump Thermostat 2 Stage Cool / 3 Stage Heat FOR AIR CONDITIONING WITH ECONOMIZER Thermostat Part No.
Manual 2100-390 Page 11.
デバイスBard EIFM-2Bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bard EIFM-2Bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBard EIFM-2Bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bard EIFM-2Bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bard EIFM-2Bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bard EIFM-2Bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBard EIFM-2Bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bard EIFM-2Bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBard EIFM-2Bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。