AFFINITY™ SERIES
SINGLE PACKAGE HEAT PUMPS
BHP024 THRU 060 2 THRU 5 NOMINAL TONS 13 SEER
FACTORY MOUNTED TXV
DESCRIPTION
All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations, are used to insure product quality. Refrigerant charge, and component part numbers are verified via computers at manufacturing point. Vital run test statistics, such as, system pressure, motor currents, air velocity and temperature unit vibration are monitored and recorded by the system to insure unit performance.
York® Affinity™ Series packaged heat pumps are designed for outdoor installation. Only utility and duct connections are required at the point of installation.
Field-installed electric heater accessories are available to provide electric heat, if required.
Equal size, side supply and return duct connections allow easy hook-up of ducts to match low crawl spaces without transition pieces.
All units provide high operating efficiencies of 13 SEER, 3.3 COP or greater, and 7.7 HSPF. All efficiencies exceed leg- islated minimum levels.
Electrical utility knockouts are provided through the bottom, as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
All model sizes share a common, compact design cabinet with a single footprint. The installer has the flexibility of set- ting one curb or pad and placing the proper tonnage unit after the internal load has been determined. Field convert- ible duct connections, from side shot to down shot, allows the installer greater flexibility and the need to carry less inventory.
The bottom duct openings are covered when they leave the factory. They are ready for a side supply / side return appli- cation. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no acces- sory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.
Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof. Plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are under 500 pounds.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

TOP DISCHARGE
A non-corrosive, long-lasting, water-tight pan is posi- tioned below the evaporator coil to collect and drain all condensate; less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality).
The top discharge condenser fan does not disrupt neighboring areas and does not dry-out vegetation sur- rounding the unit. The warm air from the top mounted fan is blown up away from the structure and any land- scaping. This allows compact location on multi-unit applications.
OUTDOOR COIL GRILLE
The heavy duty, inch NPTI copper connection is more tolerable during installation and is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.
A multi-piece totally enclosed, rigidly mounted outdoor coil grille provides protection from objects and person- nel after installation. It also provides protection during transit and installation.
LOW OPERATING SOUND LEVEL
With a heavy duty cabinet made of powder-painted, galvanized steel, the neutral color blends into sur- rounding areas. The powered paint provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy earth tone finish insure less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish exceeds ASTM-B117 standards for 1000 hours salt spray rating, the highest in the industry.
The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil, muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound alterations with it's “Super-Structure” design. This design strategically places embossments in the pan for optimum strength and rigidity.
FAN SYSTEM
The easily removable base rails provide a solid founda- tion for the entire unit and protects the unit during ship- ment. The rails provide fork lift access from all sides. Rigging holes are, provided also so that an overhead crane can be used to place the unit on a roof. On appli- cations when the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applica- tions where height is limited, the 2-3/8 inch high base rails may be removed on location.
All models operate over a wide range of design condi- tions with an (E.C.M.) electronically commutated motor that automatically adjusts the blower speed to meet a wide range of static requirements. These units easily match all types of applications and provides greater on site flexibility to match comfort requirements.
A low voltage printed circuit board contains a low volt- age terminal strip. The electrical control box is not located in the compressor compartment. All wiring internal to the unit is color/number coded.
A single piece “Water Shed” top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabi- net panels have a non-fibrous insulation that reduces insulation fibers into conditioned area.
Reliable demand defrost control provides defrost. Defrost control also provides an “X” terminal to provide a 24 volt signal for room thermostat “LED” indication of unit lockout, plus, built in 5 minute anti-short cycle pro- tection.

rate field accessories of single enthalpy and dual enthalpy are also available.
The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compres- sor, if undesirable operating conditions occur.
Sensor replaces dry bulb sensor standard in econo- mizer kit. Provides improved economizer operation by sensing the dry bulb temperature from outdoors, plus the enthalpy content of the outdoor air.
Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum effi- ciency and durability.
Additional sensor to single enthalpy sensor. Sensor selects both the return air temperature dry bulb and humidity, in conjunction with the single enthalpy, to determine the most economical mix. Single Enthalpy sensor also required.
Long life, permanently lubricated condenser and evap- orator fan motor bearings, need no annual mainte- nance. Blower assembly can be easily cleaned by the unique “Slip Track” slide-out blower assembly.
Contains screw in type High pressure, Low Pressure/ Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing Schrader ports located in the unit by furnished adapt- ers. When abnormal conditions are sensed through the pressure switches, the unit will lock out, preventing any further operation until reset or problem is corrected. Package agency approved.
Protected, externally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system.
A large, single hinged panel covers the electrical con- trols and makes servicing easy. The blower compart- ment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assembly to slide-out for easy removal for mainte- nance and ease of trouble shooting.
Kit contains protected grilles made of expanded alumi- num grilles with full perimeter 1-1/2 inch frame. Sloped hoods are also included to assure maximum protec- tion.
FILTER / FRAME KIT (SINGLE PHASE ONLY)
The installer has no need to carry an inventory of unique parts or needs special training to replace any of the components parts for these units. All are easily obtained from Source 1 or other major part houses.
Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable standard size filters are shipped in one kit (1" filter is supplied). This kit is avail- able for single phase horizontal or vertical duct applica- tion only. Standard in all 3 Phase models.
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT
Designed for duct mounted side return and unit mounted down shot return applications. Damper capa- ble of providing 0% thru 50% of outdoor air (field sup- plied). Closes on power loss, includes hood and screen assembly.
Modulating integrated economizer provides simulta- neous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Sepa-

unit mounted down shot applications. Includes hood and screen assembly.
Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from 15" square to 14" round.
The units are designed to operate with 24-volt elec- tronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.
NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure a water tight seal. Eight and 14 inch high roof curbs are available.
Each heater package provides easy installation of elec- tric heat strips. Slide in design with plug in harness and agency approved. Heaters are available from 5.0 KW sizes and are designed for single point and dual con- nection.
Provides 0% thru 50% outdoor air capability (field adjustable). Designed for duct mounted side return and
Description ............................................................................1
Heating Capacities - 5 Ton (BHP060) ................................ 14
Standard Features / Benefits ................................................1
Side & Bottom Supply Air Blower Performance (208/230/460 Volt) ............................................................. 15
Field-installed Accessories ...................................................3
Unit Cut Away .......................................................................5
Additional Static Resistance .............................................. 15
Field Wiring Diagram ......................................................... 16
Ratings .................................................................................5
Electrical Data (Basic Unit) ................................................ 17
Physical Data ........................................................................5
Cooling Capacities - 2 Ton (BHP024) ..................................6
Electrical Data (13 Seer Heat Pump / Electric Heat) ......... 18
Application Data ................................................................. 19
Cooling Capacities - 2-1/2 Ton (BHP030) ............................7
Center Of Gravity And Weights .......................................... 19
Cooling Capacities - 3 Ton (BHP036) ..................................8
Cooling Capacities - 3-1/2 Ton (BHP042) ............................9
Unit Clearances ................................................................. 19
Unit Dimensions ................................................................. 20
Cooling Capacities - 4 Ton (BHP048) ................................10
Typical Applications ........................................................... 21
Cooling Capacities - 5 Ton (BHP060) ................................11
Heating Capacities - 2 Ton (BHP024) ................................12
Roof Curb Dimensions ....................................................... 22
Typical Wiring Diagram (208/230-1-60 Power Supply) ...... 23
Heating Capacities - 2-1/2 Ton (BHP030) ..........................12
Typical Wiring Diagram (230-3-60 Power Supply) ............. 24
Heating Capacities - 3 Ton (BHP036) ................................13
Heating Capacities - 3-1/2 Ton (BHP042) ..........................13
Typical Wiring Diagram (460/575-3-60 Power Supply) ...... 25
Mechanical Specifications .................................................. 26
Heating Capacities - 4 Ton (BHP048) ................................14
% + 3 $
$LU &RROHG
120,1$/ &22/,1* &$3$&,7< 0%+
)$&725< ,167$//(' (/(&75,& +($7
%78+

HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN INDOOR COIL
HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN OUTDOOR COIL
BACK AND BOTTOM RETURN AIR AND SUPPLY AIR DUCT OPENING
HIGH VOLTAGE TERMINAL BLOCK
LOW VOLTAGE TERMINAL BLOCK
ECM DIRECT DRIVE BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY
HEAVY GAUGE REMOVABLE BASE RAILS HIGH-EFFICIENCY COMPRESSOR RIGIDLY MOUNTED
TABLE 1: RATINGS
SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supple- mentary resistance (BTU’s per hour) divided by the total electric input (watts) x 3.412.









CAP 1
OUTDOOR AIR TEMPERATURE, °F (72% RH)
AIR °F
& KW
-10 0 10 20 30 40 50 60
KW 1.791 1.898 2.005 2.112 2.219 2.326 2.433 2.540
KW 2.198 2.305 2.412 2.519 2.626 2.733 2.840 2.947
KW 2.476 2.583 2.690 2.797 2.904 3.011 3.118 3.225
KW 1.825 1.932 2.039 2.146 2.253 2.360 2.467 2.574
KW 2.232 2.339 2.446 2.553 2.660 2.767 2.874 2.981
KW 2.510 2.617 2.724 2.831 2.938 3.045 3.152 3.259
KW 1.779 1.886 1.993 2.100 2.207 2.314 2.421 2.528
KW 2.186 2.293 2.400 2.507 2.614 2.721 2.828 2.935
KW 2.464 2.571 2.678 2.785 2.892 2.999 3.106 3.213
CAP 1
OUTDOOR AIR TEMPERATURE, °F (72% RH)
AIR °F
& KW
-10 0 10 20 30 40 50 60
KW 2.410 2.505 2.599 2.694 2.789 2.883 2.978 3.073
KW 2.835 2.930 3.024 3.119 3.214 3.308 3.403 3.498
KW 3.143 3.238 3.332 3.427 3.522 3.616 3.711 3.806
KW 2.419 2.514 2.608 2.703 2.798 2.892 2.987 3.082
KW 2.844 2.939 3.033 3.128 3.223 3.317 3.412 3.507
KW 3.152 3.247 3.341 3.436 3.531 3.625 3.720 3.815
KW 2.463 2.558 2.652 2.747 2.842 2.936 3.031 3.126
KW 2.888 2.983 3.077 3.172 3.267 3.361 3.456 3.551
KW 3.196 3.291 3.385 3.480 3.575 3.669 3.764 3.859

CAP 1
OUTDOOR AIR TEMPERATURE, °F (72% RH)
AIR °F
& KW
-10 0 10 20 30 40 50 60
KW 2.342 2.568 2.795 3.022 3.249 3.476 3.703 3.930
KW 2.726 2.952 3.179 3.406 3.633 3.860 4.087 4.314
KW 3.067 3.293 3.520 3.747 3.974 4.201 4.428 4.655
KW 2.408 2.634 2.861 3.088 3.315 3.542 3.769 3.996
KW 2.792 3.018 3.245 3.472 3.699 3.926 4.153 4.380
KW 3.133 3.359 3.586 3.813 4.040 4.267 4.494 4.721
KW 2.502 2.728 2.955 3.182 3.409 3.636 3.863 4.090
KW 2.886 3.112 3.339 3.566 3.793 4.020 4.247 4.474
KW 3.227 3.453 3.680 3.907 4.134 4.361 4.588 4.815
CAP 1
OUTDOOR AIR TEMPERATURE, °F (72% RH)
AIR °F
& KW
-10 0 10 20 30 40 50 60
KW 2.403 2.771 3.140 3.509 3.877 4.246 4.615 4.983
KW 2.967 3.335 3.704 4.073 4.441 4.810 5.179 5.547
KW 3.368 3.736 4.105 4.474 4.842 5.211 5.580 5.948
KW 2.411 2.779 3.148 3.517 3.885 4.254 4.623 4.991
KW 2.975 3.343 3.712 4.081 4.449 4.818 5.187 5.555
KW 3.376 3.744 4.113 4.482 4.850 5.219 5.588 5.956

MODEL NO.
UNIT AIRFLOW
BHP
SETTING
0.15 0.30 0.50 0.70 0.90
B1HP024 Cooling TB2-A, Heating TB2-A, Electric Heat 800 CFM 91 125 161 206 240
B1HP024 Cooling TB2-B, Heating TB2-B 900 CFM 118 148 199 243 285
B1HP030 Cooling TB2-A, Heating TB2-A, Electric Heat 1000 CFM 280 321 389 449 500
B1HP030 Cooling TB2-B, Heating TB2-B 1125 CFM 356 413 490 557 620
B1HP036 Cooling TB2-A, Heating TB2-A 1050 CFM 209 261 319 372 438
B1HP036 Cooling TB2-B, Heating TB2-B, Electric Heat 1200 CFM 273 324 392 480 541
B1HP042 Electric Heat 1225 CFM 306 341 412 494 577
B1HP042 Cooling TB2-A, Heating TB2-A 1300 CFM 338 395 470 551 640
B1HP042 Cooling TB2-B, Heating TB2-B 1400 CFM 393 466 544 642 734
B1HP048 Heating TB2-A 1400 CFM 377 427 504 597 683
B1HP048 Cooling TB2-A 1500 CFM 455 516 601 703 788
B1HP048 Cooling TB2-B, Heating TB2-B, Electric Heat 1600 CFM 530 608 707 800 873
B1HP060 Cooling TB2-A 1600 CFM 385 478 489 596 703
B1HP060 Heating TB2-A 1900 CFM 400 493 593 700 807
B1HP060 Cooling TB2-B 2000 CFM 590 717 833 940 1047
Resistance” table.
DESCRIPTION
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
Wet Indoor Coil 0.01 0.01 0.01 0.02 0.01 0.02 0.03 0.04 0.04 0.03 0.04 0.04 0.05 0.05 0.06 0.07
Economizer 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.08
Filter/Frame Kit 0.01 0.02 0.03 0.04 0.05 0.05 0.06 0.06 0.07
Electric Heat 0.02 0.03 0.03 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.01 0.11 0.11 0.12

** ** = Minimum wire size of 18 AWG wire should be used for all field
R
installed 24 volt wire.
G
Y Y
W
W2
24 VOLT TRANSFORMER
PROGRAMMABLE THERMOSTAT ONLY
W1
O O
* = Only required on units with supplemental electric heat.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. CAUTION:

*

Voltage Limitations1 Compressor OD Fan
Max. Fuse
Size (VA) Min. Max. RLA LRA
FLA
024 208/230-1-60 187 253 9.3 57.0 1.1 5.0 17.7 25 25 0.96 40
030 208/230-1-60 187 253 15.0 72.5 1.1 5.0 24.9 30 30 0.96 40 208/230-3-60 187 253 10.0 63.0 1.1 5.0 18.6 25 25 0.96 75 460-3-60 414 504 5.0 31.0 0.6 5.0 11.9 15 15 0.96 75
208/230-1-60 187 253 17.2 94.0 1.1 7.3 29.9 35 35 0.96 40 208/230-3-60 187 253 11.4 78.0 1.1 7.3 22.7 30 30 0.96 75 460-3-60 414 504 5.7 40.0 0.6 7.3 15.4 20 20 0.96 75 575-3-60 518 630 4.7 31 0.6 6.8 12.7 20 20 0.96 75
208/230-1-60 187 253 20.0 104.0 1.1 7.3 33.4 40 40 0.96 40 208/230-3-60 187 253 13.9 88.0 1.1 7.3 25.8 30 30 0.96 75 460-3-60 414 504 6.4 44.0 0.6 7.3 16.1 20 20 0.96 75 575-3-60 518 630 5.4 34 0.6 6.8 13.4 20 20 0.96 75
208/230-1-60 187 253 23.4 126.0 1.5 7.3 38.1 45 45 0.96 40 208/230-3-60 187 253 13.0 93.0 1.5 7.3 25.1 30 30 0.96 75 460-3-60 414 504 6.4 46.5 0.8 7.3 16.3 20 20 0.96 75 575-3-60 518 630 5.1 37.2 0.6 6.8 13.8 20 20 0.96 75
208/230-1-60 187 253 25 150 2.3 9.1 42.7 50 50 0.96 40 208/230-3-60 187 253 17.3 130 2.3 9.1 33.0 40 40 0.96 75 460-3-60 414 504 8.4 70 1.3 9.1 21.1 25 25 0.96 75 575-3-60 540 630 7 53 1.1 9.1 19 25 25 0.96 75
240 208 230 0.75 0.92
CORRECTION
FACTORS
480 460 0.92
600 575 0.92

Compressor Cond.
Max Fuse Size1
Size RLA LRA Model No. kW Total Amps
FLA
024 208/230-1-60 9.3 57.0 1.1 5.0 2NH04500506 3.8 / 5.0* 18.1 / 20.8 40.3 / 43.8 45 / 45 45 / 45 2NH04500706 5.6 / 7.5* 27.1 / 31.3 51.6 / 56.8 60 / 60 60 / 60 2NH04501006 7.5 / 10.0* 36.1 / 41.7 62.9 / 69.8 70 / 70 70 / 70
2NH04500506 3.8 / 5.0* 18.1 / 20.8 47.4 / 50.9 50 / 60 50 / 60 2NH04500706 5.6 / 7.5* 27.1 / 31.3 58.7 / 63.9 60 / 70 60 / 70 2NH04501006 7.5 / 10.0* 36.1 / 41.7 70.0 / 76.9 70 / 80 70 / 80 2NH04501506 11.3 / 15.0* 54.2 / 62.5 92.6 / 103.0 100 / 110 100 / 110
030 208/230-1-60 15.0 72.5 1.1 5.0
2NH04500506 3.8 / 5.0* 18.1 / 20.8 52.5 / 55.9 60 / 60 60 / 60 2NH04500706 5.6 / 7.5* 27.1 / 31.3 63.8 / 69.0 70 / 70 60 / 60 2NH04501006 7.5 / 10.0* 36.1 / 41.7 75.0 / 82.0 80 / 90 80 / 90 2NH04501506 11.3 / 15.0* 54.2 / 62.5 97.6 / 108.0 100 / 110 100 / 110
036 208/230-1-60 17.2 94.0 1.1 7.3
042 208/230-1-60 20.0 104.0 1.1 7.3 2NP04501006 7.5 / 10.0* 36.1 / 41.7 78.5 / 85.5 80 / 90 80 / 90 2NP04501506 11.3 / 15.0* 54.2 / 62.5 101.1 / 111.5 100 / 125 100 / 125
2NP04501006 7.5 / 10.0* 36.1 / 41.7 83.2 / 90.1 90 / 90 90 / 90 2NP04501506 11.3 / 15.0* 54.2 / 62.5 105.8 / 116.2 110 / 125 110 / 125 2NP04502006 15.0 / 20.0* 72.2 / 83.3 128.3 / 142.2 150 / 150 150 / 150 2NP04502506 18.8 / 25.0* 90.3 / 104.2 150.9 / 168.3 175 / 175 175 / 175
048 208/230-1-60 23.4 126.0 1.5 7.3
2NP04501006 7.5 / 10.0* 36.1 / 41.7 87.7 / 94.7 100 / 100 100 / 100 2NP04501506 11.3 / 15.0* 54.2 / 62.5 110.6 / 120.8 125 / 125 125 / 125 2NP04502006 15.0 / 20.0* 72.2 / 83.3 132.8 / 146.8 150 / 150 150 / 150 2NP04502506 18.8 / 25.0* 90.3 / 104.2 155.6 / 172.9 175 / 175 175 / 175
060 208/230-1-60 25 150 21.3 9.1
030 208/230-3-60 10.0 63.0 1.1 5.0 2NH04501025 7.5 / 10.0* 20.8 / 24.1 447 / 48.7 45 / 50 45 / 50 2NH04501525 11.3 / 15.0* 31.3 / 36.1 47.7 / 63.7 60 / 70 60 / 70
036 208/230-3-60 11.4 78.0 1.1 7.3 2NH04501025 7.5 / 10.0* 20.8 / 24.1 48.7 / 52.7 60 / 60 60 / 60 2NH04501525 11.3 / 15.0* 31.3 / 36.1 76.7 / 67.8 70 / 80 70 / 80
042 208/230-3-60 13.9 88.0 1.1 7.3 2NP04501025 7.5 / 10.0* 20.8 / 24.1 51.8 / 55.8 50 / 60 50 / 60 2NP04501525 11.3 / 15.0* 31.3 / 36.1 61.7 / 67.8 70 / 80 70 / 80
2NP04501025 7.5 / 10.0* 20.8 / 24.1 51.1 / 55.1 60 / 60 60 / 60 2NP04501525 11.3 / 15.0* 31.3 / 36.1 64.1 / 70.2 70 / 80 70 / 80 2NP04502025 15.0 / 20.0* 41.7 / 48.1 77.2 / 85.2 80 / 90 80 / 90 2NP04502525 18.8 / 25.0* 52.1 / 60.1 90.2 / 100.2 100 / 100 100 / 100
048 208/230-3-60 13.0 93.0 1.5 7.3
2NP04501025 7.5 / 10.0* 20.8 / 24.1 59.1 / 63.1 70 / 70 70 / 70 2NP04501525 11.3 / 15.0* 31.3 / 36.1 72.2 / 78.1 80 / 80 80 / 80 2NP04502025 15.0 / 20.0* 41.7 / 48.1 85.1 / 93.2 90 / 100 90 / 100 2NP04502525 18.8 / 25.0* 52.1 / 60.1 98.3 / 108.2 100 / 110 100 / 110
060 208/230-3-60 17.3 130 2.3 9.1
030 460-3-60 5.0 31.0 0.6 5.0 2NH04501046 10.0** 12.0 27.5 30 30 2NH04501546 15.0** 18.0 35.4 40 40
036 460-3-60 4.7 40.0 0.6 7.3 2NH04501046 10.0** 12.0 30.7 35 35 2NH04501546 15.0** 18.0 38.6 40 40
042 460-3-60 6.4 44.0 0.6 7.3 2NP04501046 10.0** 12.0 31.6 35 35 2NP04501546 15.0** 18.0 29.4 40 40
2NP04501046 10.0** 12.0 31.8 35 35 2NP04501546 15.0** 18.0 39.6 40 40 2NH04502046 10.0** 24.1 47.5 50 50 2NH04502546 25.0** 30.1 55.3 60 60
048 460-3-60 6.4 46.5 0.8 7.3
2NP04501046 10.0** 12.0 36.1 40 40 2NP04501546 15.0** 18.0 43.6 45 45 2NH04502046 10.0** 24.1 51.1 60 60 2NH04502546 25.0** 30.1 48.7 60 60
060 460-3-60 8.4 70 1.3 9.1
036 575-3-60 4.7 31 0.6 6.8 2NH04501058 10.0** 9.6 24.7 25 25 2NH04501558 15.0** 14.4 30.7 35 35
042 575-3-60 5.4 34 0.6 6.8 2NP04501058 10.0** 9.6 25.4 30 30 2NP04501558 15.0** 14.4 31.4 35 35
2NP04501058 10.0** 9.6 25.8 30 30 2NP04501558 15.0** 14.4 31.8 35 35 2NH04502058 10.0** 19.2 37.8 40 40 2NH04502558 25.0** 24.1 43.8 45 45
048 575-3-60 5.1 37 0.6 6.8
2NP04501058 10.0*** 9.6 31.0 35 35 2NP04501558 15.0*** 14.4 37.0 40 40 2NH04502058 20.0*** 19.2 43.0 45 45 2NH04502558 25.0*** 24.1 49.0 50 50
060 575-3-60 7 53 1.1 9.1
* KW listed is for 240 volts, use Table 17 for 208 or 230 volts. ** KW listed is for 480 volts, use Table 17 for 460 volts. *** KW listed is for 600 volts, use Table 17 for 575 volts.

024 030 036 042 048 060
COOLING 800 1000 1050 1300 1500 1500
(CFM)
HEATING 800 1000 1050 1400 1400 1500
MAXIMUM AIR FLOW
COOLING 900 1125 1200 1400 1600 2050
(CFM)
HEATING 900 1125 1200 1500 1600 2050
MINIMUM OPERATING TEMPERATURE IN COOLING MODE
(AMBIENT, °F) 45
(RETURN AIR, DB °F/WB °F) 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57
(RETURN AIR, °F) 55
D
B1HP
CORNER WEIGHTS
SHIPPING
OPERATING
FRONT
UNIT SIZE
WEIGHT
WEIGHT
A B C D
OF UNIT
024 356 351 97 93 81 84
030 353 348 96 93 81 84
49-1/8 26 23-1/2 47-1/4
036 388 383 106 102 89 92
042 440 435 120 115 101 104
048 485 480 132 127 111 115
060 495 490 135 130 113 117
(MINIMUM) Front 12” Back 0” Left Side (Filter Access) 24” Right Side 24”
36” (For Condenser Air Discharge)
MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1/2 INCH BETWEEN COMBUSTIBLE ROOF CURB MATERIAL AND THE SUPPLY DUCT.

81,7 6,=( ',0(16,21 ³$´
24
$OO GLPHQVLRQV DUH LQ LQFKHV 7KH\ DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH &HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW
%$&.











Units shall be factory-assembled, single packaged, Heat Pumps, designed for outdoor mounted installa- tion. Units shall have minimum SEER ratings of 13.0. They shall have built in, equal size, field convertible duct connections for down discharge supply/return or horizontal discharge supply/return.
The units shall be factory wired, piped, charged with R- 22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded.
All units shall be manufactured in a facility certified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be classified to UL 1995/CAN/CSA No. 236-M90 conditions.

B. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally iso- lated on a dedicated, independent mounting.
room thermostat “LED” indication of unit lockout. Plus a built in 5 minute anti-short cycle protection.
D. Unit shall have large, easily removable panels, cov- ering electrical controls and compressor, allowing easy access for any maintenance or servicing.
A. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally-enhanced copper tubes with all joints brazed.
B. Evaporator and Condenser coils shall be of the direct expansion, draw-thru design.
A. Independent thermal expansion devices (TXV).
B. Solid-core filter dryer to eliminate any foreign matter.
C. Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge and without disrupting condenser or evaporator air flow.
D. The refrigeration system shall provide at least 10° F of liquid sub-cooling at design conditions.
E. Unit shall have a suction line accumulator and auto- matic reversing valve.
A. Unit shall contain a large, low voltage Terminal Board for easy connection of field low voltage wir- ing.
B. Controls shall be mounted in a large control box with tilt-out, hinged access door, allowing easy access for trouble shooting and maintenance without affect- ing the normal system operation pressures.
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bot- tom entry. This will minimize roof penetrations and avoid unit field modifications. Separate side and bot- tom openings shall be provided for the control wiring.
C. Unit shall contain a reliable demand defrost control to provide defrost. The defrost control shall also have an “X” terminal to provide a 24 volt signal for


ISO 9001 Certified Quality Management System
Subject to change without notice. Printed in U.S.A. 036-21528-007-A-1205 Copyright © by Unitary Products Group 2005. All rights reserved. Supersedes: 036-21528-006-A-1005 Unitary 5005 Norman Products York OK Group Drive 73069