AFFINITY™ SERIES

SINGLE PACKAGE HEAT PUMPS

BHP024 THRU 060 2 THRU 5 NOMINAL TONS 13 SEER

FACTORY MOUNTED TXV

DESCRIPTION

All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations, are used to insure product quality. Refrigerant charge, and component part numbers are verified via computers at manufacturing point. Vital run test statistics, such as, system pressure, motor currents, air velocity and temperature unit vibration are monitored and recorded by the system to insure unit performance.

York® Affinity™ Series packaged heat pumps are designed for outdoor installation. Only utility and duct connections are required at the point of installation.

Field-installed electric heater accessories are available to provide electric heat, if required.

STANDARD FEATURES / BENEFITS

Equal size, side supply and return duct connections allow easy hook-up of ducts to match low crawl spaces without transition pieces.

OPERATING EFFICIENCY

All units provide high operating efficiencies of 13 SEER, 3.3 COP or greater, and 7.7 HSPF. All efficiencies exceed leg- islated minimum levels.

UTILITY CONNECTIONS MADE EASY

Electrical utility knockouts are provided through the bottom, as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.

ON SITE FLEXIBILITY

All model sizes share a common, compact design cabinet with a single footprint. The installer has the flexibility of set- ting one curb or pad and placing the proper tonnage unit after the internal load has been determined. Field convert- ible duct connections, from side shot to down shot, allows the installer greater flexibility and the need to carry less inventory.

CONVERTIBLE AIRFLOW DESIGN

The bottom duct openings are covered when they leave the factory. They are ready for a side supply / side return appli- cation. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no acces- sory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.

LOWER INSTALLATION COST

Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof. Plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are under 500 pounds.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 2 of the York BHP024 user manual — CONTROLS
2ページ · クリックして拡大
2ページ

CONDENSATE PAN

TOP DISCHARGE

A non-corrosive, long-lasting, water-tight pan is posi- tioned below the evaporator coil to collect and drain all condensate; less collection of stagnate condensate will build-up. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality).

The top discharge condenser fan does not disrupt neighboring areas and does not dry-out vegetation sur- rounding the unit. The warm air from the top mounted fan is blown up away from the structure and any land- scaping. This allows compact location on multi-unit applications.

CONDENSATE DRAIN

OUTDOOR COIL GRILLE

The heavy duty, inch NPTI copper connection is more tolerable during installation and is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.

A multi-piece totally enclosed, rigidly mounted outdoor coil grille provides protection from objects and person- nel after installation. It also provides protection during transit and installation.

DURABLE FINISH

LOW OPERATING SOUND LEVEL

With a heavy duty cabinet made of powder-painted, galvanized steel, the neutral color blends into sur- rounding areas. The powered paint provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy earth tone finish insure less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish exceeds ASTM-B117 standards for 1000 hours salt spray rating, the highest in the industry.

The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil, muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound alterations with it's “Super-Structure” design. This design strategically places embossments in the pan for optimum strength and rigidity.

FULL PERIMETER BASE RAILS

FAN SYSTEM

The easily removable base rails provide a solid founda- tion for the entire unit and protects the unit during ship- ment. The rails provide fork lift access from all sides. Rigging holes are, provided also so that an overhead crane can be used to place the unit on a roof. On appli- cations when the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applica- tions where height is limited, the 2-3/8 inch high base rails may be removed on location.

All models operate over a wide range of design condi- tions with an (E.C.M.) electronically commutated motor that automatically adjusts the blower speed to meet a wide range of static requirements. These units easily match all types of applications and provides greater on site flexibility to match comfort requirements.

SIMPLE CONTROL CIRCUIT

A low voltage printed circuit board contains a low volt- age terminal strip. The electrical control box is not located in the compressor compartment. All wiring internal to the unit is color/number coded.

MORE ATTRACTIVE APPEARANCE

A single piece “Water Shed” top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabi- net panels have a non-fibrous insulation that reduces insulation fibers into conditioned area.

CONTROLS

Reliable demand defrost control provides defrost. Defrost control also provides an “X” terminal to provide a 24 volt signal for room thermostat “LED” indication of unit lockout, plus, built in 5 minute anti-short cycle pro- tection.

Page 3 of the York BHP024 user manual — MOTORIZED FRESH AIR DAMPER
3ページ · クリックして拡大
3ページ

PROTECTED COMPRESSOR

rate field accessories of single enthalpy and dual enthalpy are also available.

The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compres- sor, if undesirable operating conditions occur.

SINGLE ENTHALPY SENSOR

Sensor replaces dry bulb sensor standard in econo- mizer kit. Provides improved economizer operation by sensing the dry bulb temperature from outdoors, plus the enthalpy content of the outdoor air.

EXCLUSIVE COIL DESIGN

Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum effi- ciency and durability.

DUAL ENTHALPY SENSOR

Additional sensor to single enthalpy sensor. Sensor selects both the return air temperature dry bulb and humidity, in conjunction with the single enthalpy, to determine the most economical mix. Single Enthalpy sensor also required.

LOW MAINTENANCE

Long life, permanently lubricated condenser and evap- orator fan motor bearings, need no annual mainte- nance. Blower assembly can be easily cleaned by the unique “Slip Track” slide-out blower assembly.

UPGRADE PRESSURE PACKAGE

Contains screw in type High pressure, Low Pressure/ Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing Schrader ports located in the unit by furnished adapt- ers. When abnormal conditions are sensed through the pressure switches, the unit will lock out, preventing any further operation until reset or problem is corrected. Package agency approved.

SECURED SERVICE ACCESS PORTS

Protected, externally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system.

EASY SERVICE ACCESS

A large, single hinged panel covers the electrical con- trols and makes servicing easy. The blower compart- ment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assembly to slide-out for easy removal for mainte- nance and ease of trouble shooting.

HAIL GUARD KIT

Kit contains protected grilles made of expanded alumi- num grilles with full perimeter 1-1/2 inch frame. Sloped hoods are also included to assure maximum protec- tion.

REPLACEMENT PARTS

FILTER / FRAME KIT (SINGLE PHASE ONLY)

The installer has no need to carry an inventory of unique parts or needs special training to replace any of the components parts for these units. All are easily obtained from Source 1 or other major part houses.

Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable standard size filters are shipped in one kit (1" filter is supplied). This kit is avail- able for single phase horizontal or vertical duct applica- tion only. Standard in all 3 Phase models.

FIELD-INSTALLED ACCESSORIES

MOTORIZED FRESH AIR DAMPER

ECONOMIZER DOWN DISCHARGE / SUPPLY KIT

Designed for duct mounted side return and unit mounted down shot return applications. Damper capa- ble of providing 0% thru 50% of outdoor air (field sup- plied). Closes on power loss, includes hood and screen assembly.

Modulating integrated economizer provides simulta- neous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Sepa-

Page 4 of the York BHP024 user manual — $ 1R (OHFWULF +HDW ,QVWDOOHG
4ページ · クリックして拡大
4ページ

RECTANGLE TO ROUND ADAPTERS

unit mounted down shot applications. Includes hood and screen assembly.

Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from 15" square to 14" round.

WALL THERMOSTAT

The units are designed to operate with 24-volt elec- tronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.

ROOF CURBS

NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure a water tight seal. Eight and 14 inch high roof curbs are available.

ELECTRIC HEATERS

Each heater package provides easy installation of elec- tric heat strips. Slide in design with plug in harness and agency approved. Heaters are available from 5.0 KW sizes and are designed for single point and dual con- nection.

MANUAL OUTDOOR DAMPER

Provides 0% thru 50% outdoor air capability (field adjustable). Designed for duct mounted side return and

TABLE OF CONTENTS

Description ............................................................................1

Heating Capacities - 5 Ton (BHP060) ................................ 14

Standard Features / Benefits ................................................1

Side & Bottom Supply Air Blower Performance (208/230/460 Volt) ............................................................. 15

Field-installed Accessories ...................................................3

Unit Cut Away .......................................................................5

Additional Static Resistance .............................................. 15

Field Wiring Diagram ......................................................... 16

Ratings .................................................................................5

Electrical Data (Basic Unit) ................................................ 17

Physical Data ........................................................................5

Cooling Capacities - 2 Ton (BHP024) ..................................6

Electrical Data (13 Seer Heat Pump / Electric Heat) ......... 18

Application Data ................................................................. 19

Cooling Capacities - 2-1/2 Ton (BHP030) ............................7

Center Of Gravity And Weights .......................................... 19

Cooling Capacities - 3 Ton (BHP036) ..................................8

Cooling Capacities - 3-1/2 Ton (BHP042) ............................9

Unit Clearances ................................................................. 19

Unit Dimensions ................................................................. 20

Cooling Capacities - 4 Ton (BHP048) ................................10

Typical Applications ........................................................... 21

Cooling Capacities - 5 Ton (BHP060) ................................11

Heating Capacities - 2 Ton (BHP024) ................................12

Roof Curb Dimensions ....................................................... 22

Typical Wiring Diagram (208/230-1-60 Power Supply) ...... 23

Heating Capacities - 2-1/2 Ton (BHP030) ..........................12

Typical Wiring Diagram (230-3-60 Power Supply) ............. 24

Heating Capacities - 3 Ton (BHP036) ................................13

Heating Capacities - 3-1/2 Ton (BHP042) ..........................13

Typical Wiring Diagram (460/575-3-60 Power Supply) ...... 25

Mechanical Specifications .................................................. 26

Heating Capacities - 4 Ton (BHP048) ................................14

% + 3 $

352'8&7 &$7(*25< % 6LQJOH 3DFNDJH +HDW 3XPSV

$LU &RROHG

1(: RU &XUUHQW 'HVLJQ

120,1$/ &22/,1* &$3$&,7< 0%+

)$&725< ,167$//(' (/(&75,& +($7

+3 +HDW 3XPS 6((5

%78+

$ 1R (OHFWULF +HDW ,QVWDOOHG

Show 5 more labels / short text on this page
352'8&7 120(1&/$785( · 92/7$*( &2'( · 352'8&7 *(1(5$7,21 · · 352'8&7 ,'(17,),(5
Page 5 of the York BHP024 user manual — TABLE 2: PHYSICAL DATA
5ページ · クリックして拡大
5ページ

DIRECT DRIVE CONDENSER FAN MOTOR

HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN INDOOR COIL

HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN OUTDOOR COIL

BACK AND BOTTOM RETURN AIR AND SUPPLY AIR DUCT OPENING

DECORATIVE PROTECTIVE COIL GUARD

HIGH VOLTAGE TERMINAL BLOCK

LOW VOLTAGE TERMINAL BLOCK

ECM DIRECT DRIVE BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY

LONG-LASTING POWDER PAINT FINISH

HEAVY GAUGE REMOVABLE BASE RAILS HIGH-EFFICIENCY COMPRESSOR RIGIDLY MOUNTED

FIGURE 1 - UNIT CUT AWAY

TABLE 1: RATINGS

MODEL BHPCOOLING CAPACITY1 80 / 67-95°FHSPF1SOUND RATING2 (dbels)NET HEATING CAPACITYAVAILABLE ELECTRIC HEAT NOMINAL CAPACITY KW @47°F@17°F MBHSEEREERMBH COPMBH COPSINGLE PHASETHREE PHASE 02424.413.011.37.77921.8 3.4011.0 2.005.0, 7.5, 10.0N / A 03030.013.011.37.77728.2 3.4016.5 2.205.0, 7.5, 10.0, 15.010.0, 15.0 03635.013.011.37.77732.0 3.3018.9 2.205.0, 7.5, 10.0, 15.010.0, 15.0 04242.013.011.37.78342.0 3.4023.0 2.2010.0, 15.010.0, 15.0 04847.013.011.37.78245.0 3.3025.8 2.2010.0, 15.0, 20.0, 25.010.0, 15.0, 20.0, 25.0 06055.013.011.27.78356.5 3.3033.2 2.1510.0, 15.0, 20.0, 25.010.0, 15.0, 20.0, 25.0
1. Certified in accordance with the Uniary Small Equipment certification program, which is based on ARI Standard 210/240. 2. Rated in accordance with ARI Standard 270.

SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

COP = Coefficient of Performance - the total heating capacity provided by the refrigeration system, including circulating fan heat but excluding supple- mentary resistance (BTU’s per hour) divided by the total electric input (watts) x 3.412.

TABLE 2: PHYSICAL DATA

MODELSBHP 024030036042048060 INDOOR BLOWERCENTRIFUGAL BLOWER (Dia. x Wd. in.) FAN MOTOR HP (ECM)10 X 8 1/210 X 8 1/211 x 10 3/411 x 10 3/411 X 10 3/411 X 10 1 INDOOR COILROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.)2 15 4.383 13 4.383 15 4.383 16 5.633 16 5.633 16 5.63 OUTDOOR FANPROPELLER DIA. (in.) FAN MOTOR HP NOM. CFM TOTAL22 1/4 1,80022 1/4 1,80022 1/4 2,40022 1/4 2,40022 1/4 3,00022 1/2 3,000 OUTDOOR COILROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.)1 20 11.71 20 11.72 20 11.72 20 16.42 20 16.42 20 16.4 CHARGEREFRIGERANT 22 (lbs./oz.)5 / 55 / 158 / 89 / 1412 / 010 / 4 FILTERFACE AREA (Sq. Ft. / Qty. / Size)4.28 / 2 / 14 x 22 COMPRESSORHermetic Type, Qty. = 1ReciprocatingScrollScrollScrollScrollScroll
Page 6 of the York BHP024 user manual — ALL SENSIBLE CAPACITY
6ページ · クリックして拡大
6ページ

TABLE 3: COOLING CAPACITIES - 2 TON (BHP024)

TEMPERATURE AIR ON OUTDOOR COILTEMPERATURE OF AIR ON INDOOR COIL 800 CFM900 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH29.126.023.823.429.726.624.323.9 POWER INPUT kW1.931.911.881.871.951.931.911.90 Sensible Capacity MBH1Entering Dry Bulb °F8619.223.123.823.420.925.124.323.9 8316.920.823.823.418.322.524.323.9 8014.518.521.922.715.619.823.423.6 7712.216.119.520.312.917.220.720.9 749.913.817.218.010.314.518.018.2 71#N/A11.514.915.7#N/A11.915.415.6 68#N/A9.112.513.3#N/A9.212.712.9 95 °FNET CAP. MBH27.224.222.122.027.724.622.522.4 POWER INPUT kW2.072.062.022.022.092.082.052.04 Sensible Capacity MBH1Entering Dry Bulb °F8618.622.322.122.020.123.722.522.4 8316.220.022.122.017.521.522.522.4 8013.917.720.821.414.818.921.822.1 7711.615.318.419.012.216.219.219.4 749.213.016.116.79.513.516.516.8 71#N/A10.713.814.4#N/A10.913.814.1 68#N/A8.311.412.0#N/A8.211.211.5 105 °FNET CAP. MBH23.822.420.520.624.222.820.820.9 POWER INPUT kW2.202.212.172.162.242.242.202.19 Sensible Capacity MBH1Entering Dry Bulb °F8619.521.520.520.620.422.320.820.9 8317.219.220.520.618.520.720.820.9 8014.916.919.720.015.918.120.420.6 7712.614.617.417.713.315.417.818.0 7410.212.215.115.310.612.715.115.3 71#N/A9.912.713.0#N/A10.112.412.6 68#N/A7.610.410.7#N/A7.49.810.0 115 °FNET CAP. MBH20.420.718.919.220.620.919.119.4 POWER INPUT kW2.342.362.322.312.382.402.362.35 Sensible Capacity MBH1Entering Dry Bulb °F8620.420.718.919.220.620.919.119.4 8318.218.518.919.219.519.819.119.4 8015.916.118.718.617.017.319.019.1 7713.613.816.416.314.414.616.416.5 7411.211.514.114.011.711.913.713.8 71#N/A9.111.711.6#N/A9.311.111.2 68#N/A6.89.49.3#N/A6.68.48.5 125 °FNET CAP. MBH17.018.917.317.817.019.017.517.9 POWER INPUT kW2.472.512.462.452.522.562.512.50 Sensible Capacity MBH1Entering Dry Bulb °F8621.319.917.317.820.819.517.517.9 8319.217.717.317.820.618.917.517.9 8016.915.417.717.318.116.517.617.7 7714.613.015.415.015.413.815.015.0 7412.210.713.112.612.811.112.312.3 71#N/A8.410.710.3#N/A8.59.79.7 68#N/A6.08.48.0#N/A5.87.07.0
1. These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Page 7 of the York BHP024 user manual — ALL SENSIBLE CAPACITY
7ページ · クリックして拡大
7ページ

TABLE 4: COOLING CAPACITIES - 2-1/2 TON (BHP030)

TEMPERATURE AIR ON OUTDOOR COILTEMPERATURE OF AIR ON INDOOR COIL 1000 CFM1125 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH34.131.528.429.935.432.729.531.0 POWER INPUT kW2.522.482.442.432.642.582.542.53 Sensible Capacity MBH1Entering Dry Bulb °F8623.929.828.429.925.731.829.531.0 8321.026.928.429.922.428.529.531.0 8018.123.927.929.619.025.229.230.8 7715.221.024.926.615.721.925.927.5 7412.318.122.023.712.418.522.624.2 71#N/A15.219.120.8#N/A15.219.220.9 68#N/A12.316.217.9#N/A11.915.917.5 95 °FNET CAP. MBH32.629.426.828.933.730.427.729.8 POWER INPUT kW2.832.812.712.702.932.912.812.79 Sensible Capacity MBH1Entering Dry Bulb °F8622.828.226.828.925.029.727.729.8 8319.925.326.828.921.727.527.729.8 8017.022.426.628.318.324.227.529.5 7714.119.523.625.415.020.824.226.2 7411.116.520.722.511.717.520.922.9 71#N/A13.617.819.6#N/A14.217.619.6 68#N/A10.714.916.7#N/A10.914.316.2 105 °FNET CAP. MBH30.327.225.026.731.528.226.027.7 POWER INPUT kW3.143.123.043.063.243.223.143.16 Sensible Capacity MBH1Entering Dry Bulb °F8621.726.625.026.723.927.926.027.7 8318.824.125.026.720.626.326.027.7 8015.921.125.426.317.222.926.227.5 7713.018.222.423.313.919.622.924.2 7410.115.319.520.410.616.319.620.9 71#N/A12.416.617.5#N/A13.016.217.6 68#N/A9.513.714.6#N/A9.712.914.2 115 °FNET CAP. MBH28.024.923.224.429.326.124.425.6 POWER INPUT kW3.453.433.373.423.563.543.483.53 Sensible Capacity MBH1Entering Dry Bulb °F8620.724.923.224.422.826.124.425.6 8317.722.823.224.419.525.024.425.6 8014.819.924.224.216.221.724.825.5 7711.917.021.321.312.818.421.522.2 749.014.118.318.49.515.118.218.9 71#N/A11.215.415.4#N/A11.814.915.5 68#N/A8.312.512.5#N/A8.411.612.2 125 °FNET CAP. MBH25.622.721.422.227.224.022.723.5 POWER INPUT kW3.763.743.703.783.873.853.823.89 Sensible Capacity MBH1Entering Dry Bulb °F8619.623.321.422.221.724.322.723.5 8316.721.621.422.218.423.822.723.5 8013.718.723.022.115.120.523.523.5 7710.815.820.119.211.717.220.220.2 747.912.917.116.38.413.916.816.8 71#N/A10.014.213.4#N/A10.513.513.5 68#N/A7.111.310.4#N/A7.210.210.2
1. These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Page 8 of the York BHP024 user manual — ALL SENSIBLE CAPACITY
8ページ · クリックして拡大
8ページ

TABLE 5: COOLING CAPACITIES - 3 TON (BHP036)

TEMPERATURE AIR ON OUTDOOR COILTEMPERATURE OF AIR ON INDOOR COIL 1050 CFM1200 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH41.137.534.534.342.438.635.535.3 POWER INPUT kW2.892.812.732.733.002.912.832.82 Sensible Capacity MBH1Entering Dry Bulb °F8625.632.334.534.328.235.535.535.3 8322.529.333.533.624.732.035.535.3 8019.526.331.732.221.228.534.535.0 7716.523.228.729.117.725.031.031.5 7413.420.225.726.114.221.627.528.0 71#N/A17.222.623.1#N/A18.124.024.5 68#N/A14.119.620.0#N/A14.620.521.0 95 °FNET CAP. MBH38.534.932.532.639.435.833.333.4 POWER INPUT kW3.213.153.053.063.313.253.153.16 Sensible Capacity MBH1Entering Dry Bulb °F8625.030.932.532.627.533.933.333.4 8322.027.931.932.024.030.433.333.4 8019.024.830.530.620.526.933.033.1 7715.921.827.527.517.023.429.529.6 7412.918.824.424.513.519.926.026.1 71#N/A15.721.421.5#N/A16.422.522.6 68#N/A12.718.418.5#N/A12.919.019.1 105 °FNET CAP. MBH35.632.129.530.436.432.830.231.1 POWER INPUT kW3.613.523.443.453.703.613.533.54 Sensible Capacity MBH1Entering Dry Bulb °F8623.929.429.530.426.231.930.231.1 8320.926.629.230.022.728.930.231.1 8017.923.627.828.619.225.430.030.8 7714.820.524.825.515.721.926.527.3 7411.817.521.822.512.218.423.023.8 71#N/A14.518.719.5#N/A14.919.520.3 68#N/A11.415.716.4#N/A11.416.016.8 115 °FNET CAP. MBH32.629.326.528.233.329.927.028.8 POWER INPUT kW4.013.883.833.844.103.973.913.92 Sensible Capacity MBH1Entering Dry Bulb °F8622.827.826.528.225.029.927.028.8 8319.825.326.528.021.527.427.028.8 8016.822.325.226.518.023.927.028.5 7713.719.222.223.514.520.423.525.0 7410.716.219.120.511.016.920.021.5 71#N/A13.216.117.4#N/A13.416.518.0 68#N/A10.113.114.4#N/A9.913.014.5 125 °FNET CAP. MBH29.726.423.526.030.226.923.926.4 POWER INPUT kW4.414.254.214.224.494.334.294.30 Sensible Capacity MBH1Entering Dry Bulb °F8621.726.323.526.023.727.923.926.4 8318.724.023.825.920.225.923.926.4 8015.721.022.624.516.722.424.126.2 7712.617.919.521.513.218.920.622.7 749.614.916.518.49.715.417.119.2 71#N/A11.913.515.4#N/A11.913.615.7 #78#N/A8.810.412.4#N/A8.410.112.2
1. These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Page 9 of the York BHP024 user manual — ALL SENSIBLE CAPACITY
9ページ · クリックして拡大
9ページ

TABLE 6: COOLING CAPACITIES - 3-1/2 TON (BHP042)

TEMPERATURE AIR ON OUTDOOR COILTEMPERATURE OF AIR ON INDOOR COIL 1300 CFM1400 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH48.844.540.540.649.244.940.841.0 POWER INPUT kW3.373.323.213.203.433.383.273.26 Sensible Capacity MBH1Entering Dry Bulb °F8631.639.440.540.633.041.040.841.0 8327.835.640.140.528.936.940.841.0 8024.031.838.840.224.832.840.141.5 7720.227.935.036.420.728.836.037.4 7416.424.131.232.616.724.731.933.4 71#N/A20.327.428.7#N/A20.627.929.3 68#N/A16.523.524.9#N/A16.523.825.2 95 °FNET CAP. MBH45.441.538.338.545.741.938.638.8 POWER INPUT kW3.673.663.543.543.723.713.603.60 Sensible Capacity MBH1Entering Dry Bulb °F8630.738.238.338.532.039.838.638.8 8326.934.438.138.327.935.738.638.8 8023.030.637.537.923.931.638.839.2 7719.226.833.634.019.827.634.735.1 7415.423.029.830.215.723.530.631.0 71#N/A19.126.026.4#N/A19.426.526.9 68#N/A15.322.222.6#N/A15.322.422.8 105 °FNET CAP. MBH41.937.735.235.642.137.935.435.7 POWER INPUT kW4.013.983.893.884.064.033.943.93 Sensible Capacity MBH1Entering Dry Bulb °F8628.134.535.235.629.435.835.435.7 8324.531.634.835.125.633.035.235.5 8021.028.133.733.821.829.134.935.1 7717.424.630.130.318.025.331.131.2 7413.921.026.626.714.121.527.327.4 71#N/A17.523.023.2#N/A17.723.523.6 68#N/A13.919.519.6#N/A13.919.719.8 115 °FNET CAP. MBH38.734.232.432.938.834.332.533.0 POWER INPUT kW4.414.354.284.284.464.404.334.32 Sensible Capacity MBH1Entering Dry Bulb °F8626.832.532.432.928.133.432.533.0 8323.330.232.132.324.331.532.332.7 8019.726.731.231.020.527.732.432.2 7716.223.127.627.516.723.928.628.4 7412.619.624.124.012.920.124.824.6 71#N/A16.120.620.4#N/A16.320.920.8 68#N/A12.517.016.9#N/A12.517.117.0 125 °FNET CAP. MBH35.630.729.630.335.530.629.630.2 POWER INPUT kW4.814.734.684.674.854.774.724.71 Sensible Capacity MBH1Entering Dry Bulb °F8625.530.429.630.326.831.029.630.2 8322.028.829.429.623.030.129.529.9 8018.525.328.728.319.226.329.829.4 7714.921.725.124.815.422.526.025.6 7411.418.221.621.211.618.622.221.8 71#N/A14.618.117.7#N/A14.818.418.0 68#N/A11.114.514.1#N/A11.014.614.2
1. These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Page 10 of the York BHP024 user manual — ALL SENSIBLE CAPACITY
10ページ · クリックして拡大
10ページ

TABLE 7: COOLING CAPACITIES - 4 TON (BHP048)

TEMPERATURE AIR ON OUTDOOR COILTEMPERATURE OF AIR ON INDOOR COIL 1500 CFM1600 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH54.350.445.748.254.951.046.348.8 POWER INPUT kW3.973.853.753.744.063.943.833.83 Sensible Capacity MBH1Entering Dry Bulb °F8635.545.145.748.237.247.146.348.8 8331.240.845.347.532.542.446.348.8 8026.836.443.745.227.837.845.346.9 7722.532.039.340.923.233.140.642.3 7418.127.735.036.518.528.436.037.6 71#N/A23.330.632.2#N/A23.831.332.9 68#N/A19.026.327.8#N/A19.126.628.3 95 °FNET CAP. MBH52.047.443.546.152.347.743.846.4 POWER INPUT kW4.334.254.174.114.434.354.264.20 Sensible Capacity MBH1Entering Dry Bulb °F8634.643.543.546.136.145.343.846.4 8330.339.143.145.431.540.643.846.4 8025.934.842.143.226.836.043.644.7 7721.530.437.838.822.131.338.940.0 7417.226.133.434.517.526.634.335.3 71#N/A21.729.130.1#N/A22.029.630.7 68#N/A17.324.725.8#N/A17.324.926.0 105 °FNET CAP. MBH48.844.240.143.249.044.540.343.5 POWER INPUT kW4.714.624.524.474.814.714.614.56 Sensible Capacity MBH1Entering Dry Bulb °F8632.040.240.143.233.541.840.343.5 8328.036.539.741.829.238.040.142.7 8023.932.439.639.324.833.641.040.8 7719.928.435.535.320.529.336.736.4 7415.924.331.531.216.124.932.332.0 71#N/A20.327.427.2#N/A20.628.027.7 68#N/A16.223.423.1#N/A16.223.623.3 115 °FNET CAP. MBH45.941.437.040.746.141.537.140.8 POWER INPUT kW5.195.084.964.935.285.175.055.02 Sensible Capacity MBH1Entering Dry Bulb °F8631.038.737.040.732.540.237.140.8 8326.935.337.039.328.136.837.140.1 8022.931.338.436.923.832.539.938.3 7718.827.234.432.919.428.135.634.0 7414.823.230.428.815.023.831.229.6 71#N/A19.126.324.8#N/A19.426.825.3 68#N/A15.122.320.7#N/A15.022.520.9 125 °FNET CAP. MBH43.138.533.938.143.238.634.038.2 POWER INPUT kW5.665.535.405.395.765.635.505.48 Sensible Capacity MBH1Entering Dry Bulb °F8629.937.333.938.131.438.634.038.2 8325.934.234.236.827.035.734.137.5 8021.830.137.334.522.731.338.835.9 7717.826.133.330.518.327.034.531.5 7413.722.029.326.414.022.630.127.2 71#N/A18.025.222.4#N/A18.325.722.8 68#N/A14.021.218.4#N/A13.921.418.5
1. These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Page 11 of the York BHP024 user manual — ALL SENSIBLE CAPACITY
11ページ · クリックして拡大
11ページ

TABLE 8: COOLING CAPACITIES - 5 TON (BHP060)

TEMPERATURE AIR ON OUTDOOR COILTEMPERATURE OF AIR ON INDOOR COIL 1600 CFM2000 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH64.058.553.453.164.559.053.853.6 POWER INPUT kW4.624.554.464.315.085.004.904.74 Sensible Capacity MBH1Entering Dry Bulb °F8639.348.753.453.144.855.153.853.6 8334.644.152.753.138.849.253.853.6 8030.039.448.052.332.943.252.653.6 7725.334.843.347.626.937.246.647.6 7420.730.138.742.920.931.340.741.6 71--25.434.038.3--25.334.735.7 68--20.829.333.6--19.328.829.7 95 °FNET CAP. MBH61.155.750.850.260.555.150.349.7 POWER INPUT kW5.085.014.894.745.595.515.375.22 Sensible Capacity MBH1Entering Dry Bulb °F8638.147.450.850.243.453.550.349.7 8333.542.850.850.237.447.550.349.7 8028.838.146.749.431.441.650.349.7 7724.133.442.044.725.535.644.443.7 7419.528.837.440.119.529.738.437.8 71--24.132.735.4--23.732.431.8 68--19.428.030.7--17.726.525.8 105 °FNET CAP. MBH56.951.246.847.256.350.746.346.7 POWER INPUT kW5.645.525.375.286.176.045.885.77 Sensible Capacity MBH1Entering Dry Bulb °F8636.745.746.847.241.949.946.346.7 8332.041.146.847.235.945.946.346.7 8027.336.446.746.130.039.946.346.7 7722.731.742.041.524.034.040.340.7 7418.027.137.336.818.028.034.434.8 71--22.432.732.1--22.028.428.8 68--17.728.027.5--16.122.422.8 115 °FNET CAP. MBH52.846.842.744.252.246.242.343.7 POWER INPUT kW6.206.035.865.816.766.576.386.33 Sensible Capacity MBH1Entering Dry Bulb °F8635.244.142.744.240.446.242.343.7 8330.539.442.744.234.544.242.343.7 8025.934.746.642.828.538.342.343.7 7721.230.142.038.222.532.336.337.7 7416.525.437.333.516.626.330.331.8 71--20.732.628.8--20.424.425.8 68--16.128.024.2--14.418.419.8 125 °FNET CAP. MBH48.742.338.741.248.041.838.240.7 POWER INPUT kW6.776.546.346.347.347.106.896.88 Sensible Capacity MBH1Entering Dry Bulb °F8633.742.438.741.239.042.638.240.7 8329.137.738.741.233.042.538.240.7 8024.433.046.639.527.036.638.240.7 7719.728.441.934.921.130.632.334.7 7415.123.737.330.215.124.726.328.7 71--19.032.625.5--18.720.322.8 68--14.427.920.9--12.714.416.8
York BHP024 — TABLE 8: COOLING CAPACITIES - 5 TON (BHP060) diagram (page 11)
図 1
1. These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Page 12 of the York BHP024 user manual — TABLE 10: HEATING CAPACITIES - 2-1/2 TON (BHP030)
12ページ · クリックして拡大
12ページ

TABLE 9: HEATING CAPACITIES - 2 TON (BHP024)

CFMRETURN AIR °FCAP1 & KWOUTDOOR AIR TEMPERATURE, °F (72% RH) -100102030405060 60055MBH10.216 1.21411.748 1.30713.601 1.40115.843 1.49418.554 1.58821.834 1.68125.801 1.77530.601 1.868 KW 70MBH7.317 1.3638.849 1.45610.702 1.55012.944 1.64315.655 1.73718.935 1.83022.902 1.92427.702 2.017 KW 80MBH7.205 1.4238.737 1.51610.590 1.61012.832 1.70315.543 1.79718.823 1.89022.790 1.98427.590 2.077 KW 80055MBH10.206 1.22711.738 1.32013.591 1.41415.833 1.50718.544 1.60121.824 1.69425.791 1.78830.591 1.881 KW 70MBH7.307 1.3768.839 1.46910.692 1.56312.934 1.65615.645 1.75018.925 1.84322.892 1.93727.692 2.030 KW 80MBH7.195 1.4368.727 1.52910.580 1.62312.822 1.71615.533 1.81018.813 1.90322.780 1.99727.580 2.090 KW 100055MBH11.377 1.33912.909 1.43214.762 1.52617.004 1.61919.715 1.71322.995 1.80626.962 1.90031.762 1.993 KW 70MBH8.478 1.48810.010 1.58111.863 1.67514.105 1.76816.816 1.86220.096 1.95524.063 2.04928.863 2.142 KW 80MBH8.366 1.5489.898 1.64111.751 1.73513.993 1.82816.704 1.92219.984 2.01523.951 2.10928.751 2.202 KW
1. These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.

TABLE 10: HEATING CAPACITIES - 2-1/2 TON (BHP030)

CFMRETURN AIR °FCAP1 & KWOUTDOOR AIR TEMPERATURE, °F (72% RH) -100102030405060 75055MBH KW10.876 1.84712.808 1.91715.078 1.98717.744 2.05720.877 2.12724.556 2.19828.879 2.26833.958 2.338 70MBH KW10.046 2.13511.978 2.20514.248 2.27516.914 2.34520.047 2.41523.726 2.48628.049 2.55633.128 2.626 80MBH KW9.054 2.37710.986 2.44713.256 2.51715.922 2.58719.055 2.65722.734 2.72827.057 2.79832.136 2.868 100055MBH KW11.886 1.73113.818 1.80116.088 1.87118.754 1.94121.887 2.01125.566 2.08229.889 2.15234.968 2.222 70MBH KW11.056 2.01912.988 2.08915.258 2.15917.924 2.22921.057 2.29924.736 2.37029.059 2.44034.138 2.510 80MBH KW10.064 2.26111.996 2.33114.266 2.40116.932 2.47120.065 2.54123.744 2.61228.067 2.68233.146 2.752 125055MBH KW13.978 1.88115.910 1.95118.180 2.02120.846 2.09123.979 2.16127.658 2.23231.981 2.30237.060 2.372 70MBH KW13.148 2.16915.080 2.23917.350 2.30920.016 2.37923.149 2.44926.828 2.52031.151 2.59036.230 2.660 80MBH KW12.156 2.41114.088 2.48116.358 2.55119.024 2.62122.157 2.69125.836 2.76230.159 2.83235.238 2.902
1. These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.
Page 13 of the York BHP024 user manual — CFM RETURN
13ページ · クリックして拡大
13ページ

TABLE 11: HEATING CAPACITIES - 3 TON (BHP036)

CFM RETURN

CAP 1

OUTDOOR AIR TEMPERATURE, °F (72% RH)

AIR °F

& KW

-10 0 10 20 30 40 50 60

KW 1.791 1.898 2.005 2.112 2.219 2.326 2.433 2.540

KW 2.198 2.305 2.412 2.519 2.626 2.733 2.840 2.947

KW 2.476 2.583 2.690 2.797 2.904 3.011 3.118 3.225

KW 1.825 1.932 2.039 2.146 2.253 2.360 2.467 2.574

KW 2.232 2.339 2.446 2.553 2.660 2.767 2.874 2.981

KW 2.510 2.617 2.724 2.831 2.938 3.045 3.152 3.259

KW 1.779 1.886 1.993 2.100 2.207 2.314 2.421 2.528

KW 2.186 2.293 2.400 2.507 2.614 2.721 2.828 2.935

KW 2.464 2.571 2.678 2.785 2.892 2.999 3.106 3.213

1. These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.

TABLE 12: HEATING CAPACITIES - 3-1/2 TON (BHP042)

CFM RETURN

CAP 1

OUTDOOR AIR TEMPERATURE, °F (72% RH)

AIR °F

& KW

-10 0 10 20 30 40 50 60

KW 2.410 2.505 2.599 2.694 2.789 2.883 2.978 3.073

KW 2.835 2.930 3.024 3.119 3.214 3.308 3.403 3.498

KW 3.143 3.238 3.332 3.427 3.522 3.616 3.711 3.806

KW 2.419 2.514 2.608 2.703 2.798 2.892 2.987 3.082

KW 2.844 2.939 3.033 3.128 3.223 3.317 3.412 3.507

KW 3.152 3.247 3.341 3.436 3.531 3.625 3.720 3.815

KW 2.463 2.558 2.652 2.747 2.842 2.936 3.031 3.126

KW 2.888 2.983 3.077 3.172 3.267 3.361 3.456 3.551

KW 3.196 3.291 3.385 3.480 3.575 3.669 3.764 3.859

1. These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.
Page 14 of the York BHP024 user manual — CFM RETURN
14ページ · クリックして拡大
14ページ

TABLE 13: HEATING CAPACITIES - 4 TON (BHP048)

CFM RETURN

CAP 1

OUTDOOR AIR TEMPERATURE, °F (72% RH)

AIR °F

& KW

-10 0 10 20 30 40 50 60

KW 2.342 2.568 2.795 3.022 3.249 3.476 3.703 3.930

KW 2.726 2.952 3.179 3.406 3.633 3.860 4.087 4.314

KW 3.067 3.293 3.520 3.747 3.974 4.201 4.428 4.655

KW 2.408 2.634 2.861 3.088 3.315 3.542 3.769 3.996

KW 2.792 3.018 3.245 3.472 3.699 3.926 4.153 4.380

KW 3.133 3.359 3.586 3.813 4.040 4.267 4.494 4.721

KW 2.502 2.728 2.955 3.182 3.409 3.636 3.863 4.090

KW 2.886 3.112 3.339 3.566 3.793 4.020 4.247 4.474

KW 3.227 3.453 3.680 3.907 4.134 4.361 4.588 4.815

1. These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.

TABLE 14: HEATING CAPACITIES - 5 TON (BHP060)

CFM RETURN

CAP 1

OUTDOOR AIR TEMPERATURE, °F (72% RH)

AIR °F

& KW

-10 0 10 20 30 40 50 60

KW 2.403 2.771 3.140 3.509 3.877 4.246 4.615 4.983

KW 2.967 3.335 3.704 4.073 4.441 4.810 5.179 5.547

KW 3.368 3.736 4.105 4.474 4.842 5.211 5.580 5.948

KW 2.411 2.779 3.148 3.517 3.885 4.254 4.623 4.991

KW 2.975 3.343 3.712 4.081 4.449 4.818 5.187 5.555

KW 3.376 3.744 4.113 4.482 4.850 5.219 5.588 5.956

1. These capacities are net capacities - the indoor motor heat has been added. These power inputs are total power inputs - the indoor motor watts have been added.
Page 15 of the York BHP024 user manual — RESISTANCE, IWG
15ページ · クリックして拡大
15ページ
TABLE 15SIDE & BOTTOM SUPPLY AIR BLOWER PERFORMANCE (208/230/460 VOLT 1 )

EXTERNAL STATIC PRESSURE - IWG

MODEL NO.

MOTOR SPEED

UNIT AIRFLOW

BHP

SETTING

0.15 0.30 0.50 0.70 0.90

WATTS

B1HP024 Cooling TB2-A, Heating TB2-A, Electric Heat 800 CFM 91 125 161 206 240

B1HP024 Cooling TB2-B, Heating TB2-B 900 CFM 118 148 199 243 285

B1HP030 Cooling TB2-A, Heating TB2-A, Electric Heat 1000 CFM 280 321 389 449 500

B1HP030 Cooling TB2-B, Heating TB2-B 1125 CFM 356 413 490 557 620

B1HP036 Cooling TB2-A, Heating TB2-A 1050 CFM 209 261 319 372 438

B1HP036 Cooling TB2-B, Heating TB2-B, Electric Heat 1200 CFM 273 324 392 480 541

B1HP042 Electric Heat 1225 CFM 306 341 412 494 577

B1HP042 Cooling TB2-A, Heating TB2-A 1300 CFM 338 395 470 551 640

B1HP042 Cooling TB2-B, Heating TB2-B 1400 CFM 393 466 544 642 734

B1HP048 Heating TB2-A 1400 CFM 377 427 504 597 683

B1HP048 Cooling TB2-A 1500 CFM 455 516 601 703 788

B1HP048 Cooling TB2-B, Heating TB2-B, Electric Heat 1600 CFM 530 608 707 800 873

B1HP060 Cooling TB2-A 1600 CFM 385 478 489 596 703

B1HP060 Heating TB2-A 1900 CFM 400 493 593 700 807

B1HP060 Cooling TB2-B 2000 CFM 590 717 833 940 1047

1. All units are factory set to TB2-A.

Resistance” table.

TABLE 16: ADDITIONAL STATIC RESISTANCE

RESISTANCE, IWG

DESCRIPTION

CFM

500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000

Wet Indoor Coil 0.01 0.01 0.01 0.02 0.01 0.02 0.03 0.04 0.04 0.03 0.04 0.04 0.05 0.05 0.06 0.07

Economizer 0.00 0.00 0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.07 0.08 0.08

Filter/Frame Kit 0.01 0.02 0.03 0.04 0.05 0.05 0.06 0.06 0.07

Electric Heat 0.02 0.03 0.03 0.03 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.01 0.11 0.11 0.12

Page 16 of the York BHP024 user manual — FIGURE 2 - FIELD WIRING DIAGRAM
16ページ · クリックして拡大
16ページ

THERMOSTAT UNIT TERMINAL STRIP

** ** = Minimum wire size of 18 AWG wire should be used for all field

R

R

installed 24 volt wire.

G

G

Y Y

W

W2

24 VOLT TRANSFORMER

PROGRAMMABLE THERMOSTAT ONLY

W1

O O

* = Only required on units with supplemental electric heat.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. CAUTION:

York BHP024 — G diagram (page 16)
図 2

FIGURE 2 - FIELD WIRING DIAGRAM

*

Page 17 of the York BHP024 user manual — ELECTRIC HEAT
17ページ · クリックして拡大
17ページ

TABLE 17: ELECTRIC DATA (BASIC UNIT)

Voltage Limitations1 Compressor OD Fan

Max. Fuse

BHP

Size (VA) Min. Max. RLA LRA

FLA

FLA

024 208/230-1-60 187 253 9.3 57.0 1.1 5.0 17.7 25 25 0.96 40

030 208/230-1-60 187 253 15.0 72.5 1.1 5.0 24.9 30 30 0.96 40 208/230-3-60 187 253 10.0 63.0 1.1 5.0 18.6 25 25 0.96 75 460-3-60 414 504 5.0 31.0 0.6 5.0 11.9 15 15 0.96 75

208/230-1-60 187 253 17.2 94.0 1.1 7.3 29.9 35 35 0.96 40 208/230-3-60 187 253 11.4 78.0 1.1 7.3 22.7 30 30 0.96 75 460-3-60 414 504 5.7 40.0 0.6 7.3 15.4 20 20 0.96 75 575-3-60 518 630 4.7 31 0.6 6.8 12.7 20 20 0.96 75

208/230-1-60 187 253 20.0 104.0 1.1 7.3 33.4 40 40 0.96 40 208/230-3-60 187 253 13.9 88.0 1.1 7.3 25.8 30 30 0.96 75 460-3-60 414 504 6.4 44.0 0.6 7.3 16.1 20 20 0.96 75 575-3-60 518 630 5.4 34 0.6 6.8 13.4 20 20 0.96 75

208/230-1-60 187 253 23.4 126.0 1.5 7.3 38.1 45 45 0.96 40 208/230-3-60 187 253 13.0 93.0 1.5 7.3 25.1 30 30 0.96 75 460-3-60 414 504 6.4 46.5 0.8 7.3 16.3 20 20 0.96 75 575-3-60 518 630 5.1 37.2 0.6 6.8 13.8 20 20 0.96 75

208/230-1-60 187 253 25 150 2.3 9.1 42.7 50 50 0.96 40 208/230-3-60 187 253 17.3 130 2.3 9.1 33.0 40 40 0.96 75 460-3-60 414 504 8.4 70 1.3 9.1 21.1 25 25 0.96 75 575-3-60 540 630 7 53 1.1 9.1 19 25 25 0.96 75

1. Rated in accordance with ARI Standard 110, utilization range “A”. 2. Dual Element, Time Delay Type.

NOMINAL VOLTAGE VOLTAGE KW CAP. MULTIPLIER

240 208 230 0.75 0.92

ELECTRIC HEAT

CORRECTION

FACTORS

480 460 0.92

600 575 0.92

Show 14 more labels / short text on this page
Supply Air · Max HACR · Transformer · Model · Power Supply · Blower · MCA (Amps) · Breaker · Unit Power · Motor · Motor · Size (Amps)2 · Size (Amps) · Factor
Page 18 of the York BHP024 user manual — FLA
18ページ · クリックして拡大
18ページ

TABLE 18: ELECTRICAL DATA (13 SEER HEAT PUMP / ELECTRIC HEAT)

Compressor Cond.

Max Fuse Size1

BHP

Size RLA LRA Model No. kW Total Amps

FLA

FLA

024 208/230-1-60 9.3 57.0 1.1 5.0 2NH04500506 3.8 / 5.0* 18.1 / 20.8 40.3 / 43.8 45 / 45 45 / 45 2NH04500706 5.6 / 7.5* 27.1 / 31.3 51.6 / 56.8 60 / 60 60 / 60 2NH04501006 7.5 / 10.0* 36.1 / 41.7 62.9 / 69.8 70 / 70 70 / 70

2NH04500506 3.8 / 5.0* 18.1 / 20.8 47.4 / 50.9 50 / 60 50 / 60 2NH04500706 5.6 / 7.5* 27.1 / 31.3 58.7 / 63.9 60 / 70 60 / 70 2NH04501006 7.5 / 10.0* 36.1 / 41.7 70.0 / 76.9 70 / 80 70 / 80 2NH04501506 11.3 / 15.0* 54.2 / 62.5 92.6 / 103.0 100 / 110 100 / 110

030 208/230-1-60 15.0 72.5 1.1 5.0

2NH04500506 3.8 / 5.0* 18.1 / 20.8 52.5 / 55.9 60 / 60 60 / 60 2NH04500706 5.6 / 7.5* 27.1 / 31.3 63.8 / 69.0 70 / 70 60 / 60 2NH04501006 7.5 / 10.0* 36.1 / 41.7 75.0 / 82.0 80 / 90 80 / 90 2NH04501506 11.3 / 15.0* 54.2 / 62.5 97.6 / 108.0 100 / 110 100 / 110

036 208/230-1-60 17.2 94.0 1.1 7.3

042 208/230-1-60 20.0 104.0 1.1 7.3 2NP04501006 7.5 / 10.0* 36.1 / 41.7 78.5 / 85.5 80 / 90 80 / 90 2NP04501506 11.3 / 15.0* 54.2 / 62.5 101.1 / 111.5 100 / 125 100 / 125

2NP04501006 7.5 / 10.0* 36.1 / 41.7 83.2 / 90.1 90 / 90 90 / 90 2NP04501506 11.3 / 15.0* 54.2 / 62.5 105.8 / 116.2 110 / 125 110 / 125 2NP04502006 15.0 / 20.0* 72.2 / 83.3 128.3 / 142.2 150 / 150 150 / 150 2NP04502506 18.8 / 25.0* 90.3 / 104.2 150.9 / 168.3 175 / 175 175 / 175

048 208/230-1-60 23.4 126.0 1.5 7.3

2NP04501006 7.5 / 10.0* 36.1 / 41.7 87.7 / 94.7 100 / 100 100 / 100 2NP04501506 11.3 / 15.0* 54.2 / 62.5 110.6 / 120.8 125 / 125 125 / 125 2NP04502006 15.0 / 20.0* 72.2 / 83.3 132.8 / 146.8 150 / 150 150 / 150 2NP04502506 18.8 / 25.0* 90.3 / 104.2 155.6 / 172.9 175 / 175 175 / 175

060 208/230-1-60 25 150 21.3 9.1

030 208/230-3-60 10.0 63.0 1.1 5.0 2NH04501025 7.5 / 10.0* 20.8 / 24.1 447 / 48.7 45 / 50 45 / 50 2NH04501525 11.3 / 15.0* 31.3 / 36.1 47.7 / 63.7 60 / 70 60 / 70

036 208/230-3-60 11.4 78.0 1.1 7.3 2NH04501025 7.5 / 10.0* 20.8 / 24.1 48.7 / 52.7 60 / 60 60 / 60 2NH04501525 11.3 / 15.0* 31.3 / 36.1 76.7 / 67.8 70 / 80 70 / 80

042 208/230-3-60 13.9 88.0 1.1 7.3 2NP04501025 7.5 / 10.0* 20.8 / 24.1 51.8 / 55.8 50 / 60 50 / 60 2NP04501525 11.3 / 15.0* 31.3 / 36.1 61.7 / 67.8 70 / 80 70 / 80

2NP04501025 7.5 / 10.0* 20.8 / 24.1 51.1 / 55.1 60 / 60 60 / 60 2NP04501525 11.3 / 15.0* 31.3 / 36.1 64.1 / 70.2 70 / 80 70 / 80 2NP04502025 15.0 / 20.0* 41.7 / 48.1 77.2 / 85.2 80 / 90 80 / 90 2NP04502525 18.8 / 25.0* 52.1 / 60.1 90.2 / 100.2 100 / 100 100 / 100

048 208/230-3-60 13.0 93.0 1.5 7.3

2NP04501025 7.5 / 10.0* 20.8 / 24.1 59.1 / 63.1 70 / 70 70 / 70 2NP04501525 11.3 / 15.0* 31.3 / 36.1 72.2 / 78.1 80 / 80 80 / 80 2NP04502025 15.0 / 20.0* 41.7 / 48.1 85.1 / 93.2 90 / 100 90 / 100 2NP04502525 18.8 / 25.0* 52.1 / 60.1 98.3 / 108.2 100 / 110 100 / 110

060 208/230-3-60 17.3 130 2.3 9.1

030 460-3-60 5.0 31.0 0.6 5.0 2NH04501046 10.0** 12.0 27.5 30 30 2NH04501546 15.0** 18.0 35.4 40 40

036 460-3-60 4.7 40.0 0.6 7.3 2NH04501046 10.0** 12.0 30.7 35 35 2NH04501546 15.0** 18.0 38.6 40 40

042 460-3-60 6.4 44.0 0.6 7.3 2NP04501046 10.0** 12.0 31.6 35 35 2NP04501546 15.0** 18.0 29.4 40 40

2NP04501046 10.0** 12.0 31.8 35 35 2NP04501546 15.0** 18.0 39.6 40 40 2NH04502046 10.0** 24.1 47.5 50 50 2NH04502546 25.0** 30.1 55.3 60 60

048 460-3-60 6.4 46.5 0.8 7.3

2NP04501046 10.0** 12.0 36.1 40 40 2NP04501546 15.0** 18.0 43.6 45 45 2NH04502046 10.0** 24.1 51.1 60 60 2NH04502546 25.0** 30.1 48.7 60 60

060 460-3-60 8.4 70 1.3 9.1

036 575-3-60 4.7 31 0.6 6.8 2NH04501058 10.0** 9.6 24.7 25 25 2NH04501558 15.0** 14.4 30.7 35 35

042 575-3-60 5.4 34 0.6 6.8 2NP04501058 10.0** 9.6 25.4 30 30 2NP04501558 15.0** 14.4 31.4 35 35

2NP04501058 10.0** 9.6 25.8 30 30 2NP04501558 15.0** 14.4 31.8 35 35 2NH04502058 10.0** 19.2 37.8 40 40 2NH04502558 25.0** 24.1 43.8 45 45

048 575-3-60 5.1 37 0.6 6.8

2NP04501058 10.0*** 9.6 31.0 35 35 2NP04501558 15.0*** 14.4 37.0 40 40 2NH04502058 20.0*** 19.2 43.0 45 45 2NH04502558 25.0*** 24.1 49.0 50 50

060 575-3-60 7 53 1.1 9.1

1. Dual element, time delay type 2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

* KW listed is for 240 volts, use Table 17 for 208 or 230 volts. ** KW listed is for 480 volts, use Table 17 for 460 volts. *** KW listed is for 600 volts, use Table 17 for 575 volts.

Show 12 more labels / short text on this page
Supply · Electric Heat Accessory · Air Blower · Minimum · Max HACR2 · Model · Power Supply · Fan Motor · Circuit Ampacity · Breaker · Motor · (Amps)
Page 19 of the York BHP024 user manual — FIGURE 4 - UNIT CLEARANCES
19ページ · クリックして拡大
19ページ

TABLE 19: APPLICATION DATA

MODEL BHP

024 030 036 042 048 060

MINIMUM AIR FLOW

COOLING 800 1000 1050 1300 1500 1500

(CFM)

HEATING 800 1000 1050 1400 1400 1500

MAXIMUM AIR FLOW

COOLING 900 1125 1200 1400 1600 2050

(CFM)

HEATING 900 1125 1200 1500 1600 2050

MINIMUM OPERATING TEMPERATURE IN COOLING MODE

(AMBIENT, °F) 45

MIMINIM MIXED AIR IN COOLING MODE

(RETURN AIR, DB °F/WB °F) 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57 68 / 57

MINIMUM MIXED AIR IN HEATING MODE

(RETURN AIR, °F) 55

CENTER OF GRAVITY

D

B1HP

CORNER WEIGHTS

SHIPPING

OPERATING

FRONT

UNIT SIZE

WEIGHT

WEIGHT

A B C D

OF UNIT

024 356 351 97 93 81 84

030 353 348 96 93 81 84

49-1/8 26 23-1/2 47-1/4

B

036 388 383 106 102 89 92

042 440 435 120 115 101 104

048 485 480 132 127 111 115

060 495 490 135 130 113 117

FIGURE 3 - CENTER OF GRAVITY AND WEIGHTS

CLEARANCES

UNIT CLEARANCES

(MINIMUM) Front 12” Back 0” Left Side (Filter Access) 24” Right Side 24”

36” (For Condenser Air Discharge)

1. Units may be installed on combustible floors made from wood or class A, B or C roof covering.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1/2 INCH BETWEEN COMBUSTIBLE ROOF CURB MATERIAL AND THE SUPPLY DUCT.

FIGURE 4 - UNIT CLEARANCES

Show 4 more labels / short text on this page
Below Unit1 · 0” · Above Unit2 ·
Page 20 of the York BHP024 user manual — FIGURE 5 - UNIT DIMENSIONS
20ページ · クリックして拡大
20ページ

81,7 6,=( ',0(16,21 ³$´

24

$OO GLPHQVLRQV DUH LQ LQFKHV 7KH\ DUH VXEMHFW WR FKDQJH ZLWKRXW QRWLFH &HUWLILHG GLPHQVLRQV ZLOO EH SURYLGHG XSRQ UHTXHVW

%$&.

FIGURE 5 - UNIT DIMENSIONS

Show 10 more labels / short text on this page
)5217 · $ 29(5$// · · · · · )5217 · · ·
Page 21 of the York BHP024 user manual — FIGURE 6 - TYPICAL APPLICATIONS
21ページ · クリックして拡大
21ページ
York BHP024 — field-installed accessories diagram (page 21)
図 3 · field-installed accessories

FIGURE 6 - TYPICAL APPLICATIONS

Page 22 of the York BHP024 user manual — FIGURE 7 - ROOF CURB DIMENSIONS
22ページ · クリックして拡大
22ページ
York BHP024 — field-installed accessories diagram (page 22)
図 4 · field-installed accessories

FIGURE 7 - ROOF CURB DIMENSIONS

Page 23 of the York BHP024 user manual — FIGURE 8 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY)
23ページ · クリックして拡大
23ページ
York BHP024 — field-installed accessories diagram (page 23)
図 5 · field-installed accessories

FIGURE 8 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY)

Page 24 of the York BHP024 user manual — FIGURE 9 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPLY)
24ページ · クリックして拡大
24ページ
York BHP024 — field-installed accessories diagram (page 24)
図 6 · field-installed accessories

FIGURE 9 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPLY)

Page 25 of the York BHP024 user manual — FIGURE 10 - TYPICAL WIRING DIAGRAM (460/575-3-60 POWER SUPPLY)
25ページ · クリックして拡大
25ページ
York BHP024 — field-installed accessories diagram (page 25)
図 7 · field-installed accessories

FIGURE 10 - TYPICAL WIRING DIAGRAM (460/575-3-60 POWER SUPPLY)

Page 26 of the York BHP024 user manual — REFRIGERANT COMPONENTS
26ページ · クリックして拡大
26ページ

MECHANICAL SPECIFICATIONS

8. Filters shall be furnished and be accessible through a removable access door, sealed air tight. (Single phase models - accessory kit available. Three phase models - standard from factory.)

GENERAL DESCRIPTION

Units shall be factory-assembled, single packaged, Heat Pumps, designed for outdoor mounted installa- tion. Units shall have minimum SEER ratings of 13.0. They shall have built in, equal size, field convertible duct connections for down discharge supply/return or horizontal discharge supply/return.

9. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams without modification to building structure, duct work and base unit.
10. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards, with 3/4" NPTI copper, ridged mount connection.

The units shall be factory wired, piped, charged with R- 22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded.

All units shall be manufactured in a facility certified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be classified to UL 1995/CAN/CSA No. 236-M90 conditions.

INDOOR (SUPPLY) FAN ASSEMBLY

1. Fan shall be direct drive, constant CFM, ECM design. Job site selected (BHP) brake horse power shall not exceed the motors nameplate horse power rating.

UNIT CABINET

2. Fan wheel shall be double-inlet type with forwardcurved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume.
1. Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powered paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards.
3. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
2. The unit top shall be a single piece “Water Shed” design, with drip edges and no-seam corners to provide optimum water integrity.
4. Fan assembly shall be “Slip Track” (slide-out) design for easy removal and cleaning.
3. Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel after installation.

OUTDOOR FAN ASSEMBLY

1. The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider bracket and shall be statically balanced for smooth operation.
4. Indoor blower section shall be insulated with up to 3/4” thick, aluminum, foil faced insulation, fastened to prevent insulation from entering the air stream.
5. Cabinet panels shall be “large” size, easily removable for servicing and maintenance, with built-in lift handles.
2. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.
6. Unit shall be built on a formed, “Super-Structure” design base pan, with embossments at critical points to add strength, rigidity and aid in minimizing sound.

REFRIGERANT COMPONENTS

1. Compressors: A. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or - 10% of the unit nameplate voltage.
7. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Base rails shall be removable, when required, to lower unit height.
Page 27 of the York BHP024 user manual — ELECTRICAL REQUIREMENTS
27ページ · クリックして拡大
27ページ

B. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally iso- lated on a dedicated, independent mounting.

room thermostat “LED” indication of unit lockout. Plus a built in 5 minute anti-short cycle protection.

D. Unit shall have large, easily removable panels, cov- ering electrical controls and compressor, allowing easy access for any maintenance or servicing.

2. Coils:

A. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally-enhanced copper tubes with all joints brazed.

ELECTRIC HEATING SECTION

1. An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 25 KW.

B. Evaporator and Condenser coils shall be of the direct expansion, draw-thru design.

2. The heating section shall have an automatic reset primary limit control to prevent the heating element system from operating at an excessive temperature.

3. Refrigerant Circuit and Refrigerant Safety Components shall include:

A. Independent thermal expansion devices (TXV).

B. Solid-core filter dryer to eliminate any foreign matter.

3. The heating section assembly shall slide out of the unit for easy maintenance and service.

C. Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge and without disrupting condenser or evaporator air flow.

4. Units with electric heating sections shall be wired for a single point power supply, with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

D. The refrigeration system shall provide at least 10° F of liquid sub-cooling at design conditions.

1. Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240.

E. Unit shall have a suction line accumulator and auto- matic reversing valve.

4. Unit Controls:

2. The compressor, with standard controls, shall be capable of operation down to 45° F outdoor temperature.

A. Unit shall contain a large, low voltage Terminal Board for easy connection of field low voltage wir- ing.

ELECTRICAL REQUIREMENTS

B. Controls shall be mounted in a large control box with tilt-out, hinged access door, allowing easy access for trouble shooting and maintenance without affect- ing the normal system operation pressures.

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bot- tom entry. This will minimize roof penetrations and avoid unit field modifications. Separate side and bot- tom openings shall be provided for the control wiring.

C. Unit shall contain a reliable demand defrost control to provide defrost. The defrost control shall also have an “X” terminal to provide a 24 volt signal for

Page 28 of the York BHP024 user manual — mechanical specifications
28ページ · クリックして拡大
28ページ
York BHP024 — mechanical specifications diagram (page 28)
図 8 · mechanical specifications

ISO 9001 Certified Quality Management System

Subject to change without notice. Printed in U.S.A. 036-21528-007-A-1205 Copyright © by Unitary Products Group 2005. All rights reserved. Supersedes: 036-21528-006-A-1005 Unitary 5005 Norman Products York OK Group Drive 73069