MODELS: CU060 - 300 5-25 TONS
VERTICAL

CONDITIONING
WATER COOLED
MODELS: CH060 - 5-10 TONS
HORIZONTAL



FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE


charge are provided with the unit, for field installation. Duct flange on CU240 evaporator return is incorporated into the fil ter frame.
These units are completely assembled, piped, wired, charged and tested at the factory and are shipped ready for immediate installation. Only the power supply wiring, the thermostat wir ing, the condenser water piping, the condensate drain piping and the ductwork are required to complete the installation.
All models utilize "Scroll" type hermetic compressors. Com pressors are mounted on rubber isolators to minimize vibra tion transmission. Internal overload protection is provided. External high pressure and low pressure cutout switches are included in each compressor control circuit. The 5 ton units have a single refrigeration circuit. The 8 -20 ton units feature two independent refrigeration circuits. Each refrigeration cir cuit includes an adjustable thermal expansion valve (with external equalizer), liquid line filter drier, sight glass/moisture indicator, and service gauge ports.
Units include a one-year limited warranty on all replacement parts and a five-year limited warranty on each compressor.
The evaporator coils are constructed of internally enhanced copper tubes mechanically bonded to rippled aluminum plate fins. The evaporator coil is employed in a draw-through con figuration, and features inter-laced circuiting. Large evapora tor coil face area minimizes potential water blow-off.
The high-efficiency tube-in-tube condensers feature a convo luted inner tube design for optimum performance. Standard models feature a copper inner tube surrounded by a steel outer tube, and carry a 400 psig working pressure rating.
INDOOR FANS
GENERAL
Forward curved, double inlet and double width centrifugal blowers are used for evaporator air movement. Large diame ter wheels are employed to provide required airflow perfor mance at minimum rpm and noise levels. Blower wheels are fabricated of galvanized steel. Blowers employ solid steel shafts, supported in permanently lubricated ball bearings. All blowers are belt driven. Variable-pitch motor sheaves allow for field adjustment of blower rpm.
Horizontal (CH) units are designed for suspended mounting. HWC models are shipped with ëstraight-throughí evaporator fan discharge as standard. Airflow orientation is field convert ible to side discharge. Vertical (CU) units are designed for free-standing floor mounting. All units are completely factory wired and pre-piped. Water supply, water outlet, and conden sate drain connections are via female pipe thread fittings.
All models 5 -25 tons ship as factory-charged unitized pack ages. The 5 -15 ton units may be field split between the evap orator /compressor section and the upper blower section; installation is possible through standard height doorways and elevators. All packages are designed for free-standing floor mounting. All models are shipped with vertical evaporator fan discharge as standard. Units are completely factory wired and piped. Dual circuit models feature internally manifolded condensers.
All units are completely factory wired with all necessary con trols. Manual reset protection is provided on evaporator blower motors. A manual reset circuit is also provided on each compressor control circuit in the event of high/low pres sure cutout. A 24 volt control circuit, with oversize trans former, is provided for field connection. Units are designed to operate with conventional thermostat control interface.
FILTERS
All cabinets are completely constructed of 18 Ga. corrosion resistant "Galvalume" coated steel. The entire unit interior (both evaporator and condensing section) is insulated with 1/2" thick, 2 lbs. density insulation. Service panels are equipped with lifting handles for ease of removal and han dling. Duct flanges for return air intake and evaporator dis
All models are shipped with 2 inch thick medium-efficiency throwaway filters factory installed. Filters are accessible from either front or right side on 5-15 ton models. The CU240 filter rack is external to the cabinet (shipped loose).






At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Adjust airflow downward as necessary
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Adjust airflow downward as necessary
Values include pressure drop from wet coil and clean filters.
Values include pressure drop from wet coil and clean filters.
Shaded areas indicate oversize motors.
Shaded areas indicate oversize motors.
NOTE:







CU300 45 75
25 TON EWT EWT
10000 CFM
65∞F 85∞F 105∞F 65∞F 85∞F 105∞F
EWB EDB TC SC kW TC SC kW TC SC kW TC SC kW TC SC kW TC SC kW
75∞F 308.9 227.9 22.17 289.6 217.8 25.74 266.8 206.5 30.41 314.6 234.0 21.29 295.4 220.9 24.67 273.2 213.3 29.09
62∞F 80∞F 308.9 267.2 22.17 289.6 257.1 25.74 266.8 246.2 30.41 314.6 275.2 21.29 295.4 260.2 24.67 273.2 255.1 29.09
85∞F 308.9 308.9 22.17 289.6 257.1 25.74 266.8 266.8 30.41 314.6 314.6 21.29 295.4 295.4 24.67 273.2 273.2 29.09
75∞F 335.8 180.6 22.74 314.8 171.2 26.32 290.4 161.4 31.09 342.0 183.3 21.73 321.6 175.9 25.14 298.2 166.7 29.57
67∞F 80∞F 335.8 220.9 22.74 314.8 211.2 26.32 290.4 201.2 31.09 342.0 223.3 21.73 321.6 218.0 25.14 298.2 208.4 29.57
85∞F 335.8 260.9 22.74 314.8 251.2 26.32 290.4 241.3 31.09 342.0 263.6 21.73 321.6 259.8 25.14 298.2 250.5 29.57
75∞F 363.7 133.1 23.33 340.6 125.3 26.96 316.5 118.3 31.78 372.5 135.9 22.22 350.4 128.5 25.67 325.7 121.1 30.05
72∞F 80∞F 363.7 174.2 23.33 340.6 166.2 26.96 316.5 159.5 31.78 372.5 178.0 22.22 350.4 170.3 25.67 325.7 162.5 30.05
85∞F 363.7 215.6 23.33 340.6 207.0 26.96 316.5 200.9 31.78 372.5 219.7 22.22 350.4 211.9 25.67 325.7 204.2 30.05

UNIT Air @ 80OF EDB, 67OF EWB Water Capacity [MBH]
CFM PD [in WG] Flow [GPM] PD [PSI] EWT [OF] Total Sensible
CH096 3200 0.14 15 1.4 45 87.4 66.5 55 52.7 52.7
CH120 4000 0.21 18 1.9 45 104.6 80.3 55 63.0 63.0 30 5.2 45 127.3 88.6 55 68.9 68.9

UNIT Air @ 80oF EDB, 67oF EWB Water Capacity [MBH]
CFM PD [in WG] Flow [GPM] PD [PSI] EWT [oF] Total Sensible 45 265.2 200.0
For total system water-side pressure drop, add condenser pressure drop and water-side economizer coil

MODEL VOLTAGE COMPRESSOR EVAPORATOR MIN. CCT. MAX FUSE / # QTY RLA LRA HP FLA RPM AMPACITY CCT. BKR. AMP
CU060 208-230/3/60 1 @ 19.3 123.0 1.00 3.1 1800 27.23 45 460/3/60 1 @ 7.5 49.5 1.00 1.6 1800 10.98 15 575/3/60 1 @ 6.4 40.0 1.00 1.3 1800 9.30 15
CU096 208-230/3/60 2 @ 13.9 88.0 1.50 4.4 1800 35.68 45 460/3/60 2 @ 7.1 44.0 1.50 2.2 1800 18.18 25 575/3/60 2 @ 5.4 34.0 1.50 1.8 1800 13.95 15
CU120 208-230/3/60 2 @ 19.3 123.0 2.00 6.0 1800 49.43 60 460/3/60 2 @ 7.5 49.5 2.00 3.0 1800 19.88 25 575/3/60 2 @ 6.4 40.0 2.00 2.4 1800 16.80 20
CU180 208-230/3/60 2 @ 25.0 164.0 3.00 8.4 1800 64.65 80 460/3/60 2 @ 12.0 100.0 3.00 4.2 1800 31.20 40 575/3/60 2 @ 9.7 90.0 3.00 3.4 1800 25.23 30
CU240 208-230/3/60 2 @ 33.6 225.0 5.00 13.2 1800 88.80 110 460/3/60 2 @ 17.3 114.0 5.00 6.6 1800 45.53 60 575/3/60 2 @ 13.5 80.0 5.00 5.3 1800 35.68 45
MODEL VOLTAGE COMPRESSOR EVAPORATOR MIN. CCT. MAX FUSE / # QTY RLA LRA HP FLA RPM AMPACITY CCT. BKR. AMP
CU060 208-230/3/60 1 @ 19.3 123.0 1.00 3.1 1800 27.23 45 460/3/60 1 @ 7.5 49.5 1.00 1.6 1800 10.98 15 575/3/60 1 @ 6.4 40.0 1.00 1.3 1800 9.30 15
CU096 208-230/3/60 2 @ 13.9 88.0 1.50 4.4 1800 35.68 45 460/3/60 2 @ 7.1 44.0 1.50 2.2 1800 18.18 25 575/3/60 2 @ 5.4 34.0 1.50 1.8 1800 13.95 15
CU120 208-230/3/60 2 @ 19.3 123.0 2.00 6.0 1800 49.43 60 460/3/60 2 @ 7.5 49.5 2.00 3.0 1800 19.88 25 575/3/60 2 @ 6.4 40.0 2.00 2.4 1800 16.80 20
CU180 208-230/3/60 2 @ 25.0 164.0 3.00 8.4 1800 64.65 80 460/3/60 2 @ 12.0 100.0 3.00 4.2 1800 31.20 40 575/3/60 2 @ 9.7 90.0 3.00 3.4 1800 25.23 30
CU240A 208-230/3/60 2 @ 33.6 225.0 5.00 13.2 1800 88.80 110 460/3/60 2 @ 17.3 114.0 5.00 6.6 1800 45.53 60 575/3/60 2 @ 13.5 80.0 5.00 5.3 1800 35.68 45
MODEL VOLTAGE COMPRESSOR EVAPORATOR MIN. CCT. MAX FUSE / # QTY RLA LRA HP FLA RPM AMPACITY CCT. BKR. AMP CU300 208-230/3/60 3 @ 32.1 195.0 7.50 21.8 1800 126.13 150 460/3/60 3 @ 16.4 95.0 7.50 10.0 1800 63.30 70 575/3/60 3 @ 12.0 80.0 7.50 8.4 1800 47.40 50



FIGURE 2 - DIMENSIONAL DATA - CH 8 & 10 TON HORIZONTAL MODELS


FIGURE 3 - PHYSICAL CONFIGURATION DATA - CH 8 & 10 TON WATER SIDE ECONOMIZER


2.63"
J
SUPPLY
AIR
D
FAN MOTOR
ACCESS
FILTER ACCESS
COIL
OPTIONAL R/A
GRILLE
E
FILTER
DRAIN
PAN
CONDENSATE
WATER OUT
DRAIN
CONDENSATE
DRAIN 24.00"
COMPRESSOR/CONDENSER
WATER IN
ACCESS
ELECTRICAL
PANEL
F 0.63" A
G
FIGURE 4 - DIMENSIONAL DATA - CU 5, 8, AND 10 TON VERTICAL MODELS
A B C D RETURN AIR SUPPLY AIR E F G H J K CU060 26.00 72.00 42.00 23.00 20.00 4.00 34.00 12.25 14.88 13.50 CU096 29.00 82.00 64.00 27.00 25.00 4.00 56.00 14.75 24.63 15.88 CU120 29.00 82.00 64.00 27.00 25.00 4.00 56.00 14.75 24.63 15.88


16.50" 12.25" 20.50" 2.63"
12.25"
26.00"
ACCESS
FILTER ACCESS
COIL
85.00"
OPTIONAL R/A
GRILLE
30.00"
DRAIN WATER OUT
DRAIN CONDENSATE
CONDENSATE
24.00"
WATER IN COMPRESSOR/CONDENSER
PANEL
ACCESS
0.63"
4.00"
68.00"
30.00"
76.00"



charge applications. In addition, the blower outlet panel may be interchanged with the front panel of the fan module. Inter changing these two panels allows horizontal fan discharge to either front or rear of the unit.
All models are field convertible for multiple supply return con figurations. The 5 through 15 ton models feature a removable upper fan module that can be rotated 180∞ for top rear dis
The blower outlet panel may also be interchanged on the 20 and 25 ton units to provide horizontal discharge.



CU060 37.50 5.50 23 1 1/2 1 1/2
CU096 59.50 5.50 28 1 1/2 1 1/2
CU120 59.50 5.50 28 1 1/2 1 1/2
CU180 71.50 5.50 33 2 2
CU240 76.50 5.50 40.13 2 2
CU300 79.50 5.50 40.13 2 2


Plenum Dimensions (Inches)
A B C Side Grill Front Grill
5 Ton 42 26 20 16x12 (2x) 32x12
15 Ton 64 29 24 20x18 (2x) 28x18 (2x)
8/10 Ton 64 29 24 20x16 (2x) 38x16
20 Ton 83 32.5 28 24x20 (2x) 32x20 (2x)
25 Ton 88 34 28 24x20 (2x) 32x20 (2x)

Unit Model CFM
10 30 50 70
1800 140 126.6 113.1 99.7

2000 147.1 133 118.8 104.7
2200 153.6 138.9 124.1 109.3
3000 258.3 233.4 208.6 183.8
3200 266.6 241 215.3 189.7
3400 274.5 248.1 221.8 195.4
3600 282.1 255 227.9 200.8 4000 296.3 267.9 239.4 210.9
4400 309.5 279.8 250.1 220.3
5400 425.8 384.9 344 303.1
6000 447.4 404.4 361.4 318.4 6600 467.3 422.4 377.5 332.6
7200 569.6 514.9 460.2 405.5
8000 598.5 541 483.5 426
8800 625.3 565.2 505.1 445.1
9000 645.8 583.7 521.7 459.6
10000 677.1 612.1 547 481.9
11000 706.1 638.2 570.4 502.6
ï Steam Heating Coils are tube-in-tube ësteam distributingí type to eliminate risk of con- densate freezing.
ï Coils are constructed of 5/8 inch diameter outer copper tubes, with 3/8 inch diameter inner tubes. The outer tube is mechanically bonded to rippled aluminum plate fins. Coil casing is fabricated of heavy gauge galvanized sheet. Copper headers are complete with MPT connections.

ï All coils are 1 row, 8 fins per inch.
Unit Model GPM CFM
70 90 110 130
1800 62.4 80.8 99.3 117.8
2000 66.2 85.9 105.5 125.3
2200 69.9 90.6 111.4 132.3
3000 111.6 144.3 177.1 209.9
3200 116 150.1 184.1 218.3
3400 120.2 155.5 190.9 226.3
3600 124.3 160.8 197.3 234
4000 131.9 170.7 209.6 248.6
4400 138.9 179.9 220.9 262
5400 183.5 237.3 291.2 345.2
6000 194.6 251.7 308.9 366.2
6600 204.8 265 325.3 385.7
7200 257.6 332.7 407.9 483.2
8000 274.2 354.2 434.3 514.6
8800 289.6 374.3 459 543.9
9000 313.2 404.3 495.5 586.8
10000 333.6 430.7 527.9 625.3
11000 352.5 455.3 558.2 661.2
* Temperature difference between entering water and entering air temperature.
ï Hot Water Heating Coils are constructed of 1/2 inch diameter copper tubes, mechanically bonded to rippled aluminum plate fins. Coil casing is fabricated of heavy gauge galvanized sheet. Copper tube headers are complete with MPT connections.
ï All coils are 2 row, 8 fins per inch.








Subject to change without notice. Printed in U.S.A. 036-21217-001-B-1203 Copyright © by Unitary Products Group 2004. All rights reserved. Supersedes: 036-21217-001-A-0503