Page 1 of the York DNP030 user manual — DNP024, 030, 036, 042, 048 AND 060 13 SEER
1ページ · クリックして拡大
1ページ

DESCRIPTION

York® Affinity™ Series packaged cooling/heating air condi- tioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation.

TECHNICAL GUIDE

AFFINITY™ SERIES

The gas-fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are avail- able in natural gas with field conversion to propane.

SINGLE PACKAGE GAS/ELECTRIC

AIR COOLED AIR CONDITIONERS

FEATURING

2 THRU 5 NOMINAL TON

  • FACTORY MOUNTED TXV
  • COOLING/GAS HEATING UNITS (NATURAL GAS OR PROPANE)
  • LOW PROFILE
  • QUIET OPERATION
  • COMMON FOOTPRINT
  • OPTIONAL SLIDE IN MOTORIZED DAMPERS
  • OPTIONAL SLIDE IN ECONOMIZERS
  • OPTIONAL PROPANE CONVERSION KIT
  • OPTIONAL HIGH ALTITUDE CONVERSION KIT (NATURAL GAS/PROPANE)
  • OPTIONAL LOW NOx KIT
  • FULL PERIMETER BASE RAILS
  • BOTTOM AND SIDE UTILITY CONNECTIONS
  • 1” OR 2” CLEANABLE FILTERS STANDARD ON ALL 3 PHASE MODELS. OPTIONAL ON 1 PHASE MODELS

DNP024, 030, 036, 042, 048 AND 060 13 SEER

York DNP030 — DNP024, 030, 036, 042, 048 AND 060 13 SEER diagram (page 1)
図 1
  • WARRANTY - 1 PHASE
  • 10 year compressor
  • 20 year heat exchanger
  • 5 year other parts
  • WARRANTY - 3 PHASE
  • 5 year compressor
  • 10 year heat exchanger
  • 1 year other parts
York DNP030 — DNP024, 030, 036, 042, 048 AND 060 13 SEER diagram (page 1)
図 2
York DNP030 — DNP024, 030, 036, 042, 048 AND 060 13 SEER diagram (page 1)
図 3
York DNP030 — DNP024, 030, 036, 042, 048 AND 060 13 SEER diagram (page 1)
図 4
York DNP030 — DNP024, 030, 036, 042, 048 AND 060 13 SEER diagram (page 1)
図 5

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 2 of the York DNP030 user manual — FIGURE 1 - PRODUCT NOMENCLATURE
2ページ · クリックして拡大
2ページ

TABLE OF CONTENTS

DESCRIPTION 1 STANDARD FEATURES/BENEFITS 3 FIELD-INSTALLED ACCESSORIES 4 TYPICAL WIRING DIAGRAM NOTES 32 MECHANICAL SPECIFICATIONS 33

19 TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY) 30

20 TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY) 31

21 TYPICAL WIRING DIAGRAM LEGEND 32

LIST OF FIGURES

LIST OF TABLES

Fig# Pg#

1 PRODUCT NOMENCLATURE 2

Tbl# Pg#

2 UNIT COMPONENT LOCATION 6

1 PHYSICAL DATA 6

3 FIELD WIRING DIAGRAM CONTROL WIRING 18

2 RATINGS COOLING/GAS HEATING 7

4 POWER WIRING FIELD DIAGRAM 19

3 DNP024 COOLING CAPACITIES - 2 TON 8

5 UNIT DIMENSIONS - FRONT 20

4 DNP030 COOLING CAPACITIES - 2-1/2 TON 10

6 UNIT DIMENSIONS - FRONT & BOTTOM 21

5 DNP036 COOLING CAPACITIES - 3 TON 11

7 UNIT DIMENSIONS - BACK & BOTTOM 21

6 DNP042 COOLING CAPACITIES - 3-1/2 TON 12

8 TYPICAL SLAB ON GROUND INSTALLATION 22

7 DNP048 COOLING CAPACITIES - 4 TON 13

9 TYPICAL ROOF CURB INSTALLATION 22

8 DNP060 COOLING CAPACITIES - 5 TON 14

10 TYPICAL DUCT APPLICATIONS 23

9 TWO TON AIR PERFORMANCE 15

11 UNIT CENTER OF GRAVITY 23

10 SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 16

12 ROOF CURB DIMENSIONS 24

13 ROOF CURB CROSS SECTION 24

11 BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 17

14 TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY) 25

12 ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON 18

15 TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230- 1-60 POWER SUPPLY) 26

13 ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON 18

16 TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY) 27

14 ELECTRICAL DATA 19

15 UNIT DIMENSIONS FRONT 20

17 TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230- 3-60 POWER SUPPLY) 28

16 UNIT MINIMUM CLEARANCES 20

18 TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY) 29

17 UNIT WEIGHTS AND CENTER OF GRAVITY 23

' 1 3 1

' 6LQJOH3DFNDJH$LU&RQGLWLRQHU

VW*HQHUDWLRQ QG*HQHUDWLRQ

%78+

13 6((5*DV+HDW(OHFWULF 120,1$/&22/,1* &$3$&,7< 0%+

1 1DWXUDO*DV+HDW,QVWDOOHG

%78+ %78+

FIGURE 1 - PRODUCT NOMENCLATURE

Show 11 more labels / short text on this page
352'8&7&$7(*25< · 92/7$*( &2'( · 352'8&7*(1(5$7,21 · · 120,1$/*$6+($7,1* 287387&$3$&,7< · 352'8&7,'(17,),(5 · )$&725< ,167$//('*$6+($7 · %78+ · %78+ · %78+ · %78+
Page 3 of the York DNP030 user manual — STANDARD FEATURES/BENEFITS
3ページ · クリックして拡大
3ページ

STANDARD FEATURES/BENEFITS

will build-up. The condensate pan conforms to ASHRAE 62- 89 standards (Ventilation for Acceptable Indoor Air Quality).

OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of 13.0. All efficiencies exceed legislated minimum levels.

CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI cop- per connection is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.

ON SITE FLEXIBILITY - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper ton- nage unit on that curb after the internal load has been deter- mined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory.

DURABLE FINISH - With a heavy duty cabinet made of pow- der-painted, galvanized steel the neutral color blends into surrounding areas. The powdered paint provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy finish insures less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish meets ASTM-B117 stan- dards for 1000 hours salt spray rating. The highest in the industry.

LOWER INSTALLATION COST - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are well under 500 pounds.

FULL PERIMETER BASE RAILS - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location.

All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and tem- perature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance.

MORE ATTRACTIVE APPEARANCE - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that will not release insulation fibers into conditioned area.

Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces.

UTILITY CONNECTIONS MADE EASY - Gas and electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.

TOP DISCHARGE - The top discharge condenser fan does not disrupt neighboring areas or dry-out vegetation surround- ing the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.

CONVERTIBLE AIRFLOW DESIGN - The bottom duct open- ings are covered when they leave the factory ready to be used for a side supply / side return application. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.

CONDENSER COIL GRILLE - A multi-piece totally enclosed, rigidly mounted condenser coil grille provides protection from objects after installation and provides protection during transit.

LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up and away from the liv- ing area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compres- sor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for opti- mum strength and rigidity.

CONDENSATE PAN - A non-corrosive, long-lasting, water- tight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate

Page 4 of the York DNP030 user manual — FIELD-INSTALLED ACCESSORIES
4ページ · クリックして拡大
4ページ

FAN SYSTEM - All 2-1/2, 3, 3-1/2 and 4 ton models operate over a wide range of design conditions with a constant CFM, electrically commutated (ECM) fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement. These models have 2 cooling speeds and a single heating speed. The cooling speed is factory set and can be field adjusted to a second speed. The heating speed is factory set to maintain mid point rise at the units heating input. It cannot be field adjusted. This allows maximum comfort conditions.

LOW MAINTENANCE - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip- Track slide-out blower assembly.

SECURED SERVICE ACCESS PORTS - Protected, exter- nally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required.

Two ton models operate over a wide range of design condi- tions with a 3-speed direct-drive fan motor. These single phase models have the Comfort-Match system that allows different speed taps for heating or cooling operations.

EASY SERVICE ACCESS - A large, single panel covers the electrical and gas controls makes servicing easy. The blower compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assem- bly to slide-out for easy removal for maintenance and ease of trouble shooting.

SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also pro- vided to simplify the field interface of external controls. Mate- n-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.

REPLACEMENT PARTS - The installer requires no special training to replace any of the components of these units and does not need to maintain an inventory of unique parts.

SYSTEM INTEGRATION - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit.

FIELD-INSTALLED ACCESSORIES

PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the com- pressor if undesirable operating conditions occur.

LOW NOx KIT - Kit includes all the necessary hardware and instructions to field convert units to reduce emissions to less than 40 nanogram per Joule. California requirement on single phase models only.

PROPANE CONVERSION KIT - Kit includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane.

EXCLUSIVE COIL DESIGN - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability.

HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane) - Kit includes all necessary labels and instructions to field alter units with natural gas/propane for installations above 2000 feet. Burner orifices must be obtained from Source 1 Parts. Propane Conversion Kit must be obtained separately.

HEAT EXCHANGERS - Are corrosion-resistant, aluminized- steel tubular construction to provide long-life, trouble-free operation. The unique blow-through design also assures that condensate does not collect in humid areas when in the cool- ing cycle. This adds to longer heat exchanger life and higher long term efficiencies.

ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modu- lating integrated economizer provides simultaneous opera- tion between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided.

POST PURGE INDUCED DRAFT COMBUSTION - Exhausts combustion products from the heat exchanger upon comple- tion of the heating cycle to prolong the heat exchanger life.

SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this self diagnostic control, less on site time is required to trouble shoot these units.

HOT SURFACE TO PILOT IGNITION - Provides faster heat delivery. This ignition is highly reliable, durable and elimi- nates nuisance lockouts. Also assures starts in damp condi- tions.

SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved econo- mizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air.

MULTI PORT IN-SHOT BURNERS - No field adjustment is required to mix the air and gas. These burners are con- structed of high-grade corrosion-resistant, aluminized-steel.

DUAL ENTHALPY SENSOR - Additional sensor to single enthalpy sensor. Sensor senses both the return air tempera- ture dry bulb and humidity in conjunction with the single

Page 5 of the York DNP030 user manual — FIELD-INSTALLED ACCESSORIES
5ページ · クリックして拡大
5ページ

enthalpy to determine the most economical mix. Single Enthalpy sensor also required.

50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.

PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by fur- nished adapters. When abnormal conditions are sensed through the pressure switches, the unit will lock out prevent- ing any further operation until reset or problem is corrected. Package agency approved.

RECTANGLE TO ROUND ADAPTERS - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening.

ROOF CURBS - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also pro- vides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available.

HAIL GUARD KIT - Kit contains protective grilles made of expanded aluminum with full perimeter frame. Sloped hoods are also included to assure maximum protection.

MANUAL OUTDOOR DAMPER - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.

ANTI SHORT CYCLE TIMER - Automatically prevents the compressor from restarting for 5 minutes after cycled off.Not required if Thermostat 2ET07700224 and 2ET04700224 are used.

WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.

FILTER / FRAME KIT (Single Phase only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable stan- dard size filters are shipped in one kit. The filter rack is suit- able for either 1" or 2" filters. (1" filter is supplied) This kit is available for single phase horizontal or vertical duct applica- tion only. Standard in all 3 Phase models.

LOW AMBIENT KIT - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Stan- dard unit operation 45º F.

TRANSFORMER KIT - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper.)

MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through

Page 6 of the York DNP030 user manual — COMPRESSOR
6ページ · クリックして拡大
6ページ

DIRECT DRIVE

CONDENSER

FAN MOTOR

BLOW-THROUGH DESIGN WITH RELIABLE ALUMINIZED STEEL TUBULAR HEAT EX HANGERS C

HIGHLY EFFICIENT ENHANCE

D

COPPER TUBE/ALUMINUM FIN

EVAPORATOR COIL

HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN

LONG LASTING POWDER PAINT

CONDENSER COIL

FINISH

DECORATIVE PROTECTIVE COIL GAURD

REAR AND BOTTOM

HIGH EFFICIENCY

RET R U N AIR AND SUPPLY AIR DUCT OPENINGS

COMPRESSOR

RIGIDLY MOUNTED

HOT SURFACE PILOT

ASSEMBLY

HIGH GRADE ALUMINIZED

HEAVY GAUGE

REMOVABLE

IN-SHOT BURNERS

BASE RAILS

LOW VOLTAGE TERMINAL BLOCK

SELF-DIAGNOSTIC CONTROLS WITH "COMFORT-MATCH" SPEED CONTROL

DIRECT DRIVE BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY

AUTOMATIC GAS VALVE (1/2" - 14 NPTI)

HIGH VOLTAGE TERMINAL BLOCK POWER VENTER MOTOR

FIGURE 2 - UNIT COMPONENT LOCATION

TABLE 1: PHYSICAL DATA

MODELDNP 024 030 036042048060 EVAPORATOR BLOWERCENTRIFUGAL BLOWER (Dia. x W. in.) FAN MOTOR HP10 x 8 10 1/2 3x 8 11 x 10 /4 3/412 x 11 112 x 11 112 x 11 1 EVAPORATOR COILROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.)2 15 1 3.5 33 3 3 13 .5 3.53 13 4.53 16 4.53 16 4.5 CONDENSER FANPROPELLER DIA. (in.) FAN MOTOR HP NOM. CFM TOTAL22 2 1/4 1 2,200 2,42 22 /4 1/4 00 2,40022 1/4 2,40022 1/3 3,00022 1/3 3,500 CONDENSER COILROWS DEEP FINS PER INCH FACE AREA (Sq. Ft.)2 20 2 11.7 111 2 0 20 .7 11.72 20 14.72 20 14.72 20 14.7 CHARGEREFRIGERANT 22 (lbs./oz.)6 / 4 4/ 9 6 / 129 / 68 / 48 / 8 FILTERFACE AREA (Sq. Ft.) Size (Actual)2.6 / 19 x 19.5 2.6 / 19x 19.5 2.6 / 19 x 19.53.1 / 19.5 x 11.5 (2 Reqd.)3.1 / 19.5 x 11.5 (2 Reqd.)3.1 / 19.5 x11.5 (2 Reqd.) FURNACE SECTIONNATURAL GAS BURNER ORIFICE NO. (Drill Size) PROPANE BURNER ORIFICE NO. (Drill Size) GAS CONNECTION SIZE43 4 55 5 1/2 NPTI 1/23 43 5 55 NPTI 1/2 NPTI40 53 1/2 NPTI40 53 1/2 NPTI40 53 1/2 NPTI COMPRESSORHERMETIC TYPE, (Qty. = 1)Recip Scroll ScrollScrollScrollScroll
Page 7 of the York DNP030 user manual — TABLE 2: RATINGS COOLING/GAS HEATING
7ページ · クリックして拡大
7ページ

TABLE 2: RATINGS COOLING/GAS HEATING

MODEL DNPNET COOLING CAPACITY1SOUND RATING (dbels)2GAS HEAT CAPACITY / EFFICIENCIES MBHSEER3EER4INPUT (MBH)OUTPUT (MBH)AFUE5 (%)NUMBER OF BURNERSTEMP. RISE (°F) RANGE 024N0360625.413.311.681453680.2225 - 55 024N0560625.413.311.681705680.2330 - 60 030N0360630.613.411.7580453680.2225 - 55 030N0362530.613.411.7580453680.2225 - 55 030N0364630.613.411.7580453680.2225 - 55 030N0560630.613.411.7580705680.2330 - 60 030N0562530.613.411.7580705680.2330 - 60 030N0564630.613.411.7580705680.2330 - 60 036N0360637.413.6511.7581453680.4225 - 55 036N0362537.413.6511.7581453680.4225 - 55 036N0364637.413.6511.7581453680.4225 - 55 036N0365837.413.6511.7581453680.4225 - 55 036N0560637.413.6511.7581705680.2325 - 55 036N0562537.413.6511.7581705680.2325 - 55 036N0564637.413.6511.7581705680.2325 - 55 036N0565837.413.6511.7581705680.2325 - 55 036N0720637.413.6511.7581907280.1430 - 60 036N0722537.413.6511.7581907280.1430 - 60 036N0724637.413.6511.7581907280.1430 - 60 036N0725837.413.6511.7581907280.1430 - 60 042N065064413.710.6580806480.6325 - 55 042N065254413.710.6580806480.6325 - 55 042N065464413.710.6580806480.6325 - 55 042N065584413.710.6580806480.6325 - 55 042N090064413.710.65801088680.8445 - 75 042N090254413.710.65801088680.8445 - 75 042N090464413.710.65801088680.8445 - 75 042N090584413.710.65801088680.8445 - 75 048N065064813.211.784806480.8325 - 55 048N065254813.211.784806480.8325 - 55 048N065464813.211.784806480.8325 - 55 048N065584813.211.784806480.8325 - 55 048N090064813.211.7841088680.6435 - 65 048N090254813.211.7841088680.6435 - 65 048N090464813.211.7841088680.6435 - 65 048N090584813.211.7841088680.6435 - 65 048N110064813.211.78413510780.5545 - 75 048N110254813.211.78413510780.5545 - 75 048N110464813.211.78413510780.5545 - 75 048N110584813.211.78413510780.5545 - 75 060N0650655.513.011.284806480.8325 - 55 060N0652555.513.011.284806480.8325 - 55 060N0654655.513.011.284806480.8325 - 55 060N0655855.513.011.284806480.8325 - 55 060N0900655.513.011.2841088680.6435 - 65 060N0902555.513.011.2841088680.6435 - 65 060N0904655.513.011.2841088680.6435 - 65 060N0905855.513.011.2841088680.6435 - 65 060N1100655.513.011.28413510780.5545 - 75 060N1102555.513.011.28413510780.5545 - 75 060N1104655.513.011.28413510780.5545 - 75 060N1105855.513.011.28413510780.5545 - 75
1. Net Cooling Capacity = ARI 210 standard rating conditions. 2. (dbels) = ARI 270-95 3. Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period. 4. Tested in accordance with ARI 210 Standard Rating Conditions. 5. AFUE = Annual Fuel Utilization Efficiency.
Page 8 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
8ページ · クリックして拡大
8ページ

TABLE 3: DNP024 COOLING CAPACITIES - 2 TON

AIR ON EVAPORATOR COILTEMPERATURE OF AIR ON CONDENSER COILTEMPERATURE OF AIR ON CONDENSER COIL 85°F95°F NET CAP. MBHPOWER INPUT KWSENSIBLE CAPACITY1NET CAP. MBHPOWER INPUT KWSENSIBLE CAPACITY1 ENTERING DRY BULB, °FENTERING DRY BULB, °F CFMWB °F8683807774716886838077747168 6007224.71.9015.013.311.69.98.1#N/A#N/A23.12.0315.013.311.69.98.1#N/A#N/A 6722.61.9118.416.714.913.211.59.88.121.02.0318.116.414.713.011.39.57.8 6220.91.8920.919.517.816.114.412.711.019.52.0019.519.417.716.014.312.510.8 5720.61.8820.620.218.516.815.113.411.719.51.9919.519.517.916.214.512.711.0 7007226.41.9417.014.912.910.98.9#N/A#N/A24.62.0816.714.712.710.78.6#N/A#N/A 6724.11.9420.718.716.714.712.710.68.622.32.0820.118.116.114.112.110.08.0 6222.31.9322.321.619.917.915.913.911.820.72.0520.720.719.417.415.313.311.3 5722.01.9222.021.820.718.716.714.612.620.72.0420.720.719.617.615.613.511.5 8007228.01.9719.016.614.312.09.6#N/A#N/A26.02.1318.516.113.811.59.1#N/A#N/A 6725.61.9823.120.818.516.113.811.59.123.72.1322.219.817.515.212.810.58.2 6223.71.9623.723.722.019.717.415.012.722.02.0922.022.021.118.816.414.111.8 5723.31.9523.323.322.920.518.215.913.522.02.0922.022.021.319.016.714.312.0 9007228.22.0120.417.715.112.49.8#N/A#N/A26.22.1519.917.214.611.99.3#N/A#N/A 6725.82.0124.522.119.516.814.211.58.823.92.1523.121.218.515.813.210.57.9 6223.81.9923.823.823.020.317.715.012.422.12.1222.122.121.719.116.413.711.1 5723.51.9823.523.523.220.617.915.312.622.22.1122.222.221.819.216.513.911.2 10007228.32.0421.818.815.912.99.9#N/A#N/A26.52.1821.318.315.412.49.4#N/A#N/A 6725.92.0425.923.520.517.514.511.58.624.12.1824.122.519.516.513.510.57.6 6224.02.0224.024.024.021.018.015.012.022.32.1422.322.322.319.316.413.410.4 5723.62.0123.623.623.620.617.614.711.722.32.1422.322.322.319.416.413.410.4
AIR ON EVAPORATOR COILTEMPERATURE OF AIR ON CONDENSER COILTEMPERATURE OF AIR ON CONDENSER COIL 105°F115°F NET CAP. MBHPOWER INPUT KWSENSIBLE CAPACITY1NET CAP. MBHPOWER INPUT KWSENSIBLE CAPACITY1 ENTERING DRY BULB, °FENTERING DRY BULB, °F CFMWB °F8683807774716886838077747168 6007221.52.2014.412.710.99.27.5#N/A#N/A20.02.3613.712.010.38.66.9#N/A#N/A 6719.52.1717.615.914.212.510.89.17.418.12.3017.215.413.712.010.38.66.9 6218.42.1518.418.316.715.013.311.69.917.32.3017.317.315.714.012.310.68.9 5718.52.1518.518.516.915.213.511.810.017.52.3117.517.515.914.212.510.89.1 7007222.82.2416.014.012.09.97.9#N/A#N/A21.02.4015.313.311.29.27.2#N/A#N/A 6720.72.2119.417.615.513.511.59.57.419.02.3418.617.015.012.910.98.96.9 6219.52.1919.519.418.316.214.212.210.218.22.3418.218.217.215.113.111.19.1 5719.62.1919.619.618.516.414.412.410.418.42.3518.418.417.315.313.311.39.2 8007224.12.2817.615.313.010.68.3#N/A#N/A22.12.4316.814.512.29.87.5#N/A#N/A 6721.82.2521.119.216.914.512.29.97.520.02.3820.018.516.213.911.59.26.9 6220.52.2420.520.519.817.515.212.810.519.12.3819.119.118.616.213.911.69.2 5720.72.2420.720.720.017.715.413.010.719.32.3819.319.318.716.414.111.79.4 9007224.32.3219.016.313.711.08.3#N/A#N/A22.32.4818.115.412.710.17.4#N/A#N/A 6722.02.2921.620.317.715.112.49.87.120.22.4320.219.517.014.311.69.06.3 6220.72.2720.720.720.417.715.112.49.719.32.4319.319.319.016.413.711.18.4 5720.82.2720.820.820.517.915.212.69.919.52.4319.519.519.216.613.911.38.6 10007224.52.3620.317.314.311.48.4#N/A#N/A22.52.5319.316.313.310.37.4#N/A#N/A 6722.22.3322.221.418.615.612.69.76.720.42.4720.420.417.714.811.88.85.8 6220.92.3120.920.920.917.915.012.09.019.52.4719.519.519.516.513.510.67.6 5721.02.3121.021.021.018.015.112.19.119.72.4819.719.719.716.713.710.87.8
1. These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY

Page 9 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
9ページ · クリックして拡大
9ページ

TABLE 3: DNP024 COOLING CAPACITIES - 2 TON (CONT’D)

TEMPERATURE OF AIR ON CONDENSER COIL

125°F

NET CAP. MBHPOWER INPUT KW WB °F868380777471 7218.42.513.111.49.78.06.3#N/A 6716.62.416.715.013.311.59.88.1 6216.22.516.216.214.813.111.49.6 5716.52.516.516.514.913.211.59.8 7219.32.614.612.510.58.56.5#N/A 6717.42.517.816.414.412.410.38.3 6217.02.517.017.016.014.012.010.0 5717.22.517.217.216.214.212.110.1 7220.12.616.013.711.39.06.7#N/A 6718.12.518.917.915.513.210.98.5 6217.72.517.717.717.315.012.610.3 5718.02.518.018.017.515.112.810.5 7220.42.617.114.511.89.26.5#N/A 6718.32.618.718.616.213.510.98.2 6217.92.617.917.917.715.012.49.7 5718.22.618.218.217.915.312.69.9 7220.62.718.315.312.39.36.3#N/A 6718.52.618.519.316.913.910.97.9 6218.12.618.118.118.115.112.19.2 5718.42.718.418.418.415.412.49.4
1. These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY

Page 10 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
10ページ · クリックして拡大
10ページ

TABLE 4: DNP030 COOLING CAPACITIES - 2-1/2 TON

TEMPERATURE OF AIR ON CONDENSER COILAIR ON EVAPORATOR COIL 1,000 CFM1,250 CFM WB °FWB °F 7267625772676257 85 °FNET CAP.MBH33.631.630.330.234.532.431.131.0 TOTAL POWER INPUT kW2.42.42.32.32.62.62.52.5 Sensible Capacity MBH1Entering Dry Bulb °F8623.629.230.330.227.232.431.131.0 8320.726.330.330.223.529.731.131.0 8017.823.428.429.619.725.931.131.0 7714.920.525.526.716.022.227.327.3 7412.017.522.623.812.318.523.623.5 71N/A14.619.720.8N/A14.819.919.8 68N/A11.716.817.9N/A11.016.216.1 95 °FNET CAP. MBH32.730.528.828.933.531.329.629.7 TOTAL POWER INPUT kW2.62.62.62.52.82.82.82.7 Sensible Capacity MBH1Entering Dry Bulb °F8623.129.028.828.926.931.329.629.7 8320.226.128.828.923.129.729.629.7 8017.323.227.928.419.426.029.629.7 7714.420.325.025.415.722.325.926.0 7411.517.322.122.512.018.522.122.2 71N/A14.419.219.6N/A14.818.418.5 68N/A11.516.316.7N/A11.114.714.8 105 °FNET CAP.MBH31.028.327.327.332.229.428.328.3 TOTAL POWERINPUT kW2.92.92.92.93.13.13.03.0 Sensible Capacity MBH1Entering Dry Bulb °F8622.627.627.327.326.429.428.328.3 8319.625.127.327.322.628.628.328.3 8016.722.226.426.818.925.128.328.3 7713.819.323.523.815.221.424.624.6 7410.916.420.620.911.517.620.820.9 71N/A13.517.718.0N/A13.917.117.2 68N/A10.514.815.1N/A10.213.413.4 115 °FNET CAP.MBH29.326.225.725.730.827.527.027.0 TOTAL POWER NPUT kW3.23.33.23.23.43.43.33.3 Sensible Capacity MBH1Entering Dry Bulb °F8622.026.225.725.725.827.527.027.0 8319.024.125.725.722.127.527.027.0 8016.121.224.925.218.424.227.027.0 7713.218.322.022.214.720.523.323.2 7410.315.419.119.310.916.819.519.5 71N/A12.516.216.4N/A13.015.815.8 68N/A9.613.313.5N/A9.312.112.1 125 °FNET CAP. MBH27.624.124.224.029.425.625.725.6 TOTAL POWER INPUT kW3.53.63.53.53.63.73.63.6 Sensible Capacity MBH1Entering Dry Bulb °F8621.424.824.224.025.325.625.725.6 8318.423.224.224.021.626.425.725.6 8015.520.223.423.617.923.325.725.6 7712.617.320.520.714.219.622.021.9 749.714.417.617.710.415.918.318.1 71N/A11.514.714.8N/A12.114.514.4 68N/A8.611.811.9N/A8.410.810.7
York DNP030 — TABLE 4: DNP030 COOLING CAPACITIES - 2-1/2 TON diagram (page 10)
図 6
1. These capacities are net capacities (the indoor fan heat is deducted)

ALL SENSIBLE CAPACITY

Page 11 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
11ページ · クリックして拡大
11ページ

TABLE 5: DNP036 COOLING CAPACITIES - 3 TON

TEMPERATURE OF AIR ON CONDENSER COILAIR ON EVAPORATOR COIL 1,200 CFM1,350 CFM WB °FWB °F 7267625772676257 85 °FNET CAP. MBH43.339.937.436.74440.53837.2 TOTAL POWER INPUT kW2.932.892.92.883.083.053.063.04 Sensible Capacity MBH1Entering Dry Bulb °F8629.535.837.436.731.838.43837.2 832632.337.436.727.834.43837.2 8022.528.834.835.623.830.436.736.7 771925.331.332.119.926.432.732.7 7415.521.827.828.615.922.528.728.7 71-18.324.325.1-18.524.724.7 68-14.820.821.6-14.520.720.7 95 °FNET CAP. MBH41.437.135.735.342.53836.636.2 TOTAL POWER INPUT kW3.223.273.183.153.323.373.283.25 Sensible Capacity MBH1Entering Dry Bulb °F8628.534.835.735.33136.936.636.2 832531.335.735.32733.736.636.2 8021.527.833.533.92329.725.535.5 771824.33030.41925.731.531.5 7414.520.826.526.91521.717.627.5 71-17.32323.4-17.723.623.5 68-13.819.519.9-13.819.619.5 105 °FNET CAP. MBH38.534.833.933.639.635.834.834.5 TOTAL POWER INPUT kW3.613.613.53.483.733.723.613.59 Sensible Capacity MBH1Entering Dry Bulb °F8627.633.633.933.629.935.134.834. 5 8324.130.133.933.62632.434.834.5 8020.626.63232.22228.433.933.8 7717.123.128.528.71824.429.929.8 7413.619.62525.21420.525.925.8 71-16.121.521.7-16.521.921.8 68-12.61818.2-12.51817.9 115 °FNET CAP. MBH35.632.632.231.936.733.533.132.8 TOTAL POWER INPUT kW4.013.953.823.84.144.073.933.92 Sensible Capacity MBH1Entering Dry Bulb °F8626.632.432.231.928.933.433.132.8 8323.128.932.231.924.931.133.132.8 8019.625.430.630.62127.132.332.1 7716.121.927.127.11723.228.328.1 7412.618.423.623.61319.224.324.1 71-14.920.120.1-15.220.320.2 68-11.416.616.6-11.216.316.2 125 °FNET CAP. MBH32.830.230.430.133.731.231.330 TOTAL POWER INPUT kW4.44.34.14.14.54.44.34.2 Sensible Capacity MBH1Entering Dry Bulb °F8625.631.230.430.127.931.631.331 8322.127.730.430.123.929.931.331 8018.624.219.128.919.925.930.630.4 7715.120.725.625.415.921.926.626.4 7411.617.222.121.91217.922.722.5 71-13.718.618.4-13.918.718.5 68-10.215.114.9-9.914.714.5
1. These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY

Page 12 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
12ページ · クリックして拡大
12ページ

TABLE 6: DNP042 COOLING CAPACITIES - 3-1/2 TON

TEMPERATURE OF AIR ON CONDENSER COILAIR ON EVAPORATOR COIL 1,350 CFM1,500 CFM WB °FWB °F 7267625772676257 85 °FNET CAP.48.444.540.941.254.049.645.646.0 TOTAL POWER3.43.33.33.33.83.73.63.7 Sensible Capacity MBH1Entering Dry Bulb °F8633.039.940.941.236.844.445.646.0 8329.136.040.941.232.440.145.646.0 8025.232.038.140.428.135.742.445.0 7721.328.134.236.523.731.338.140.7 7417.324.230.232.619.327.033.736.3 71N/A20.326.328.7N/A22.629.331.9 68N/A16.422.424.7N/A18.225.027.6 95 °FNET CAP.46.142.439.639.151.347.344.143.5 TOTAL POWER3.83.63.83.64.24.04.24.0 Sensible Capacity MBH1Entering Dry Bulb °F8632.238.839.639.135.943.344.143.5 8328.334.939.639.131.638.944.143.5 8024.431.037.638.727.234.541.943.1 7720.527.133.734.822.830.237.638.7 7416.623.129.830.818.525.833.234.4 71N/A19.225.926.9N/A21.428.830.0 68N/A15.321.923.0N/A17.124.525.6 105 °FNET CAP.43.540.037.237.248.544.641.441.5 TOTAL POWER4.24.14.14.04.64.54.64.5 Sensible Capacity MBH1Entering Dry Bulb °F8631.338.037.237.234.942.341.441.5 8327.434.137.237.230.638.041.441.5 8023.530.236.236.726.233.640.340.9 7719.626.232.332.821.829.236.036.5 7415.722.328.328.817.424.931.632.2 71N/A18.424.424.9N/A20.527.227.8 68N/A14.520.521.0N/A16.122.823.4 115 °FNET CAP.41.037.634.735.445.741.938.739.4 TOTAL POWER4.64.54.54.55.15.05.15.0 Sensible Capacity MBH1Entering Dry Bulb °F8630.437.234.735.433.941.438.739.4 8326.533.334.735.429.537.138.739.4 8022.629.334.734.725.232.738.738.7 7718.725.430.830.820.828.334.334.3 7414.721.526.926.816.424.030.029.9 71N/A17.623.022.9N/A19.625.625.6 68N/A13.719.019.0N/A15.221.221.2 125 °FNET CAP.38.535.232.333.643.039.236.037.4 TOTAL POWER5.05.04.94.95.65.55.55.5 Sensible Capacity MBH1Entering Dry Bulb °F8629.536.332.333.632.940.536.037.4 8325.632.432.333.628.536.136.037.4 8021.728.533.332.724.131.837.136.4 7717.724.629.428.819.827.432.732.1 7413.820.725.424.915.423.028.327.7 71N/A16.721.520.9N/A18.724.023.3 68N/A12.817.617.0N/A14.319.619.0
1. These capacities are net capacities (the indoor fan heat is deducted)

ALL SENSIBLE CAPACITY

Page 13 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
13ページ · クリックして拡大
13ページ

TABLE 7: DNP048 COOLING CAPACITIES - 4 TON

AIR ON EVAPORATOR COIL 1,400 CFM 1,600 CFM WB °F WB °F

TEMPERATURE

OF AIR ON CONDENSER COIL

72 67 62 57 72 67 62 57

NET CAP.

MBH 54.0 49.2 45.6 45.9 55.2 50.4 46.6 46.9

TOTAL POWER

INPUT kW 3.69 3.66 3.62 3.57 3.85 3.83 3.79 3.73

86 35.8 43.7 45.6 45.9 39.1 47.7 46.6 46.9

85 °F

83 31.7 39.6 44.6 45.3 34.5 43 46.6 46.9 80 27.7 35.6 42.4 43.6 29.8 38.3 45.7 46.9 77 23.6 31.6 38.4 39.5 25.1 33.7 41 42.3

MBH 1

74 19.6 27.5 34.3 35.5 20.5 29 36.3 37.6 71 - 23.5 30.3 31.4 - 24.3 31.7 32.9 68 - 19.4 26.2 27.4 - 19.7 27 28.3

NET CAP.

MBH 51.8 46.8 43.8 44.0 51.9 46.9 43.9 44.2

TOTAL POWER

INPUT kW 4.07 4.04 4.01 3.99 4.21 4.18 4.15 4.12

86 35.4 42.9 43.8 44.0 38.4 46.4 43.9 44.2 83 31.4 38.9 42.8 43.2 33.8 41.7 43.9 44.2

95 °F

80 27.4 34.9 40.9 41.5 29.1 37.1 43.5 44.2 77 23.3 30.8 36.8 37.5 24.4 32.4 38.8 39.5 74 19.3 26.8 32.8 33.4 19.8 27.7 34.1 34.8

MBH 1

71. 22.7 28.7 29.4 - 23.1 29.5 30.2 68 - 18.7 24.7 25.4 - 18.4 24.8 25.5

NET CAP.

MBH 48.7 44.3 41.4 41.7 49.2 44.7 41.8 42.1

TOTAL POWER

INPUT kW 4.49 4.45 4.38 4.34 4.63 4.59 4.51 4.48

86 34.1 41.3 41.4 41.7 37.1 4.44 41.8 42.1 83 30.0 37.7 40.7 41.1 32.4 40.6 41.8 42.1 80 26.0 33.6 38.9 39.4 27.8 35.9 41.6 42.1

105 °F

MBH 1

77 22.0 29.6 34.9 35.3 23.1 31.3 36.9 37.4 74 17.8 25.6 30.8 31.3 18.4 26.6 32.3 32.7 71 - 21.5 26.8 27.3 - 21.9 27.6 28.1

68. 17.5 22.8 23.2 - 17.3 22.9 23.4

NET CAP.

MBH 45.7 41.8 39.1 39.4 46.4 42.5 39.7 40

TOTAL POWER

INPUT kW 4.91 4.86 4.74 4.70 5.05 5 4.87 4.83

86 32.7 39.7 39.1 39.4 35.8 42.5 39.7 40 83 28.7 36.5 38.7 38.9 31.1 39.5 39.7 40 80 24.6 32.4 37.0 37.2 26.4 34.8 39.7 40

115 °F

MBH 1

77 20.6 28.4 32.9 33.2 21.8 30.1 35 35.3 74 16.6 24.4 28.9 29.1 17.1 25.5 30.4 30.6 71 - 20.3 24.9 25.1 - 20.8 25.7 26

68. 16.3 20.8 21.1 - 16.2 21 21.3

NET CAP.

MBH 42.7 39.3 36.8 37.0 43.6 40.2 37.6 37.9

TOTAL POWER

INPUT kW 4.3 5.3 5.1 5.0 5.5 5.4 5.2 5.2

86 31.4 38.0 36.8 37.0 34.5 40.5 37.6 37.9

125 °F

83 27.3 35.3 36.7 36.8 29.8 38.4 37.6 37.9 80 23.3 31.2 35.1 35.1 25.1 33.7 37.6 37.9 77 19.2 27.2 31.0 31.0 20.5 29 33.2 33.2

MBH 1

74 15.2 23.1 27.0 27.0 15.8 24.4 28.5 28.5 71 - 19.1 22.9 23.0 - 19.7 23.8 23.9 68 - 15.1 18.9 18.9 - 15 19.2 19.2

1. These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY

Show 15 more labels / short text on this page
Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F
Page 14 of the York DNP030 user manual — ALL SENSIBLE CAPACITY
14ページ · クリックして拡大
14ページ

TABLE 8: DNP060 COOLING CAPACITIES - 5 TON

AIR ON EVAPORATOR COIL 1,500 CFM 1,800 CFM WB °F WB °F

TEMPERATURE

OF AIR ON CONDENSER COIL

72 67 62 57 72 67 62 57

NET CAP.

MBH 63.5 57.6 52.7 53.1 64.3 58.3 53.3 53.7

TOTAL POWER

INPUT kW 4.49 4.44 4.38 4.27 4.68 4.63 4.57 4.45

86 39.4 47.5 52.7 53.1 41.4 49.6 53.3 53.7

85 °F

83 35.0 43.2 50.9 53.1 36.1 44.3 52.0 53.7 80 30.6 38.8 46.5 50.5 30.7 38.9 46.6 50.7 77 26.3 34.4 42.1 46.2 25.4 33.5 41.2 45.3

MBH 1

74 21.9 30.0 37.7 41.8 20.0 28.2 35.9 39.9 71 -- 25.7 33.4 37.4 -- 22.8 30.5 34.6 68 -- 21.3 29.0 33.1 -- 17.4 25.1 29.2

NET CAP.

MBH 60.6 56.0 52.1 51.5 61.2 56.6 52.6 52.0

TOTAL POWER

INPUT kW 4.96 4.90 4.80 4.73 5.12 5.05 4.95 4.88

86 38.2 46.6 52.1 51.5 43.3 52.6 52.6 52.0 83 33.9 42.2 49.8 51.5 38.0 47.2 52.6 52.0

95 °F

80 29.5 37.8 45.4 48.7 32.6 41.9 50.3 52.0 77 25.1 33.5 41.1 44.4 27.3 36.5 44.9 46.7 74 20.7 29.1 36.7 40.0 21.9 31.1 39.5 41.3

MBH 1

71 -- 24.7 32.3 35.6 -- 25.8 34.2 35.9 68 -- 20.3 27.9 31.2 -- 20.4 28.8 30.6

NET CAP.

MBH 57.6 53.3 49.5 49.3 58.4 54.1 50.2 50.0

TOTAL POWER

INPUT kW 5.52 5.43 5.34 5.27 5.69 5.60 5.51 5.43

86 37.1 45.3 49.5 49.3 42.6 51.8 50.2 50.0 83 32.7 40.9 48.4 49.3 37.2 46.4 50.2 50.0 80 28.4 36.6 44.1 46.4 31.8 41.1 49.1 50.0

105 °F

MBH 1

77 24.0 32.2 39.8 42.1 26.5 35.7 43.7 44.7 74 19.6 27.8 35.4 37.7 21.1 30.3 38.3 39.3 71 -- 23.4 31.0 33.3 -- 25.0 33.0 33.9

68 -- 19.1 26.6 29.0 -- 19.6 27.6 28.6

NET CAP.

MBH 54.6 50.6 46.9 47.1 55.7 51.6 47.9 48.0

TOTAL POWER

INPUT kW 6.07 5.97 5.89 5.81 6.26 6.16 6.07 5.99

86 36.0 44.0 46.9 47.1 41.8 51.0 47.9 48.0 83 31.6 39.7 46.9 47.1 36.4 45.6 47.9 48.0 80 27.2 35.3 42.9 44.2 31.1 40.3 47.9 48.0

115 °F

MBH 1

77 22.8 30.9 38.5 39.8 25.7 34.9 42.5 42.7 74 18.5 26.5 34.1 35.4 20.3 29.5 37.1 37.3 71 -- 22.2 29.7 31.0 -- 24.2 31.8 31.9

68 -- 17.8 25.4 26.7 -- 18.8 26.4 26.6

NET CAP.

MBH 51.6 47.9 44.4 44.9 52.9 49.1 45.5 46.0

TOTAL POWER

INPUT kW 6.62 6.51 6.43 6.35 6.82 6.71 6.62 6.54

86 34.8 42.8 44.4 44.9 41.0 50.2 45.5 46.0

125 °F

83 30.5 38.4 45.5 44.9 35.6 44.8 45.5 46.0 80 26.1 34.0 41.6 41.9 30.3 39.5 46.7 46.0 77 21.7 29.6 37.2 37.5 24.9 34.1 41.3 40.7

MBH 1

74 17.3 25.3 32.8 33.1 19.6 28.7 35.9 35.3 71 -- 20.9 28.4 28.7 -- 23.4 30.6 29.9 68 -- 16.5 24.1 24.4 -- 18.0 25.2 24.6

1. These capacities are net capacities (the indoor fan heat is deducted).

ALL SENSIBLE CAPACITY

Show 15 more labels / short text on this page
Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F · Sensible Capacity · Entering Dry · Bulb °F
Page 15 of the York DNP030 user manual — BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230 VOLTS
15ページ · クリックして拡大
15ページ

TABLE 9: TWO TON AIR PERFORMANCE 1

EXTERNAL STAIC PRESSURE - IWG

MODEL #

.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10

MTR SPD

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

WATTS

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

CFM

SIDE SUPPLY AIR PERFORMANCE - 208 VOLT

HI - 984 443 894 422 751 390 608 358 -

MED 994 333 947 321 901 309 854 297 774 280 695 263 615 246 -

LOW 743 243 700 235 657 226 614 218 -

SIDE SUPPLY AIR BLOWER PERFORMANCE - 230 VOLT

HI - 929 491 809 473 688 454 -

MED - 999 353 944 338 865 319 785 299 706 280 -

LOW 998 372 906 333 813 294 721 255 651 241 -

BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208 VOLT

HI - 886 398 805 380 676 351 547 322 -

MED 895 300 853 289 811 278 769 267 697 252 625 237 554 221 -

LOW 669 219 630 211 591 204 553 196 -

BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 230 VOLTS

HI - 836 442 728 425 620 409 -

MED - 899 318 850 304 778 287 707 269 635 252 -

LOW 898 335 815 300 732 265 649 230 586 217 -

1. Above data includes allowances for a dry evaporator coil, gas heat exchanger and no filters. For additional pressure drops, refer to Table 12 and 13.

DNP (Cooling/ · Heating)

Page 16 of the York DNP030 user manual — EXTERNAL STATIC PRESSURE - IWG
16ページ · クリックして拡大
16ページ

TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 1

EXTERNAL STATIC PRESSURE - IWG

MODEL #

MODE (COOLING / HEATING) CFM

DNP

.20 .30 .40 .50 .60 .70 .80 .90 1.0

WATTS

030 COOLING (FACTORY SETTING) 1000 248 298 325 365 385 411 470 498 500

030 COOLING (FIELD SETTING) 1250 342 385 431 474 510 562 614 657 694

030 HEATING (2 TUBE) (FACTORY SETTING) 850 169 217 237 278 302 334 374 401 431

030 HEATING (3 TUBE) (FACTORY SETTING) 1100 300 338 378 416 447 493 539 576 609

036 COOLING (FACTORY SETTING) 1200 354 396 436 511 548 599 641 677 721

036 COOLING (FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826

036 HEATING (2 TUBE) (FACTORY SETTING) 700 207 231 254 298 320 349 - - -

036 HEATING (3 TUBE) (FACTORY SETTING) 1250 383 432 478 543 581 628 - - -

036 HEATING (4 TUBE) (FACTORY SETTING) 1350 442 503 563 606 648 685 - - -

042 COOLING (FACTORY SETTING) 1350 410 457 504 575 646 687 729 780 830

042 COOLING (FIELD SETTING) 1500 450 500 553 641 729 798 830 872 939

042 HEATING (3 TUBE) (FACTORY SETTING) 1500 450 500 553 641 729 798 830 872 939

042 HEATING (4 TUBE) (FACTORY SETTING) 1275 388 433 478 545 612 652 691 739 787

048 COOLING (FACTORY SETTING) 1400 427 476 525 599 673 716 759 812 865

048 COOLING (FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030

048 HEATING (3 TUBE) (FACTORY SETTING) 1525 458 511 564 654 744 814 - - -

048 HEATING (4 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -

048 HEATING (5 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -

060 COOLING (FACTORY SETTING) 1500 439 526 559 636 716 748 816 884 941

060 COOLING (FIELD SETTING) 1800 659 809 814 946 1001 1053 1124 1176 1180

060 HEATING (3 TUBE) (FACTORY SETTING) 1500 439 526 559 636 716 748 816 884 941

060 HEATING (4 TUBE) (FACTORY SETTING) 1700 576 757 788 872 929 979 1000 1121 1188

060 HEATING (5 TUBE) (FACTORY SETTING) 1700 576 757 788 872 929 979 1000 1121 1188

1. Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11 and 12.
Page 17 of the York DNP030 user manual — EXTERNAL STATIC PRESSURE - IWG
17ページ · クリックして拡大
17ページ

TABLE 11: BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 1

EXTERNAL STATIC PRESSURE - IWG

MODEL #

MODE (COOLING / HEATING) CFM

DNP

.20 .30 .40 .50 .60 .70 .80 .90 1.0

WATTS

030 COOLING (FACTORY SETTING) 1000 248 298 325 365 385 411 470 498 500

030 COOLING (FIELD SETTING) 1250 342 385 431 474 510 562 614 657 694

030 HEATING (2 TUBE) (FACTORY SETTING) 850 169 217 237 278 302 334 374 401 431

030 HEATING (3 TUBE) (FACTORY SETTING) 1100 300 338 378 416 447 493 539 576 609

036 COOLING (FACTORY SETTING) 1200 354 396 436 511 548 599 641 677 721

036 COOLING (FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826

036 HEATING (2 TUBE) (FACTORY SETTING) 700 207 231 254 298 320 349 - - -

036 HEATING (3 TUBE) (FACTORY SETTING) 1250 383 432 478 543 581 628 - - -

036 HEATING (4 TUBE) (FACTORY SETTING) 1350 442 503 563 606 648 685 - - -

042 COOLING (FACTORY SETTING) 1350 410 457 504 575 646 687 729 780 830

042 COOLING (FIELD SETTING) 1500 450 500 553 641 729 798 830 872 939

042 HEATING (3 TUBE) (FACTORY SETTING) 1500 450 500 553 641 729 798 830 872 939

042 HEATING (4 TUBE) (FACTORY SETTING) 1275 388 433 478 545 612 652 691 739 787

048 COOLING (FACTORY SETTING) 1400 427 476 525 599 673 716 759 812 865

048 COOLING (FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030

048 HEATING (3 TUBE) (FACTORY SETTING) 1525 458 511 564 654 744 814 - - -

048 HEATING (4 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -

048 HEATING (5 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -

060 COOLING (FACTORY SETTING) 1500 345 487 554 569 654 745 784 835 896

060 COOLING (FIELD SETTING) 1800 567 663 794 917 948 1015 1048 1155 1175

060 HEATING (3 TUBE) (FACTORY SETTING) 1500 345 487 554 569 654 745 784 835 896

060 HEATING (4 TUBE) (FACTORY SETTING) 1700 504 603 698 771 831 1043 1102 1155 1202

060 HEATING (5 TUBE) (FACTORY SETTING) 1700 504 603 698 771 831 1043 1102 1155 1202

1. Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11 and 12.
Page 18 of the York DNP030 user manual — R
18ページ · クリックして拡大
18ページ

TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON

RESISTANCE, IWG

DESCRIPTION

CFM

500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600

WET EVAPORATOR COIL.01 .01 .01 .02 .03 .04 .05 .06 .07 .08 .09 .09

ECONOMIZER1.00 .00 .00 .01 .02 .03 .04 .05 .06

FILTER FRAME KIT.01 .02 .04 .06 .08 .10 .13 .16 .17 .18 .19 .20

1. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 13: ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON

RESISTANCE, IWG

DESCRIPTION

CFM

1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000

WET EVAPORATOR COIL.02 .03 .04 .05 .06 .07 .07 .08 .09 .09

ECONOMIZER1.02 .02 .02 .03 .03 .04 .04 .04 .05 .05

FILTER FRAME KIT.04 .04 .05 .05 .06 .07 .08 .09 .10 .11

1. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

THERMOSTAT UNIT TERMINAL STRIP

** ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.

R

R

G

G

Y Y

24 VOLT TRANSFORMER

W

W

PROGRAMMABLE THERMOSTAT ONLY

FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING

Page 19 of the York DNP030 user manual — SUPPLY
19ページ · クリックして拡大
19ページ

FIGURE 4 - POWER WIRING FIELD DIAGRAM

TABLE 14: ELECTRICAL DATA

VOLTAGE LIMITATIONS1 COMPRESSOR COND.

SUPPLY

MAX. FUSE

MAX. HACR BREAKER

AIR BLOWER

MINIMUM

UNIT POWER FACTOR

MODEL

DNP POWER SUPPLY

FAN MOTOR,

CIRCUIT AMPACITY

TRANSFORMER

SIZE (VA) MIN. MAX. RLA LRA

SIZE, AMPS 2

FLA

MOTOR

SIZE, AMPS

FLA

024 208/230-1-60 187 253 8.0 53.5 1.1 2.6 16.5 20 20 0.96 40

030 208/230-1-60 187 253 13.6 67 1.1 6.8 24.9 35 35 0.96 40

030 208/230-3-60 187 253 8.6 55 1.1 6.8 18.7 25 25 0.96 75

030 460-3-60 432 504 5.7 39 0.6 6.8 13.4 20 20 0.96 75

036 208/230-1-60 187 253 17.2 88 1.1 6.8 29.4 45 45 0.96 40

036 208/230-3-60 187 253 11.4 77 1.1 6.8 22.2 30 30 0.96 75

036 460-3-60 432 504 5.7 39 0.6 6.8 14.8 20 20 0.96 75

036 575-3-60 540 630 4.7 31 0.6 6.8 13.3 20 20 0.96 75

042 208/230-1-60 187 253 20 104 1.3 9.1 35.4 50 50 0.96 40

042 208/230-3-60 187 253 13.9 88 1.3 9.1 27.8 40 40 0.96 75

042 460-3-60 432 504 6.4 44 0.7 9.1 18.5 25 25 0.96 75

042 575-3-60 540 630 5.4 34 0.6 9.1 16.8 25 25 0.96 75

048 208/230-1-60 187 253 23.4 126 1.9 9.1 39.5 60 60 0.96 40

048 208/230-3-60 187 253 13 93 1.9 9.1 26.5 35 35 0.96 75

048 460-3-60 432 504 6.4 46.5 1.0 9.1 18.4 25 25 0.96 75

048 575-3-60 540 630 5.1 37.2 0.8 9.1 17.3 25 25 0.96 75

060 208/230-1-60 187 253 25 150 2.8 9.1 43.2 60 60 0.96 40

060 208/230-3-60 187 253 17.3 123 2.8 9.1 33.5 45 45 0.96 75

060 460-3-60 432 504 8.4 70 2.8 9.1 22.6 30 30 0.96 75

060 575-3-60 540 630 7.0 53 2.8 9.1 21.2 30 30 0.96 75

1. Rated in accordance with ARI Standard 110, utilization range “A”. 2. Dual element, time delay type.

Page 20 of the York DNP030 user manual — RIGHT SIDE 12”
20ページ · クリックして拡大
20ページ

V ENTAIROUTLETHOOD

BLOWERSERVICE

ACCESSCOMPARTMENT PANEL GASSUPPLY1-1/4"DIA. HOLE(1/2"NPTI CONNECTION)

C ONDENSERCOIL

UNITCONDENSATE CONNECTION3/4"NPTI (TRAPRECOMMENDED)

B H IGHVOLTAGE CONN.1-3/8"DIA. KNOCKOUT

HIGHVOLTAGE CONN.7/8"DIA. KNOCKOUT

REFRIGERANT CONNECTIONS

GASSUPPLY1-1/4"DIA. KNOCKOUT(1/2"NPTI CONNECTION)

COMBUSTIONAIR INLETLOUVERS

FRONT

LOWVOLTAGECONN. 1-3/8"DIA.KNOCKOUT X7/8"HOLE

11 12-3/4 49-1/8

GAS/ELECTRICCONTRO L

S ERVICEACCESS COMPARTMENTPANEL

(OVERALL)

( OVERALL)

All dimensions are in inches. They are subject to change with- out notice. Certified dimensions will be provided upon request.

FIGURE 5 - UNIT DIMENSIONS - FRONT

TABLE 15: UNIT DIMENSIONS FRONT

TABLE 16: UNIT MINIMUM CLEARANCES 1 2

DIMENSION

UNIT SIZE

CLEARANCES

“A” “B”

FRONT 36”

024, 030, 036 33-1/2 18-1/4

BACK 0”

042, 048, 060 41-1/2 23-1/8

LEFT SIDE (Filter-Access) 24”

RIGHT SIDE 12”

BELOW UNIT 3

ABOVE UNIT 4

36” (For Condenser Air Discharge)

1. A 1” clearance must be provided between any combustible material and the supply air ductwork. 2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
4. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
Show 8 more labels / short text on this page
2-3/8 · 3-3/4 · 2-1/2 · 5-3/8 · 1-1/2 · 47-1/4 · 2-5/8 3-1/3 · 0”
Page 21 of the York DNP030 user manual — FIGURE 7 - UNIT DIMENSIONS - BACK & BOTTOM
21ページ · クリックして拡大
21ページ

8-7/8 11-7/8 19-1/4 HIGH VOLTAGE CONN. 1-3/32" DIA. KNOCKOUT FRONT

GAS SUPPLY 1-5/8" DIA. KNOCKOUT (1/2" NPTI CONNECTION)

LOW VOLTAGE CONN.

" DIA. KNOCKOUT /8 7

CONDENSATE DRAIN 3/4"' NPTI

FIGURE 6 - UNIT DIMENSIONS - FRONT & BOTTOM

FIGURE 7 - UNIT DIMENSIONS - BACK & BOTTOM

Show 7 more labels / short text on this page
4-5/8 · 26-3/4 · · · · ·
Page 22 of the York DNP030 user manual — FIGURE 9 - TYPICAL ROOF CURB INSTALLATION
22ページ · クリックして拡大
22ページ

!

! " "

FIGURE 8 - TYPICAL SLAB ON GROUND INSTALLATION

! " "

!

FIGURE 9 - TYPICAL ROOF CURB INSTALLATION

Show 4 more labels / short text on this page
· · ·
Page 23 of the York DNP030 user manual — "D"
23ページ · クリックして拡大
23ページ

FIGURE 10 - TYPICAL DUCT APPLICATIONS

TABLE 17: UNIT WEIGHTS AND CENTER OF GRAVITY

SHIPPING

OPERATING

CORNER WEIGHTS

ROOF CURB

UNIT SIZE

WEIGHT

WEIGHT

(location, lbs.) ECONOMIZER

(lbs.)

(lbs.)

(lbs.)

(lbs.) “A” “B” “C” “D”

024, 030, 036 400 395 100 96 98 101 40 8” - 70 14” - 75 042, 048, 060 475 470 133 130 102 104

"D"

CENTER OF

FRONT

GRAVITY

OF UNIT

"C"

"B"

FIGURE 11 - UNIT CENTER OF GRAVITY

49-1/8 25 25 · 47-1/4

Page 24 of the York DNP030 user manual — FIGURE 13 - ROOF CURB CROSS SECTION
24ページ · クリックして拡大
24ページ

% # & '

# $

#

% # & '

FIGURE 12 - ROOF CURB DIMENSIONS 1

& ' &

& ( " !

!

FIGURE 13 - ROOF CURB CROSS SECTION

1. 8” Roof curb also available
Show 4 more labels / short text on this page
· · ·
Page 25 of the York DNP030 user manual — FIGURE 14 - TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY)
25ページ · クリックして拡大
25ページ

FIGURE 14 - TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY)

Page 26 of the York DNP030 user manual — OFF
26ページ · クリックして拡大
26ページ

3H,5H

10G

15H

17H

100/BK

035-18578D000 REV. C BEFORE SERVICING THIS UNIT CAUTION - OPEN ALL DISCONNECTS

L K J H G F E D C B A

T1

230V PRI

COMPR

MOTOR OD FAN

(SEE NOTE 5) 805/BL

ASCT

75 VA SEC 24V

107/PR

HSP

PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.

S

R

(OPTIONAL ACCESSORIES - SEE NOTE 5)

CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL

AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

100/BK

110/BK

BLK

BRN

PRP

FS HP LP

201/BR

4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.

107/PR

101/BK

103/BR

102/Y

110/BK

MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1. 6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION

RC2

7 2 802/BK 803/BK 804/BK

MOTOR ID FAN

801/BL (SEE NOTE 5)

BLU

BLU

7. SHUNT CONTACT ALSO USED WITH CRANKCASE HEATER. (OPTIONAL)

RC1

806/BR

ID MOTOR CONTROLLER

P3

104/R

B LR A

807/BL

1 P2

S3 S2

GAS

VALVE

3. MOTORS ARE INHERENTLY PROTECTED.

M2-2

M2-1

240V/BK

240V/PR

T1

T2

T2

T1

M1-1

M1-2

M1

PRP

BLK

108/PR

GRN

800/Y

230-1-60 MOTOR DRAFT

S5/P5

211/PR PS

LR

LUG GND

P4/S4

108/PR

208/230-1-60 POWER SUPPLY

SEE DETAIL "A"

COOL/BLU

W1/WHT

NOTES:

HEAT/BLK

C2/BRN

C1/BRN

Y1/YEL

R/RED

214/BR

224/R

90 SEC 60 SEC

180 SEC 120 SEC

LS 213/R ALS 205/R

SETTING FACTORY

220/O

COOL/BLU

224/R

M2

221/BR

201/BR

200/R

S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE CN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD

S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROL S3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE

S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL

COOL/BLU TO: WIRE CONNECT

HEAT/BK

1000 (ARI RATING) TB2-A -030

1250 TB2-B

1200 (ARI RATING) TB2-A

1350 TB2-B

1350 (ARI RATING) TB2-A -042

1500 TB2-B

1400 (ARI RATING) TB2-A

1600 TB2-B

BOARD CONTROL

203/BR

UNUSED

MOTOR

LEADS

XFMR

210/BL

208/PR

207/Y

209/BK

206/R

202/Y

DI

NEUTRAL

INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*

COOL

CN1

P1

(CFM) AIRFLOW FOR COOLING

COMBUSTION BLOWER POSTPURGE: 5 SEC

INDOOR BLOWER COOL ON DELAY: 3 SEC

INDOOR BLOWER COOL OFF DELAY: 30 SEC

INDOOR BLOWER HEAT ON DELAY: 30 SEC

* BLACK SQUARE INDICATES SWITCH POSITION

"SPEED" CONNECTIONS FOR COOLING BLOWER SEE TABLE 1

HUM

EAC

HEAT

6 5 3 2 1 4

FOR COOLING AIRFLOW BLOWER CONNECTIONS TABLE 1

N

N

S

204/O RS

CONTROL BOARD SETTINGS:

213/R

ON DELAY

R/RED

Y

UNIT SIZE

OFF

TB2

B

TB1

G

Y

W

R

CONTROL SETPOINT (DEG F) UNIT SIZE DEVICE

+/- CLOSE +/- OPEN

030 2 TUBE LS 140 110 6 9

030 3 TUBE LS 160 130 6 9

036 2 TUBE LS 140 110 6 9

LS 160 130 6 9

036 4 TUBE LS 160 130 6 9

042 3 TUBE LS 140 110 6 9

042 4 TUBE LS 140 110 6 9

048 3 TUBE LS 150 120 6 9

048 4 TUBE LS 175 145 6 9

048 5 TUBE LS 160 130 6 9

ID FAN

MOTOR

TEMPERATURE CONTROLS

CONNECTION DIAGRAM ELEMENTARY DIAGRAM COOLING UNIT WITH GAS HEAT

AUTO

COOL

W HEAT

ON

Y

OFF

RS

ALS

RS

ALS

RS

ALS

RS

ALS

RS

ALS

RS

ALS

RS

ALS

RS

ALS

RS

ALS

RS

ALS

OPEN @ 7 PSIG LP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

RC1/RC2 COMP. START & OUTDOOR FAN RUN CAPACITOR

ON CONTROL BOARD, 24-1-60, 18VA MAX EAC ELECTRONIC AIR CLEANER RELAY OUTPUT

ACCESSORY) OPENS @ 380 PSIG HP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE F FS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

BOARD, 24-1-60, 18VA MAX HUM HUMIDIFIER RELAY OUTPUT ON CONTROL

036 3 TUBE

LR LOCK OUT RELAY (OPTIONAL ACCESSORY)

ROOM THERMOSTAT 24V CONNECTIONS

G

M1 CONTACTOR, COMPR & OD FAN

M2 CONTACTOR, DRAFT INDUCER MOTOR

.193 IWC NOM (.33 IWC MAX) PS PRESSURE SWITCH - MAKES @

IDENTIFIED TERMINAL ON CAPACITOR

FIELD WIRING OPTIONAL WIRING AND DEVICES

CCH CRANKASE HEATER (OPTIONAL)

T1

(OPTIONAL ACCESSORY) ASCT ANTI-SHORT CYCLE TIMER

HSP HOT SURFACE TO PILOT

T1 TRANSFORMER, 24V, 40 VA

MOTOR "SPEED" CONNECTIONS TB2 TERMINAL BLOCK, 24V, ID

FACTORY WIRING AND DEVICES

THERMOSTAT ROOM

S/P CONFIGURATION

D/P CONFIGURATION

ALS AUXILARY LIMIT SWITCH

TB1 ON CONTROL BOARD

GND/GRN

240V/PRP

240V/BLK

OPTIONAL CCH

BLK CCH

BLK

BLK CCH

BLK

T2 L2 M1-2

DETAIL "A"

COMPR COMPRESSOR

LS LIMIT SWITCH

RS ROLLOUT SWITCH

R

LEGEND:

S5

S4 ID MOTOR CONTROLLER

8 7 6 5 4 3 2 1

C1/BRN

HSP

YEL Y1/

15 14 13 12 11 10 9

213/R

224/R

220/O

221/BR

214/BR

201/BR

200/R

CONTROL BOX

213/R 224/R 214/BR

/BLU COOL

PRP

BLK

101/BK

GRN

BLU BLK

CLEAR

BLU

R/RED

102/Y

104/R

BLK

UNUSED

MOTOR

LEADS

XFMR

BRN C2/

201/BR 200/R

DI

DRAFT

MOTOR

/BLK HEAT

100/BK 107/PR

PRP

WHT W1/

C2/BRN

HUM

EAC

N

N

204/O

209/BK

BRN C1/

T1

SEC

2 S

207/Y

210/BL

802/BK

800/Y 202/Y

CLEAR

BLU

BLU

BLK

T2

T1

T2

T1

COOL

HEAT

CN1

206/R

CCH BLK

BLK BRN PRP

OUTDOOR

MOTOR

M1

CONTROL BOARD

FAN

B

M2

B

(SEE NOTE 5) LR

7 B

GAS HEAT SECTION

S3

(SEE NOTE 5) 202/Y

Y1/YEL

W1/WHT

208/PR

GAS VALVE

211/PR

210/BL

209/BK

221/BR

203/BR

103/BR

PRP

207/Y

804/BK

802/BK

804/BK

220/O

TB2

800/Y

801/BL

FS 803/BK

HP 803/BK

LP 805/BL

HERM RC1/RC2

B

DELAY

Y

G

Y

W

R

S2

TB1

240V/PRP

108/PR

240V/BLK

110/BK

108/PR

107/PR

110/BK

100/BK

"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2

OFF

801/BL 805/BL

806/BR

213/R

204/O

206/R

211/PR

BRN

FAN

ALS 205/R

213/R

205/R

208/PR

104/R

R/RED

G/GRA

103/BR 101/BK

S C

LUG GND

203/BR

202/Y

(SEE NOTE 5) ASCT

COMPR

R

102/Y

807/BL

RS

LS

PS

FIGURE 15 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-1-60 POWER SUPPLY)

Show 23 more labels / short text on this page
230-1-60 · 230-1-60 · 230-1-60 · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- ---
Page 27 of the York DNP030 user manual — FIGURE 16 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY)
27ページ · クリックして拡大
27ページ
York DNP030 — Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY diagram (page 27)
図 7 · Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY

FIGURE 16 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY)

Page 28 of the York DNP030 user manual — OFF
28ページ · クリックして拡大
28ページ

3H,5H

10G

15H

17H

100/BK

035-18845D000 REV.C BEFORE SERVICING THIS UNIT CAUTION - OPEN ALL DISCONNECTS

L K J H G F E D C B A

T1

(SEE NOTE 5) 805/BL

ASCT

230V PRI

CB 75 VA SEC 24V

COMPR

MOTOR OD FAN

107/PR

PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.

HSP

(OPTIONAL ACCESSORIES - SEE NOTE 5)

CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL

AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING

4. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE SIZE AND MINIMUM CIRCUIT AMPACITY.

100/BK

110/BK

BLK

BRN

PRP

FS HP LP

201/BR

107/PR

121/BK

123/BL

126/Y

110/BK

MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1. 6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION

7 2 802/BK 803/BK 804/BK

MOTOR ID FAN

RC2

801/BL (SEE NOTE 5)

200/R

BLU

BLU

105/BL

806/BR

ID MOTOR CONTROLLER

3.2 AMP

P3

B LR A

S3 S2

807/BL

M2-2

M2-1

240V/PRP

1 P2

GAS

VALVE

3. MOTORS ARE INHERENTLY PROTECTED.

240V/BLK

T1

T2

T3

T2

T1

M1-1

M1-2

M1-3

M1

PRP

BLK

GRN

108/PR

211/PR PS

800/Y

230-1-60 MOTOR DRAFT

LR

LUG GND

P4/S4

108/PR

COOL/BLU

W1/WHT

NOTES:

208/230-3-60 POWER SUPPLY

HEAT/BLK

C2/BRN

C1/BRN

Y1/YEL

R/RED

214/BR

224/R

90 SEC 60 SEC

180 SEC 120 SEC

LS 213/R ALS 205/R

SETTING FACTORY

224/R

220/O

M2

221/BR

S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROL S3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE

S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL

HEAT/BK

COOL/BLU

201/BR

212/R

S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE CN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD

BOARD CONTROL

UNUSED

MOTOR

LEADS

210/BL

208/PR

209/BK

COOL/BLU TO: WIRE CONNECT

203/BR

202/Y

DI

XFMR

207/Y

206/R

1000 (ARI RATING) TB2-A -030

1250 TB2-B

1200 (ARI RATING) TB2-A

1350 TB2-B

1350 (ARI RATING) TB2-A -042

1500 TB2-B

1400 (ARI RATING) TB2-A

1600 TB2-B

INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*

NEUTRAL

* BLACK SQUARE INDICATES SWITCH POSITION

COOL

HEAT

CN1

P1

FOR COOLING AIRFLOW BLOWER CONNECTIONS TABLE 1

COMBUSTION BLOWER POSTPURGE: 5 SEC

INDOOR BLOWER COOL ON DELAY: 3 SEC

INDOOR BLOWER COOL OFF DELAY: 30 SEC

INDOOR BLOWER HEAT ON DELAY: 30 SEC

"SPEED" CONNECTIONS FOR COOLING BLOWER SEE TABLE 1

HUM

EAC

N

N

6 5 3 2 1 4

(CFM) AIRFLOW FOR COOLING

S

204/O RS

CONTROL BOARD SETTINGS:

ON DELAY

R/RED

Y

213/R

UNIT SIZE

OFF

TB2

B

TB1

G

Y

W

R

ID FAN

MOTOR

CONNECTION DIAGRAM ELEMENTARY DIAGRAM COOLING UNIT WITH GAS HEAT

OPEN @ 7 PSIG LP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)

AUTO

COOL

OFF

W HEAT

ACCESSORY) OPENS @ 380 PSIG HP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE F FS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)

ON

Y

ON CONTROL BOARD, 24-1-60, 18VA MAX EAC ELECTRONIC AIR CLEANER RELAY OUTPUT

BOARD, 24-1-60, 18VA MAX HUM HUMIDIFIER RELAY OUTPUT ON CONTROL

LR LOCK OUT RELAY (OPTIONAL ACCESSORY)

+/- CLOSE +/- OPEN

030 2 TUBE LS 140 110 6 9

030 3 TUBE LS 160 130 6 9

036 2 TUBE LS 140 110 6 9

LS 160 130 6 9

036 4 TUBE LS 160 130 6 9

042 3 TUBE LS 140 110 6 9

042 4 TUBE LS 140 110 6 9

048 3 TUBE LS 150 120 6 9

048 4 TUBE LS 175 145 6 9

048 5 TUBE LS 160 130 6 9

IDENTIFIED TERMINAL ON CAPACITOR

ROOM THERMOSTAT 24V CONNECTIONS

CONTROL SETPOINT (DEG F) UNIT SIZE DEVICE

M1 CONTACTOR, COMPR & OD FAN

M2 CONTACTOR, DRAFT INDUCER MOTOR

.193 IWC NOM (.33 IWC MAX) PS PRESSURE SWITCH - MAKES @

RC2 OUTDOOR FAN RUN CAPACITOR

(OPTIONAL ACCESSORY) ASCT ANTI-SHORT CYCLE TIMER

MOTOR "SPEED" CONNECTIONS TB2 TERMINAL BLOCK, 24V, ID

FACTORY WIRING AND DEVICES

OPTIONAL WIRING AND DEVICES

G

TEMPERATURE CONTROLS

ALS AUXILARY LIMIT SWITCH

HSP HOT SURFACE TO PILOT

T1 TRANSFORMER, 24V, 75 VA

TB1 ON CONTROL BOARD

CB CIRCUIT BREAKER

THERMOSTAT ROOM

COMPR COMPRESSOR

RS ROLLOUT SWITCH

GND/GRN

240V/PRP

240V/BLK

ALS

ALS

ALS

ALS

ALS

ALS

ALS

ALS

ALS

ALS

LS LIMIT SWITCH

FIELD WIRING

R

RS

RS

RS

RS

RS

RS

RS

RS

RS

RS

LEGEND:

036 3 TUBE

S5

S4 ID MOTOR CONTROLLER

8 7 6 5 4 3 2 1

15 14 13 12 11 10 9

213/R

224/R

220/O

221/BR

214/BR

C1/BRN

201/BR

212/R

HSP

YEL Y1/

213/R 214/BR

CONTROL BOX

126/Y

105/BL

123/BL

121/BK

BLU BLK

BLU

/BLU COOL

BK

GRN

CLEAR

R/RED

PRP

BLK

UNUSED

MOTOR

LEADS

XFMR

BRN C2/

201/BR 200/R

DI

DRAFT

MOTOR

/BLK HEAT

100/BK 107/PR

209/BK

PRP

WHT W1/

C2/BRN

HUM

EAC

N

N

204/O

BRN C1/

T1

SEC

2 S

207/Y

210/BL

802/BK

800/Y 202/Y

CLEAR

T2

T1

T3

T2

T1

COOL

HEAT

CN1

206/R

BLU

BLU

BLK BRN PRP

OUTDOOR

MOTOR

CONTROL BOARD

FAN

B

M2

M1

(SEE NOTE 5) LR

7 B

GAS HEAT SECTION

S3

Y1/YEL

W1/WHT

208/PR

GAS VALVE

211/PR

207/Y

210/BL

209/BK

804/BK

802/BK

804/BK

221/BR

220/O

B

FS 803/BK

HP 803/BK

LP 805/BL

TB2

B

800/Y

801/BL

S2

DELAY

Y

TB1

G

Y

W

R

100/BK

110/BK

105/BL

240V/PRP

108/PR

240V/BLK

110/BK

108/PR

(SEE NOTE 5) 202/Y 107/PR

"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2

OFF

801/BL 805/BL

806/BR

213/R

204/O

206/R

208/PR

211/PR

BRN

PRP

R/RED

ALS 205/R

213/R

205/R

123/BL 121/BK

203/BR

203/BR

202/Y

224/R

(SEE NOTE 5) ASCT

LUG GND

RC2

G/GRA

200/R

CB

COMPR

126/Y

212/R

807/BL

RS

LS

PS

FIGURE 17 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-3-60 POWER SUPPLY)

Show 23 more labels / short text on this page
230-3-60 · 230-1-60 · 230-1-60 · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- --- · --- ---
Page 29 of the York DNP030 user manual — FIGURE 18 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY)
29ページ · クリックして拡大
29ページ
York DNP030 — Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY diagram (page 29)
図 8 · Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY

FIGURE 18 - TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY)

Page 30 of the York DNP030 user manual — FIGURE 19 - TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY)
30ページ · クリックして拡大
30ページ
York DNP030 — Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY diagram (page 30)
図 9 · Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY

FIGURE 19 - TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY)

Page 31 of the York DNP030 user manual — FIGURE 20 - TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY)
31ページ · クリックして拡大
31ページ
York DNP030 — Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY diagram (page 31)
図 10 · Table 17: UNIT WEIGHTS AND CENTER OF GRAVITY

FIGURE 20 - TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY)

Page 32 of the York DNP030 user manual — FIGURE 21 - TYPICAL WIRING DIAGRAM LEGEND
32ページ · クリックして拡大
32ページ

TYPICAL WIRING DIAGRAM NOTES

5. Select indoor blower cooling speed from unit wiring diagram Table 1. Heating speed is preset at the factory.
1. All field wiring to be accomplished following city, local and/or national codes in effect at time of installation of this unit.
6. If both LR and ASCT are present, wire 801/BL and 805/ BL are connected to ASCT-3 if LR only is present wire 801/BL and 805/BL are connected to M1 coil. If ASCT only is present wire 202/Y is connected to ASCT-3. If neither LR or ASCT are present, Wire 202/Y is connect to M1 coil.
2. Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation if any of the wire as supplied with this unit must be removed it must be replaced with type 105°C, 600V wire or equivalent clearly renumbered for identification. Verify proper operation after servicing.
7. Shunt contact also used with crankcase heater. (Optional).
3. Motors are inherently protected.
4. See unit nameplate for maximum fuse size and minimum circuit ampacity.

Open all disconnects before servicing this unit.

LEGEND :

ALS ASCT

AUXILLARY LIMIT SWITCH ANTI-SHORT CYCLE TIMER (OPTIONAL ACCESSORY) COMPRESSOR

COMPR EAC

ELECTRIC AIR CLEANER RELAY OUTPUT

ON CONTROL BOARD, 24-1-60, 18VA MAX. FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 250 F HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 380 PSIG HOT SURFACE TO PILOT HUMIDIFER RELAY OUTPUT ON CONTROL BOARD, 24-1-60, 18VA MAX. LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG LOCK OUT RELAY (OPTIONAL ACCESSORY) LIMIT SWITCH CONTACTOR, COMPR. & O.D.FAN CONTACTOR, DRAFT INDUCER MOTOR PRESSURE SWITCH MAKES @ .193 IWC NOM. (.33 IWC MAX.) COMPR. START & OUTDOOR FAN RUN CAPACITOR ROLL OUT SWITCH TRANSFORMER, 24V, 40VA TRANSFORMER, 480/240 VOLT TERMINAL BLOCK, 24V, I.D. MOTOR "SPEED" CONNECTION IDENTIFIED TERMINAL ON CAPACITOR

FS

HP

HSP HUM

LP

LR LS M1 M2 PS

RC1/RC2 RS T1 T2 TB2

ROOM THERMOSTAT 24V CONNECTIONS TB1 ON CONTROL BOARD FACTORY WIRING AND DEVICES OPTIONAL WIRING AND DEVICES

FIELD WIRING

DNP LEGEND WIRING DIA.

FIGURE 21 - TYPICAL WIRING DIAGRAM LEGEND

Page 33 of the York DNP030 user manual — Refrigerant Circuit and Refrigerant Safety Components:
33ページ · クリックして拡大
33ページ

MECHANICAL SPECIFICATIONS

without modification to building structure, duct work and base unit. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards, with 3/4” NPTI copper, ridged mount connection.

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s DNP is a unit that gives you the flexibility and choices you need in today’s market. These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The gas fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are avail- able in natural gas with field conversion to propane.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be direct drive, multi-speed design. Job site selected (BHP) brake horsepower shall not exceed the motors nameplate horsepower rating. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bear- ings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be “Slip Track” (slide-out) design for easy removal and cleaning.

DESCRIPTION

Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heating units, designed for outdoor mounted installation. For SEER ratings, refer to technical literature. They shall have built in, equal size, field convertible duct connections for down discharge supply/return or horizontal discharge supply/return. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility cer- tified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. The heating performance shall be rated to DOE and GAMA test procedures. Units shall be CSA listed and classi- fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/ CAN/CSA No. 236-M90 conditions.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.

REFRIGERANT COMPONENTS

Compressors:

a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or - 10% of the unit nameplate voltage.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTM- B117 standards. The unit top shall be a single piece “Water Shed” design, with drip edges and no-seam corners to pro- vide optimum water integrity. Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel after installation. Indoor blower section shall be insulated with up to 3/4” thick, aluminum, foil faced insulation, fastened to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily remov- able for servicing and maintenance, with built-in lift handles. Unit shall be built on a formed, “Super-Structure” design base pan, with embossments at critical points to add strength, rigidity and aid in minimizing sound. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, for truck access and proper sealing on roof curb applications. Base rails shall be removable, when required, to lower unit height. Filters shall be furnished and be accessible through a removable access door, sealed air- tight. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams

b. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally iso- lated on a dedicated, independent mounting.

Coils:

a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.

b. Evaporator coil shall be of the direct expansion, blow through design, while condenser coil shall be draw through design.

Refrigerant Circuit and Refrigerant Safety Components:

a. Shall include independent thermal expansion devices (TXV).

b. Shall include filter/strainer to eliminate any foreign matter.

Page 34 of the York DNP030 user manual — UNIT OPERATING CHARACTERISTICS
34ページ · クリックして拡大
34ページ

UNIT OPERATING CHARACTERISTICS

ELECTRICAL REQUIREMENTS

Unit shall be capable of starting and running at 125º F out- door temperature, exceeding maximum load criteria ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 45º F outdoor tempera- ture. Accessory low ambient kit shall be available for opera- tion to 0º F.

All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

Page 35 of the York DNP030 user manual — UNIT OPERATING CHARACTERISTICS
35ページ · クリックして拡大
35ページ
Page 35 of the York DNP030 user manual — UNIT OPERATING CHARACTERISTICS
Page 36 of the York DNP030 user manual — Unitary 5005 Norman Products York OK Group Drive 73069
36ページ · クリックして拡大
36ページ

Subject to change without notice. Printed in U.S.A. 036-21366-007-A-1205 Copyright © 2005 by Unitary Products Group. All rights reserved. Supersedes: 036-21366-006-A-1005

Unitary 5005 Norman Products York OK Group Drive 73069