DESCRIPTION
York® Affinity™ Series packaged cooling/heating air condi- tioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation.
AFFINITY™ SERIES
The gas-fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are avail- able in natural gas with field conversion to propane.
AIR COOLED AIR CONDITIONERS
2 THRU 5 NOMINAL TON





FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION 1 STANDARD FEATURES/BENEFITS 3 FIELD-INSTALLED ACCESSORIES 4 TYPICAL WIRING DIAGRAM NOTES 32 MECHANICAL SPECIFICATIONS 33
19 TYPICAL WIRING DIAGRAM D*NP 030-048 (460/575-3-60 POWER SUPPLY) 30
20 TYPICAL WIRING DIAGRAM D*NP 060 (460/575-3-60 POWER SUPPLY) 31
21 TYPICAL WIRING DIAGRAM LEGEND 32
LIST OF TABLES
Fig# Pg#
1 PRODUCT NOMENCLATURE 2
2 UNIT COMPONENT LOCATION 6
1 PHYSICAL DATA 6
2 RATINGS COOLING/GAS HEATING 7
4 POWER WIRING FIELD DIAGRAM 19
3 DNP024 COOLING CAPACITIES - 2 TON 8
5 UNIT DIMENSIONS - FRONT 20
4 DNP030 COOLING CAPACITIES - 2-1/2 TON 10
6 UNIT DIMENSIONS - FRONT & BOTTOM 21
5 DNP036 COOLING CAPACITIES - 3 TON 11
7 UNIT DIMENSIONS - BACK & BOTTOM 21
6 DNP042 COOLING CAPACITIES - 3-1/2 TON 12
7 DNP048 COOLING CAPACITIES - 4 TON 13
9 TYPICAL ROOF CURB INSTALLATION 22
8 DNP060 COOLING CAPACITIES - 5 TON 14
10 TYPICAL DUCT APPLICATIONS 23
9 TWO TON AIR PERFORMANCE 15
11 UNIT CENTER OF GRAVITY 23
10 SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 16
12 ROOF CURB DIMENSIONS 24
13 ROOF CURB CROSS SECTION 24
11 BOTTOM SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS 17
14 TYPICAL WIRING DIAGRAM D*NP 024 (208/230-1-60 POWER SUPPLY) 25
12 ADDITIONAL STATIC PRESSURE RESISTANCE - 2, 2-1/2, 3 TON 18
15 TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230- 1-60 POWER SUPPLY) 26
13 ADDITIONAL STATIC PRESSURE RESISTANCE - 3-1/2, 4 AND 5 TON 18
16 TYPICAL WIRING DIAGRAM D*NP 060 (208/230-1-60 POWER SUPPLY) 27
14 ELECTRICAL DATA 19
15 UNIT DIMENSIONS FRONT 20
17 TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230- 3-60 POWER SUPPLY) 28
16 UNIT MINIMUM CLEARANCES 20
18 TYPICAL WIRING DIAGRAM D*NP 060 (208/230-3-60 POWER SUPPLY) 29
17 UNIT WEIGHTS AND CENTER OF GRAVITY 23
' 1 3 1
%78+
1 1DWXUDO*DV+HDW,QVWDOOHG
%78+ %78+

will build-up. The condensate pan conforms to ASHRAE 62- 89 standards (Ventilation for Acceptable Indoor Air Quality).
OPERATING EFFICIENCY - All units provide high operating efficiencies and have a minimum AFUE of 80% and SEER of 13.0. All efficiencies exceed legislated minimum levels.
CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI cop- per connection is more durable over time. The connection is rigidly mounted to assure proper fit and leak tight seal.
ON SITE FLEXIBILITY - All model sizes share a common, compact design cabinet in a single footprint. The installer has the flexibility of setting one curb and placing the proper ton- nage unit on that curb after the internal load has been deter- mined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibility with less inventory.
DURABLE FINISH - With a heavy duty cabinet made of pow- der-painted, galvanized steel the neutral color blends into surrounding areas. The powdered paint provides a better paint to steel bond, which resists corrosion and rust creep. The special primer formulas and glossy finish insures less fading when exposed to sunlight and offers a more attractive on site appearance. This paint finish meets ASTM-B117 stan- dards for 1000 hours salt spray rating. The highest in the industry.
LOWER INSTALLATION COST - Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof, plus, the installer can fit this unit between the wheel wells of full size pick-up truck. All models are well under 500 pounds.
FULL PERIMETER BASE RAILS - The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the inch high base rails may be removed on location.
All units are completely wired, charged with R-22 and tested prior to shipment. Unique test stations using a new state of the art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers at assembly. Vital run test statistics such as system pressure, motor currents, air velocity and tem- perature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance.
MORE ATTRACTIVE APPEARANCE - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square footage on installation and provides a wider variety of installations. The one piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance. The cabinet panels have a non-fibrous insulation that will not release insulation fibers into conditioned area.
Equal size, side supply and return duct connections allows easy hook-up of ducts to match low crawl spaces without transition pieces.
UTILITY CONNECTIONS MADE EASY - Gas and electric utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
TOP DISCHARGE - The top discharge condenser fan does not disrupt neighboring areas or dry-out vegetation surround- ing the unit. The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications.
CONVERTIBLE AIRFLOW DESIGN - The bottom duct open- ings are covered when they leave the factory ready to be used for a side supply / side return application. If a bottom supply / bottom return application is desired, you simply remove the two panels from the bottom of the unit and place them in the side supply / side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.
CONDENSER COIL GRILLE - A multi-piece totally enclosed, rigidly mounted condenser coil grille provides protection from objects after installation and provides protection during transit.
LOW OPERATING SOUND LEVEL - The upward air flow carries the normal operating noise up and away from the liv- ing area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compres- sor operating sounds. The unique formed base pan also aids in sound alterations with it's Super-Structure design. This design strategically places embossments in the pan for opti- mum strength and rigidity.
CONDENSATE PAN - A non-corrosive, long-lasting, water- tight pan is positioned below the evaporator coil to collect and drain all condensate. Less collection of stagnate condensate

FAN SYSTEM - All 2-1/2, 3, 3-1/2 and 4 ton models operate over a wide range of design conditions with a constant CFM, electrically commutated (ECM) fan motor. These units easily match all types of applications and provide greater on site flexibility to match comfort requirement. These models have 2 cooling speeds and a single heating speed. The cooling speed is factory set and can be field adjusted to a second speed. The heating speed is factory set to maintain mid point rise at the units heating input. It cannot be field adjusted. This allows maximum comfort conditions.
LOW MAINTENANCE - Long life, permanently lubricated condenser and evaporator fan motor bearings need no annual maintenance adding greater reliability to the unit. Blower assembly can be easily cleaned by the unique Slip- Track slide-out blower assembly.
SECURED SERVICE ACCESS PORTS - Protected, exter- nally mounted, re-usable service access ports are provided on both the high and low lines for ease of evacuating and charging the system. No final field mounting required.
Two ton models operate over a wide range of design condi- tions with a 3-speed direct-drive fan motor. These single phase models have the Comfort-Match system that allows different speed taps for heating or cooling operations.
EASY SERVICE ACCESS - A large, single panel covers the electrical and gas controls makes servicing easy. The blower compartment has an additional large panel with a built-in handle tab. Removing this panel will allow the blower assem- bly to slide-out for easy removal for maintenance and ease of trouble shooting.
SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip. An additional set of pin connectors is also pro- vided to simplify the field interface of external controls. Mate- n-lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted on a Control-Tilt control panel to allow the access cover to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
REPLACEMENT PARTS - The installer requires no special training to replace any of the components of these units and does not need to maintain an inventory of unique parts.
SYSTEM INTEGRATION - Each unit has the internal ability to integrate an electronic air cleaner or humidifier to work in conjunction with the base unit.
PROTECTED COMPRESSOR - The compressor is internally protected against high pressure and temperature. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the com- pressor if undesirable operating conditions occur.
LOW NOx KIT - Kit includes all the necessary hardware and instructions to field convert units to reduce emissions to less than 40 nanogram per Joule. California requirement on single phase models only.
PROPANE CONVERSION KIT - Kit includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural gas to propane.
EXCLUSIVE COIL DESIGN - Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability.
HIGH ALTITUDE CONVERSION KIT (Natural Gas/Propane) - Kit includes all necessary labels and instructions to field alter units with natural gas/propane for installations above 2000 feet. Burner orifices must be obtained from Source 1 Parts. Propane Conversion Kit must be obtained separately.
HEAT EXCHANGERS - Are corrosion-resistant, aluminized- steel tubular construction to provide long-life, trouble-free operation. The unique blow-through design also assures that condensate does not collect in humid areas when in the cool- ing cycle. This adds to longer heat exchanger life and higher long term efficiencies.
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT - Modu- lating integrated economizer provides simultaneous opera- tion between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available. A built-in barometric relief of 25% is provided.
POST PURGE INDUCED DRAFT COMBUSTION - Exhausts combustion products from the heat exchanger upon comple- tion of the heating cycle to prolong the heat exchanger life.
SELF DIAGNOSTIC FAN CONTROL MODULE - Due to this self diagnostic control, less on site time is required to trouble shoot these units.
HOT SURFACE TO PILOT IGNITION - Provides faster heat delivery. This ignition is highly reliable, durable and elimi- nates nuisance lockouts. Also assures starts in damp condi- tions.
SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb sensor standard in economizer kit. Provides improved econo- mizer operation by sensing the dry bulb temperature from outdoors plus the enthalpy content of the outdoor air.
MULTI PORT IN-SHOT BURNERS - No field adjustment is required to mix the air and gas. These burners are con- structed of high-grade corrosion-resistant, aluminized-steel.
DUAL ENTHALPY SENSOR - Additional sensor to single enthalpy sensor. Sensor senses both the return air tempera- ture dry bulb and humidity in conjunction with the single

enthalpy to determine the most economical mix. Single Enthalpy sensor also required.
50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.
PRESSURE SWITCH UPGRADE KIT - Contains screw in type High pressure, Low Pressure/Loss of Charge switch, freeze protection switch and lockout relay. Switches are placed onto existing scharder ports located in the unit by fur- nished adapters. When abnormal conditions are sensed through the pressure switches, the unit will lock out prevent- ing any further operation until reset or problem is corrected. Package agency approved.
RECTANGLE TO ROUND ADAPTERS - Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current duct openings on the base unit. Transition is from side square duct opening to 14" round duct opening.
ROOF CURBS - NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also pro- vides seal strip to assure a water tight seal. 8 and 14 inch high roof curbs are available.
HAIL GUARD KIT - Kit contains protective grilles made of expanded aluminum with full perimeter frame. Sloped hoods are also included to assure maximum protection.
MANUAL OUTDOOR DAMPER - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.
ANTI SHORT CYCLE TIMER - Automatically prevents the compressor from restarting for 5 minutes after cycled off.Not required if Thermostat 2ET07700224 and 2ET04700224 are used.
WALL THERMOSTAT - The units are designed to operate with 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat / single stage cool thermostats - with or without the economizer.
FILTER / FRAME KIT (Single Phase only) - Kit contains the necessary hardware to field install return air filters into the base unit. Pre-cut filter racks and appropriate cleanable stan- dard size filters are shipped in one kit. The filter rack is suit- able for either 1" or 2" filters. (1" filter is supplied) This kit is available for single phase horizontal or vertical duct applica- tion only. Standard in all 3 Phase models.
LOW AMBIENT KIT - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Stan- dard unit operation 45º F.
TRANSFORMER KIT - Kit provides necessary hardware to provide single phase models from factory furnished 40 VA transformer capability to 75 VA transformer capability. (Required on installations with economizer or motorized damper.)
MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through

CONDENSER
FAN MOTOR
BLOW-THROUGH DESIGN WITH RELIABLE ALUMINIZED STEEL TUBULAR HEAT EX HANGERS C
D
COPPER TUBE/ALUMINUM FIN
EVAPORATOR COIL
HIGHLY EFFICIENT ENHANCED COPPER TUBE/ALUMINUM FIN
LONG LASTING POWDER PAINT
CONDENSER COIL
FINISH
DECORATIVE PROTECTIVE COIL GAURD
REAR AND BOTTOM
HIGH EFFICIENCY
RET R U N AIR AND SUPPLY AIR DUCT OPENINGS
RIGIDLY MOUNTED
HOT SURFACE PILOT
ASSEMBLY
HIGH GRADE ALUMINIZED
HEAVY GAUGE
REMOVABLE
IN-SHOT BURNERS
BASE RAILS
LOW VOLTAGE TERMINAL BLOCK
SELF-DIAGNOSTIC CONTROLS WITH "COMFORT-MATCH" SPEED CONTROL
DIRECT DRIVE BLOWER MOTOR WITH SLIDE-OUT BLOWER ASSEMBLY
AUTOMATIC GAS VALVE (1/2" - 14 NPTI)
HIGH VOLTAGE TERMINAL BLOCK POWER VENTER MOTOR
FIGURE 2 - UNIT COMPONENT LOCATION
TABLE 1: PHYSICAL DATA



125°F





AIR ON EVAPORATOR COIL 1,400 CFM 1,600 CFM WB °F WB °F
OF AIR ON CONDENSER COIL
72 67 62 57 72 67 62 57
NET CAP.
MBH 54.0 49.2 45.6 45.9 55.2 50.4 46.6 46.9
INPUT kW 3.69 3.66 3.62 3.57 3.85 3.83 3.79 3.73
86 35.8 43.7 45.6 45.9 39.1 47.7 46.6 46.9
83 31.7 39.6 44.6 45.3 34.5 43 46.6 46.9 80 27.7 35.6 42.4 43.6 29.8 38.3 45.7 46.9 77 23.6 31.6 38.4 39.5 25.1 33.7 41 42.3
74 19.6 27.5 34.3 35.5 20.5 29 36.3 37.6 71 - 23.5 30.3 31.4 - 24.3 31.7 32.9 68 - 19.4 26.2 27.4 - 19.7 27 28.3
NET CAP.
MBH 51.8 46.8 43.8 44.0 51.9 46.9 43.9 44.2
INPUT kW 4.07 4.04 4.01 3.99 4.21 4.18 4.15 4.12
86 35.4 42.9 43.8 44.0 38.4 46.4 43.9 44.2 83 31.4 38.9 42.8 43.2 33.8 41.7 43.9 44.2
80 27.4 34.9 40.9 41.5 29.1 37.1 43.5 44.2 77 23.3 30.8 36.8 37.5 24.4 32.4 38.8 39.5 74 19.3 26.8 32.8 33.4 19.8 27.7 34.1 34.8
NET CAP.
MBH 48.7 44.3 41.4 41.7 49.2 44.7 41.8 42.1
INPUT kW 4.49 4.45 4.38 4.34 4.63 4.59 4.51 4.48
86 34.1 41.3 41.4 41.7 37.1 4.44 41.8 42.1 83 30.0 37.7 40.7 41.1 32.4 40.6 41.8 42.1 80 26.0 33.6 38.9 39.4 27.8 35.9 41.6 42.1
MBH 1
77 22.0 29.6 34.9 35.3 23.1 31.3 36.9 37.4 74 17.8 25.6 30.8 31.3 18.4 26.6 32.3 32.7 71 - 21.5 26.8 27.3 - 21.9 27.6 28.1
NET CAP.
MBH 45.7 41.8 39.1 39.4 46.4 42.5 39.7 40
INPUT kW 4.91 4.86 4.74 4.70 5.05 5 4.87 4.83
86 32.7 39.7 39.1 39.4 35.8 42.5 39.7 40 83 28.7 36.5 38.7 38.9 31.1 39.5 39.7 40 80 24.6 32.4 37.0 37.2 26.4 34.8 39.7 40
MBH 1
77 20.6 28.4 32.9 33.2 21.8 30.1 35 35.3 74 16.6 24.4 28.9 29.1 17.1 25.5 30.4 30.6 71 - 20.3 24.9 25.1 - 20.8 25.7 26
NET CAP.
MBH 42.7 39.3 36.8 37.0 43.6 40.2 37.6 37.9
INPUT kW 4.3 5.3 5.1 5.0 5.5 5.4 5.2 5.2
86 31.4 38.0 36.8 37.0 34.5 40.5 37.6 37.9
83 27.3 35.3 36.7 36.8 29.8 38.4 37.6 37.9 80 23.3 31.2 35.1 35.1 25.1 33.7 37.6 37.9 77 19.2 27.2 31.0 31.0 20.5 29 33.2 33.2
74 15.2 23.1 27.0 27.0 15.8 24.4 28.5 28.5 71 - 19.1 22.9 23.0 - 19.7 23.8 23.9 68 - 15.1 18.9 18.9 - 15 19.2 19.2

AIR ON EVAPORATOR COIL 1,500 CFM 1,800 CFM WB °F WB °F
OF AIR ON CONDENSER COIL
72 67 62 57 72 67 62 57
NET CAP.
MBH 63.5 57.6 52.7 53.1 64.3 58.3 53.3 53.7
INPUT kW 4.49 4.44 4.38 4.27 4.68 4.63 4.57 4.45
86 39.4 47.5 52.7 53.1 41.4 49.6 53.3 53.7
83 35.0 43.2 50.9 53.1 36.1 44.3 52.0 53.7 80 30.6 38.8 46.5 50.5 30.7 38.9 46.6 50.7 77 26.3 34.4 42.1 46.2 25.4 33.5 41.2 45.3
74 21.9 30.0 37.7 41.8 20.0 28.2 35.9 39.9 71 -- 25.7 33.4 37.4 -- 22.8 30.5 34.6 68 -- 21.3 29.0 33.1 -- 17.4 25.1 29.2
NET CAP.
MBH 60.6 56.0 52.1 51.5 61.2 56.6 52.6 52.0
INPUT kW 4.96 4.90 4.80 4.73 5.12 5.05 4.95 4.88
86 38.2 46.6 52.1 51.5 43.3 52.6 52.6 52.0 83 33.9 42.2 49.8 51.5 38.0 47.2 52.6 52.0
80 29.5 37.8 45.4 48.7 32.6 41.9 50.3 52.0 77 25.1 33.5 41.1 44.4 27.3 36.5 44.9 46.7 74 20.7 29.1 36.7 40.0 21.9 31.1 39.5 41.3
71 -- 24.7 32.3 35.6 -- 25.8 34.2 35.9 68 -- 20.3 27.9 31.2 -- 20.4 28.8 30.6
NET CAP.
MBH 57.6 53.3 49.5 49.3 58.4 54.1 50.2 50.0
INPUT kW 5.52 5.43 5.34 5.27 5.69 5.60 5.51 5.43
86 37.1 45.3 49.5 49.3 42.6 51.8 50.2 50.0 83 32.7 40.9 48.4 49.3 37.2 46.4 50.2 50.0 80 28.4 36.6 44.1 46.4 31.8 41.1 49.1 50.0
MBH 1
77 24.0 32.2 39.8 42.1 26.5 35.7 43.7 44.7 74 19.6 27.8 35.4 37.7 21.1 30.3 38.3 39.3 71 -- 23.4 31.0 33.3 -- 25.0 33.0 33.9
68 -- 19.1 26.6 29.0 -- 19.6 27.6 28.6
NET CAP.
MBH 54.6 50.6 46.9 47.1 55.7 51.6 47.9 48.0
INPUT kW 6.07 5.97 5.89 5.81 6.26 6.16 6.07 5.99
86 36.0 44.0 46.9 47.1 41.8 51.0 47.9 48.0 83 31.6 39.7 46.9 47.1 36.4 45.6 47.9 48.0 80 27.2 35.3 42.9 44.2 31.1 40.3 47.9 48.0
MBH 1
77 22.8 30.9 38.5 39.8 25.7 34.9 42.5 42.7 74 18.5 26.5 34.1 35.4 20.3 29.5 37.1 37.3 71 -- 22.2 29.7 31.0 -- 24.2 31.8 31.9
68 -- 17.8 25.4 26.7 -- 18.8 26.4 26.6
NET CAP.
MBH 51.6 47.9 44.4 44.9 52.9 49.1 45.5 46.0
INPUT kW 6.62 6.51 6.43 6.35 6.82 6.71 6.62 6.54
86 34.8 42.8 44.4 44.9 41.0 50.2 45.5 46.0
83 30.5 38.4 45.5 44.9 35.6 44.8 45.5 46.0 80 26.1 34.0 41.6 41.9 30.3 39.5 46.7 46.0 77 21.7 29.6 37.2 37.5 24.9 34.1 41.3 40.7
74 17.3 25.3 32.8 33.1 19.6 28.7 35.9 35.3 71 -- 20.9 28.4 28.7 -- 23.4 30.6 29.9 68 -- 16.5 24.1 24.4 -- 18.0 25.2 24.6

MODEL #
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00 1.10
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
SIDE SUPPLY AIR PERFORMANCE - 208 VOLT
HI - 984 443 894 422 751 390 608 358 -
MED 994 333 947 321 901 309 854 297 774 280 695 263 615 246 -
LOW 743 243 700 235 657 226 614 218 -
HI - 929 491 809 473 688 454 -
MED - 999 353 944 338 865 319 785 299 706 280 -
LOW 998 372 906 333 813 294 721 255 651 241 -
HI - 886 398 805 380 676 351 547 322 -
MED 895 300 853 289 811 278 769 267 697 252 625 237 554 221 -
LOW 669 219 630 211 591 204 553 196 -
HI - 836 442 728 425 620 409 -
MED - 899 318 850 304 778 287 707 269 635 252 -
LOW 898 335 815 300 732 265 649 230 586 217 -
DNP (Cooling/ · Heating)

MODEL #
MODE (COOLING / HEATING) CFM
DNP
.20 .30 .40 .50 .60 .70 .80 .90 1.0
WATTS
030 COOLING (FACTORY SETTING) 1000 248 298 325 365 385 411 470 498 500
030 COOLING (FIELD SETTING) 1250 342 385 431 474 510 562 614 657 694
030 HEATING (2 TUBE) (FACTORY SETTING) 850 169 217 237 278 302 334 374 401 431
030 HEATING (3 TUBE) (FACTORY SETTING) 1100 300 338 378 416 447 493 539 576 609
036 COOLING (FACTORY SETTING) 1200 354 396 436 511 548 599 641 677 721
036 COOLING (FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826
036 HEATING (2 TUBE) (FACTORY SETTING) 700 207 231 254 298 320 349 - - -
036 HEATING (3 TUBE) (FACTORY SETTING) 1250 383 432 478 543 581 628 - - -
036 HEATING (4 TUBE) (FACTORY SETTING) 1350 442 503 563 606 648 685 - - -
042 COOLING (FACTORY SETTING) 1350 410 457 504 575 646 687 729 780 830
042 COOLING (FIELD SETTING) 1500 450 500 553 641 729 798 830 872 939
042 HEATING (3 TUBE) (FACTORY SETTING) 1500 450 500 553 641 729 798 830 872 939
042 HEATING (4 TUBE) (FACTORY SETTING) 1275 388 433 478 545 612 652 691 739 787
048 COOLING (FACTORY SETTING) 1400 427 476 525 599 673 716 759 812 865
048 COOLING (FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030
048 HEATING (3 TUBE) (FACTORY SETTING) 1525 458 511 564 654 744 814 - - -
048 HEATING (4 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -
048 HEATING (5 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -
060 COOLING (FACTORY SETTING) 1500 439 526 559 636 716 748 816 884 941
060 COOLING (FIELD SETTING) 1800 659 809 814 946 1001 1053 1124 1176 1180
060 HEATING (3 TUBE) (FACTORY SETTING) 1500 439 526 559 636 716 748 816 884 941
060 HEATING (4 TUBE) (FACTORY SETTING) 1700 576 757 788 872 929 979 1000 1121 1188
060 HEATING (5 TUBE) (FACTORY SETTING) 1700 576 757 788 872 929 979 1000 1121 1188

MODEL #
MODE (COOLING / HEATING) CFM
DNP
.20 .30 .40 .50 .60 .70 .80 .90 1.0
WATTS
030 COOLING (FACTORY SETTING) 1000 248 298 325 365 385 411 470 498 500
030 COOLING (FIELD SETTING) 1250 342 385 431 474 510 562 614 657 694
030 HEATING (2 TUBE) (FACTORY SETTING) 850 169 217 237 278 302 334 374 401 431
030 HEATING (3 TUBE) (FACTORY SETTING) 1100 300 338 378 416 447 493 539 576 609
036 COOLING (FACTORY SETTING) 1200 354 396 436 511 548 599 641 677 721
036 COOLING (FIELD SETTING) 1350 442 503 563 606 648 685 721 774 826
036 HEATING (2 TUBE) (FACTORY SETTING) 700 207 231 254 298 320 349 - - -
036 HEATING (3 TUBE) (FACTORY SETTING) 1250 383 432 478 543 581 628 - - -
036 HEATING (4 TUBE) (FACTORY SETTING) 1350 442 503 563 606 648 685 - - -
042 COOLING (FACTORY SETTING) 1350 410 457 504 575 646 687 729 780 830
042 COOLING (FIELD SETTING) 1500 450 500 553 641 729 798 830 872 939
042 HEATING (3 TUBE) (FACTORY SETTING) 1500 450 500 553 641 729 798 830 872 939
042 HEATING (4 TUBE) (FACTORY SETTING) 1275 388 433 478 545 612 652 691 739 787
048 COOLING (FACTORY SETTING) 1400 427 476 525 599 673 716 759 812 865
048 COOLING (FIELD SETTING) 1600 476 532 587 687 786 872 958 994 1030
048 HEATING (3 TUBE) (FACTORY SETTING) 1525 458 511 564 654 744 814 - - -
048 HEATING (4 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -
048 HEATING (5 TUBE) (FACTORY SETTING) 1600 476 532 587 687 786 872 - - -
060 COOLING (FACTORY SETTING) 1500 345 487 554 569 654 745 784 835 896
060 COOLING (FIELD SETTING) 1800 567 663 794 917 948 1015 1048 1155 1175
060 HEATING (3 TUBE) (FACTORY SETTING) 1500 345 487 554 569 654 745 784 835 896
060 HEATING (4 TUBE) (FACTORY SETTING) 1700 504 603 698 771 831 1043 1102 1155 1202
060 HEATING (5 TUBE) (FACTORY SETTING) 1700 504 603 698 771 831 1043 1102 1155 1202

DESCRIPTION
CFM
500 600 700 800 900 1,000 1,100 1,200 1,300 1,400 1,500 1,600
WET EVAPORATOR COIL.01 .01 .01 .02 .03 .04 .05 .06 .07 .08 .09 .09
ECONOMIZER1.00 .00 .00 .01 .02 .03 .04 .05 .06
FILTER FRAME KIT.01 .02 .04 .06 .08 .10 .13 .16 .17 .18 .19 .20
DESCRIPTION
CFM
1,100 1,200 1,300 1,400 1,500 1,600 1,700 1,800 1,900 2,000
WET EVAPORATOR COIL.02 .03 .04 .05 .06 .07 .07 .08 .09 .09
ECONOMIZER1.02 .02 .02 .03 .03 .04 .04 .04 .05 .05
FILTER FRAME KIT.04 .04 .05 .05 .06 .07 .08 .09 .10 .11
** ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.
R
G
G
Y Y
24 VOLT TRANSFORMER
W
W
PROGRAMMABLE THERMOSTAT ONLY
FIGURE 3 - FIELD WIRING DIAGRAM CONTROL WIRING

TABLE 14: ELECTRICAL DATA
VOLTAGE LIMITATIONS1 COMPRESSOR COND.
MAX. FUSE
MAX. HACR BREAKER
AIR BLOWER
MINIMUM
UNIT POWER FACTOR
MODEL
DNP POWER SUPPLY
FAN MOTOR,
CIRCUIT AMPACITY
TRANSFORMER
SIZE (VA) MIN. MAX. RLA LRA
SIZE, AMPS 2
FLA
MOTOR
SIZE, AMPS
FLA
024 208/230-1-60 187 253 8.0 53.5 1.1 2.6 16.5 20 20 0.96 40
030 208/230-1-60 187 253 13.6 67 1.1 6.8 24.9 35 35 0.96 40
030 208/230-3-60 187 253 8.6 55 1.1 6.8 18.7 25 25 0.96 75
030 460-3-60 432 504 5.7 39 0.6 6.8 13.4 20 20 0.96 75
036 208/230-1-60 187 253 17.2 88 1.1 6.8 29.4 45 45 0.96 40
036 208/230-3-60 187 253 11.4 77 1.1 6.8 22.2 30 30 0.96 75
036 460-3-60 432 504 5.7 39 0.6 6.8 14.8 20 20 0.96 75
036 575-3-60 540 630 4.7 31 0.6 6.8 13.3 20 20 0.96 75
042 208/230-1-60 187 253 20 104 1.3 9.1 35.4 50 50 0.96 40
042 208/230-3-60 187 253 13.9 88 1.3 9.1 27.8 40 40 0.96 75
042 460-3-60 432 504 6.4 44 0.7 9.1 18.5 25 25 0.96 75
042 575-3-60 540 630 5.4 34 0.6 9.1 16.8 25 25 0.96 75
048 208/230-1-60 187 253 23.4 126 1.9 9.1 39.5 60 60 0.96 40
048 208/230-3-60 187 253 13 93 1.9 9.1 26.5 35 35 0.96 75
048 460-3-60 432 504 6.4 46.5 1.0 9.1 18.4 25 25 0.96 75
048 575-3-60 540 630 5.1 37.2 0.8 9.1 17.3 25 25 0.96 75
060 208/230-1-60 187 253 25 150 2.8 9.1 43.2 60 60 0.96 40
060 208/230-3-60 187 253 17.3 123 2.8 9.1 33.5 45 45 0.96 75
060 460-3-60 432 504 8.4 70 2.8 9.1 22.6 30 30 0.96 75
060 575-3-60 540 630 7.0 53 2.8 9.1 21.2 30 30 0.96 75

BLOWERSERVICE
ACCESSCOMPARTMENT PANEL GASSUPPLY1-1/4"DIA. HOLE(1/2"NPTI CONNECTION)
C ONDENSERCOIL
UNITCONDENSATE CONNECTION3/4"NPTI (TRAPRECOMMENDED)
B H IGHVOLTAGE CONN.1-3/8"DIA. KNOCKOUT
HIGHVOLTAGE CONN.7/8"DIA. KNOCKOUT
REFRIGERANT CONNECTIONS
GASSUPPLY1-1/4"DIA. KNOCKOUT(1/2"NPTI CONNECTION)
COMBUSTIONAIR INLETLOUVERS
FRONT
LOWVOLTAGECONN. 1-3/8"DIA.KNOCKOUT X7/8"HOLE
11 12-3/4 49-1/8
S ERVICEACCESS COMPARTMENTPANEL
(OVERALL)
( OVERALL)
All dimensions are in inches. They are subject to change with- out notice. Certified dimensions will be provided upon request.
TABLE 15: UNIT DIMENSIONS FRONT
TABLE 16: UNIT MINIMUM CLEARANCES 1 2
UNIT SIZE
CLEARANCES
“A” “B”
FRONT 36”
024, 030, 036 33-1/2 18-1/4
042, 048, 060 41-1/2 23-1/8
LEFT SIDE (Filter-Access) 24”
BELOW UNIT 3
ABOVE UNIT 4
36” (For Condenser Air Discharge)

8-7/8 11-7/8 19-1/4 HIGH VOLTAGE CONN. 1-3/32" DIA. KNOCKOUT FRONT
LOW VOLTAGE CONN.
CONDENSATE DRAIN 3/4"' NPTI
FIGURE 6 - UNIT DIMENSIONS - FRONT & BOTTOM

!
! " "
! " "
!

TABLE 17: UNIT WEIGHTS AND CENTER OF GRAVITY
OPERATING
CORNER WEIGHTS
ROOF CURB
UNIT SIZE
WEIGHT
WEIGHT
(location, lbs.) ECONOMIZER
(lbs.)
(lbs.)
(lbs.)
(lbs.) “A” “B” “C” “D”
024, 030, 036 400 395 100 96 98 101 40 8” - 70 14” - 75 042, 048, 060 475 470 133 130 102 104
CENTER OF
FRONT
GRAVITY
OF UNIT
"C"
"B"
FIGURE 11 - UNIT CENTER OF GRAVITY
49-1/8 25 25 · 47-1/4

% # & '
# $
#
% # & '
& ' &
& ( " !
!


10G
15H
17H
100/BK
035-18578D000 REV. C BEFORE SERVICING THIS UNIT CAUTION - OPEN ALL DISCONNECTS
L K J H G F E D C B A
230V PRI
COMPR
MOTOR OD FAN
(SEE NOTE 5) 805/BL
ASCT
75 VA SEC 24V
107/PR
HSP
PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.
R
(OPTIONAL ACCESSORIES - SEE NOTE 5)
CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL
AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
110/BK
BLK
BRN
PRP
FS HP LP
201/BR
101/BK
103/BR
102/Y
110/BK
MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1. 6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION
7 2 802/BK 803/BK 804/BK
MOTOR ID FAN
801/BL (SEE NOTE 5)
BLU
BLU
806/BR
ID MOTOR CONTROLLER
P3
104/R
B LR A
807/BL
1 P2
S3 S2
GAS
VALVE
M2-1
240V/BK
240V/PR
T1
T2
T2
T1
M1-1
M1-2
M1
PRP
BLK
108/PR
GRN
800/Y
230-1-60 MOTOR DRAFT
S5/P5
211/PR PS
LR
LUG GND
P4/S4
108/PR
208/230-1-60 POWER SUPPLY
SEE DETAIL "A"
COOL/BLU
W1/WHT
NOTES:
HEAT/BLK
C2/BRN
C1/BRN
Y1/YEL
R/RED
214/BR
224/R
90 SEC 60 SEC
180 SEC 120 SEC
LS 213/R ALS 205/R
SETTING FACTORY
220/O
COOL/BLU
224/R
M2
221/BR
201/BR
200/R
S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE CN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD
S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROL S3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE
S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL
HEAT/BK
1000 (ARI RATING) TB2-A -030
1250 TB2-B
1200 (ARI RATING) TB2-A
1350 TB2-B
1350 (ARI RATING) TB2-A -042
1500 TB2-B
1400 (ARI RATING) TB2-A
1600 TB2-B
BOARD CONTROL
203/BR
UNUSED
MOTOR
LEADS
XFMR
210/BL
208/PR
207/Y
209/BK
206/R
202/Y
DI
NEUTRAL
INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*
COOL
CN1
P1
(CFM) AIRFLOW FOR COOLING
COMBUSTION BLOWER POSTPURGE: 5 SEC
INDOOR BLOWER COOL ON DELAY: 3 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
* BLACK SQUARE INDICATES SWITCH POSITION
"SPEED" CONNECTIONS FOR COOLING BLOWER SEE TABLE 1
HUM
EAC
HEAT
6 5 3 2 1 4
N
N
S
204/O RS
CONTROL BOARD SETTINGS:
213/R
ON DELAY
R/RED
Y
UNIT SIZE
OFF
TB2
B
TB1
G
Y
W
R
CONTROL SETPOINT (DEG F) UNIT SIZE DEVICE
+/- CLOSE +/- OPEN
030 2 TUBE LS 140 110 6 9
030 3 TUBE LS 160 130 6 9
036 2 TUBE LS 140 110 6 9
LS 160 130 6 9
036 4 TUBE LS 160 130 6 9
042 3 TUBE LS 140 110 6 9
042 4 TUBE LS 140 110 6 9
048 3 TUBE LS 150 120 6 9
048 4 TUBE LS 175 145 6 9
048 5 TUBE LS 160 130 6 9
ID FAN
MOTOR
TEMPERATURE CONTROLS
CONNECTION DIAGRAM ELEMENTARY DIAGRAM COOLING UNIT WITH GAS HEAT
COOL
W HEAT
ON
Y
OFF
RS
ALS
RS
ALS
RS
ALS
RS
ALS
RS
ALS
RS
ALS
RS
ALS
RS
ALS
RS
ALS
RS
ALS
OPEN @ 7 PSIG LP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)
ON CONTROL BOARD, 24-1-60, 18VA MAX EAC ELECTRONIC AIR CLEANER RELAY OUTPUT
ACCESSORY) OPENS @ 380 PSIG HP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE F FS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)
BOARD, 24-1-60, 18VA MAX HUM HUMIDIFIER RELAY OUTPUT ON CONTROL
LR LOCK OUT RELAY (OPTIONAL ACCESSORY)
ROOM THERMOSTAT 24V CONNECTIONS
G
M1 CONTACTOR, COMPR & OD FAN
M2 CONTACTOR, DRAFT INDUCER MOTOR
.193 IWC NOM (.33 IWC MAX) PS PRESSURE SWITCH - MAKES @
FIELD WIRING OPTIONAL WIRING AND DEVICES
CCH CRANKASE HEATER (OPTIONAL)
T1
(OPTIONAL ACCESSORY) ASCT ANTI-SHORT CYCLE TIMER
HSP HOT SURFACE TO PILOT
T1 TRANSFORMER, 24V, 40 VA
MOTOR "SPEED" CONNECTIONS TB2 TERMINAL BLOCK, 24V, ID
FACTORY WIRING AND DEVICES
THERMOSTAT ROOM
S/P CONFIGURATION
D/P CONFIGURATION
ALS AUXILARY LIMIT SWITCH
TB1 ON CONTROL BOARD
GND/GRN
240V/PRP
240V/BLK
OPTIONAL CCH
BLK CCH
BLK
BLK CCH
BLK
T2 L2 M1-2
DETAIL "A"
COMPR COMPRESSOR
LS LIMIT SWITCH
RS ROLLOUT SWITCH
R
LEGEND:
S5
S4 ID MOTOR CONTROLLER
8 7 6 5 4 3 2 1
HSP
YEL Y1/
15 14 13 12 11 10 9
224/R
220/O
221/BR
214/BR
201/BR
200/R
CONTROL BOX
213/R 224/R 214/BR
/BLU COOL
PRP
BLK
101/BK
GRN
BLU BLK
CLEAR
BLU
R/RED
102/Y
104/R
BLK
UNUSED
MOTOR
LEADS
XFMR
BRN C2/
201/BR 200/R
DI
DRAFT
MOTOR
/BLK HEAT
100/BK 107/PR
PRP
WHT W1/
C2/BRN
HUM
EAC
N
N
204/O
209/BK
BRN C1/
T1
SEC
2 S
207/Y
210/BL
802/BK
800/Y 202/Y
CLEAR
BLU
BLU
BLK
T2
T1
T2
T1
COOL
HEAT
CN1
206/R
CCH BLK
BLK BRN PRP
OUTDOOR
MOTOR
M1
CONTROL BOARD
FAN
B
M2
B
(SEE NOTE 5) LR
7 B
GAS HEAT SECTION
S3
(SEE NOTE 5) 202/Y
Y1/YEL
W1/WHT
208/PR
GAS VALVE
211/PR
210/BL
209/BK
221/BR
203/BR
103/BR
PRP
207/Y
804/BK
802/BK
804/BK
220/O
TB2
800/Y
801/BL
FS 803/BK
HP 803/BK
LP 805/BL
HERM RC1/RC2
B
DELAY
Y
G
Y
W
R
S2
TB1
240V/PRP
108/PR
240V/BLK
110/BK
108/PR
107/PR
110/BK
100/BK
"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2
801/BL 805/BL
806/BR
213/R
204/O
206/R
211/PR
BRN
FAN
ALS 205/R
213/R
205/R
208/PR
104/R
R/RED
G/GRA
103/BR 101/BK
S C
LUG GND
203/BR
202/Y
(SEE NOTE 5) ASCT
COMPR
R
102/Y
807/BL
RS
LS
PS
FIGURE 15 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-1-60 POWER SUPPLY)



10G
15H
17H
100/BK
035-18845D000 REV.C BEFORE SERVICING THIS UNIT CAUTION - OPEN ALL DISCONNECTS
L K J H G F E D C B A
(SEE NOTE 5) 805/BL
ASCT
230V PRI
CB 75 VA SEC 24V
COMPR
MOTOR OD FAN
107/PR
PRESENT, WIRE 202/Y IS CONNECTED TO M1 COIL. ONLY IS PRESENT WIRE 202/Y IS CONNECTED TO ASCT-3. IF NEITHER LR OR ASCT ARE IF LR ONLY IS PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO M1 COIL. IF ASCT 5. IF BOTH LR AND ASCT ARE PRESENT, WIRE 801/BL AND 805/BL ARE CONNECTED TO ASCT-3.
(OPTIONAL ACCESSORIES - SEE NOTE 5)
CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT. 1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR NATIONAL
AFTER SERVICING. CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY PROPER OPERATION IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600V WIRE OR EQUIVALENT IF ANY OF THE WIRE AS SUPPLIED WITH THIS UNIT MUST BE REMOVED, CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. 2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
110/BK
BLK
BRN
PRP
FS HP LP
201/BR
107/PR
121/BK
123/BL
126/Y
110/BK
MOVE '108/PR' WIRE FROM 230V TO 208V ON TRANFORMER T1. 6. UNIT FACTORY WIRED FOR 230 VOLT OPERATION. FOR 208 VOLT OPERATION
MOTOR ID FAN
RC2
801/BL (SEE NOTE 5)
200/R
BLU
BLU
105/BL
806/BR
ID MOTOR CONTROLLER
3.2 AMP
P3
B LR A
S3 S2
807/BL
M2-2
M2-1
240V/PRP
1 P2
GAS
VALVE
T1
T2
T3
T2
T1
M1-1
M1-2
M1-3
M1
PRP
BLK
GRN
108/PR
211/PR PS
800/Y
230-1-60 MOTOR DRAFT
LR
LUG GND
P4/S4
108/PR
COOL/BLU
W1/WHT
NOTES:
208/230-3-60 POWER SUPPLY
HEAT/BLK
C2/BRN
C1/BRN
Y1/YEL
R/RED
214/BR
224/R
90 SEC 60 SEC
180 SEC 120 SEC
LS 213/R ALS 205/R
SETTING FACTORY
224/R
220/O
M2
221/BR
S4/P4 SOCKET/PLUG CONNECTION, 24V, 16 PIN ON ID MOTOR CONTROL S3/P3 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE
S5/P5 SOCKET/PLUG CONNECTION, 230V, 5 PIN ON ID MOTOR CONTROL
COOL/BLU
201/BR
212/R
S2/P2 SOCKET/PLUG CONNECTION, 24V, 4 PIN ON GAS VALVE CN1/P1 SOCKET/PLUG CONNECTION, 24V, 6 PIN ON CONTROL BOARD
UNUSED
MOTOR
LEADS
210/BL
208/PR
209/BK
COOL/BLU TO: WIRE CONNECT
203/BR
202/Y
DI
XFMR
207/Y
206/R
1000 (ARI RATING) TB2-A -030
1250 TB2-B
1200 (ARI RATING) TB2-A
1350 TB2-B
1350 (ARI RATING) TB2-A -042
1500 TB2-B
1400 (ARI RATING) TB2-A
1600 TB2-B
INDOOR BLOWER HEAT OFF DELAY: (SEE RIGHT)*
NEUTRAL
* BLACK SQUARE INDICATES SWITCH POSITION
COOL
HEAT
CN1
P1
FOR COOLING AIRFLOW BLOWER CONNECTIONS TABLE 1
COMBUSTION BLOWER POSTPURGE: 5 SEC
INDOOR BLOWER COOL ON DELAY: 3 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
"SPEED" CONNECTIONS FOR COOLING BLOWER SEE TABLE 1
HUM
EAC
N
N
6 5 3 2 1 4
S
204/O RS
CONTROL BOARD SETTINGS:
ON DELAY
R/RED
Y
213/R
UNIT SIZE
OFF
TB2
B
TB1
G
Y
W
R
ID FAN
MOTOR
CONNECTION DIAGRAM ELEMENTARY DIAGRAM COOLING UNIT WITH GAS HEAT
OPEN @ 7 PSIG LP LOW PRESSURE SWITCH (OPTIONAL ACCESSORY)
COOL
OFF
W HEAT
ACCESSORY) OPENS @ 380 PSIG HP HIGH PRESSURE SWITCH (OPTIONAL OPEN @ 26 DEGREE F FS FREEZESTAT SWITCH (OPTIONAL ACCESSORY)
Y
ON CONTROL BOARD, 24-1-60, 18VA MAX EAC ELECTRONIC AIR CLEANER RELAY OUTPUT
BOARD, 24-1-60, 18VA MAX HUM HUMIDIFIER RELAY OUTPUT ON CONTROL
+/- CLOSE +/- OPEN
030 2 TUBE LS 140 110 6 9
030 3 TUBE LS 160 130 6 9
036 2 TUBE LS 140 110 6 9
LS 160 130 6 9
036 4 TUBE LS 160 130 6 9
042 3 TUBE LS 140 110 6 9
042 4 TUBE LS 140 110 6 9
048 3 TUBE LS 150 120 6 9
048 4 TUBE LS 175 145 6 9
048 5 TUBE LS 160 130 6 9
IDENTIFIED TERMINAL ON CAPACITOR
ROOM THERMOSTAT 24V CONNECTIONS
CONTROL SETPOINT (DEG F) UNIT SIZE DEVICE
M1 CONTACTOR, COMPR & OD FAN
M2 CONTACTOR, DRAFT INDUCER MOTOR
.193 IWC NOM (.33 IWC MAX) PS PRESSURE SWITCH - MAKES @
(OPTIONAL ACCESSORY) ASCT ANTI-SHORT CYCLE TIMER
MOTOR "SPEED" CONNECTIONS TB2 TERMINAL BLOCK, 24V, ID
FACTORY WIRING AND DEVICES
OPTIONAL WIRING AND DEVICES
G
TEMPERATURE CONTROLS
ALS AUXILARY LIMIT SWITCH
HSP HOT SURFACE TO PILOT
T1 TRANSFORMER, 24V, 75 VA
TB1 ON CONTROL BOARD
CB CIRCUIT BREAKER
THERMOSTAT ROOM
COMPR COMPRESSOR
RS ROLLOUT SWITCH
GND/GRN
240V/PRP
240V/BLK
ALS
ALS
ALS
ALS
ALS
ALS
ALS
ALS
ALS
ALS
LS LIMIT SWITCH
FIELD WIRING
R
RS
RS
RS
RS
RS
RS
RS
RS
RS
RS
LEGEND:
036 3 TUBE
S5
S4 ID MOTOR CONTROLLER
8 7 6 5 4 3 2 1
15 14 13 12 11 10 9
224/R
220/O
221/BR
214/BR
C1/BRN
201/BR
212/R
HSP
YEL Y1/
213/R 214/BR
CONTROL BOX
126/Y
105/BL
123/BL
121/BK
BLU BLK
BLU
/BLU COOL
BK
GRN
CLEAR
R/RED
PRP
BLK
UNUSED
MOTOR
LEADS
XFMR
BRN C2/
201/BR 200/R
DI
DRAFT
MOTOR
/BLK HEAT
100/BK 107/PR
209/BK
PRP
WHT W1/
C2/BRN
HUM
EAC
N
N
204/O
BRN C1/
T1
SEC
2 S
207/Y
210/BL
802/BK
800/Y 202/Y
CLEAR
T2
T1
T3
T2
T1
COOL
HEAT
CN1
206/R
BLU
BLU
BLK BRN PRP
OUTDOOR
MOTOR
CONTROL BOARD
FAN
B
M2
M1
(SEE NOTE 5) LR
7 B
GAS HEAT SECTION
S3
Y1/YEL
W1/WHT
208/PR
GAS VALVE
211/PR
207/Y
210/BL
209/BK
804/BK
802/BK
804/BK
221/BR
220/O
B
FS 803/BK
HP 803/BK
LP 805/BL
TB2
B
800/Y
801/BL
S2
DELAY
Y
TB1
G
Y
W
R
100/BK
110/BK
105/BL
240V/PRP
108/PR
240V/BLK
110/BK
108/PR
(SEE NOTE 5) 202/Y 107/PR
"SPEED" CONNECTIONS COOLING BLOWER FOR HEATING AND SEE TABLES 1 AND 2
801/BL 805/BL
806/BR
213/R
204/O
206/R
208/PR
211/PR
BRN
PRP
R/RED
ALS 205/R
213/R
205/R
123/BL 121/BK
203/BR
203/BR
202/Y
224/R
(SEE NOTE 5) ASCT
LUG GND
RC2
G/GRA
200/R
CB
COMPR
126/Y
212/R
807/BL
RS
LS
PS
FIGURE 17 - TYPICAL WIRING DIAGRAM D*NP 030-048 (208/230-3-60 POWER SUPPLY)







Open all disconnects before servicing this unit.
ALS ASCT
AUXILLARY LIMIT SWITCH ANTI-SHORT CYCLE TIMER (OPTIONAL ACCESSORY) COMPRESSOR
ELECTRIC AIR CLEANER RELAY OUTPUT
ON CONTROL BOARD, 24-1-60, 18VA MAX. FREEZESTAT SWITCH (OPTIONAL ACCESSORY) OPEN @ 250 F HIGH PRESSURE SWITCH (OPTIONAL ACCESSORY) OPENS @ 380 PSIG HOT SURFACE TO PILOT HUMIDIFER RELAY OUTPUT ON CONTROL BOARD, 24-1-60, 18VA MAX. LOW PRESSURE SWITCH (OPTIONAL ACCESSORY) OPEN @ 7 PSIG LOCK OUT RELAY (OPTIONAL ACCESSORY) LIMIT SWITCH CONTACTOR, COMPR. & O.D.FAN CONTACTOR, DRAFT INDUCER MOTOR PRESSURE SWITCH MAKES @ .193 IWC NOM. (.33 IWC MAX.) COMPR. START & OUTDOOR FAN RUN CAPACITOR ROLL OUT SWITCH TRANSFORMER, 24V, 40VA TRANSFORMER, 480/240 VOLT TERMINAL BLOCK, 24V, I.D. MOTOR "SPEED" CONNECTION IDENTIFIED TERMINAL ON CAPACITOR
HP
HSP HUM
LP
LR LS M1 M2 PS
RC1/RC2 RS T1 T2 TB2
ROOM THERMOSTAT 24V CONNECTIONS TB1 ON CONTROL BOARD FACTORY WIRING AND DEVICES OPTIONAL WIRING AND DEVICES
DNP LEGEND WIRING DIA.

without modification to building structure, duct work and base unit. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards, with 3/4” NPTI copper, ridged mount connection.
Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s DNP is a unit that gives you the flexibility and choices you need in today’s market. These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The gas fired heaters have aluminized steel tubular heat exchangers and hot surface to pilot ignition. They are avail- able in natural gas with field conversion to propane.
Fan shall be direct drive, multi-speed design. Job site selected (BHP) brake horsepower shall not exceed the motors nameplate horsepower rating. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bear- ings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be “Slip Track” (slide-out) design for easy removal and cleaning.
Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heating units, designed for outdoor mounted installation. For SEER ratings, refer to technical literature. They shall have built in, equal size, field convertible duct connections for down discharge supply/return or horizontal discharge supply/return. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility cer- tified to ISO 9001 standards, and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. The heating performance shall be rated to DOE and GAMA test procedures. Units shall be CSA listed and classi- fied to ANSI Z21.47/CAN/CSA 2.3 standards and UL 1995/ CAN/CSA No. 236-M90 conditions.
The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.
Compressors:
a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or - 10% of the unit nameplate voltage.
Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTM- B117 standards. The unit top shall be a single piece “Water Shed” design, with drip edges and no-seam corners to pro- vide optimum water integrity. Unit shall have a rigidly mounted condenser coil guard to provide protection from objects and personnel after installation. Indoor blower section shall be insulated with up to 3/4” thick, aluminum, foil faced insulation, fastened to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily remov- able for servicing and maintenance, with built-in lift handles. Unit shall be built on a formed, “Super-Structure” design base pan, with embossments at critical points to add strength, rigidity and aid in minimizing sound. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, for truck access and proper sealing on roof curb applications. Base rails shall be removable, when required, to lower unit height. Filters shall be furnished and be accessible through a removable access door, sealed air- tight. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams
b. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally iso- lated on a dedicated, independent mounting.
a. Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.
b. Evaporator coil shall be of the direct expansion, blow through design, while condenser coil shall be draw through design.
a. Shall include independent thermal expansion devices (TXV).
b. Shall include filter/strainer to eliminate any foreign matter.

ELECTRICAL REQUIREMENTS
Unit shall be capable of starting and running at 125º F out- door temperature, exceeding maximum load criteria ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 45º F outdoor tempera- ture. Accessory low ambient kit shall be available for opera- tion to 0º F.
All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.



Subject to change without notice. Printed in U.S.A. 036-21366-007-A-1205 Copyright © 2005 by Unitary Products Group. All rights reserved. Supersedes: 036-21366-006-A-1005